The Indoor Unit Installation; Remote Controller Installation - LG LT-C1260CL Service Manual

Ceiling cassette air conditioner
Table of Contents

Advertisement

3. The Indoor Unit Installation

Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
• The following parts is option.
Hanging Bolt
- W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
CAUTION
• Tighten the nut and bolt to prevent unit falling.

4. Remote Controller Installation

• Although the room temperature sensor is in the indoor unit, the remote controller should be installed
in such places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
• Select control position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment, television set, etc.)
• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
Keep the length of the bolt
from the bracket to 40mm
Flat washer for M10
(accessory)
Ceiling board
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Adjust the same height
–15–
Ceiling
Air Conditioner body
Paper model
for installation
• Drill the piping hole on the wall slightly tilted to the
outdoor side using a Ø 70 hole-core drill.
Indoor
Ceiling board
Set screw of
paper model (4 pieces)
Open the ceiling board
along the outer edge of the
paper model
Wall
Outdoor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lt-c1262hlLt-c1260hl