KB Electronics KBDA-24D Installation And Operation Manual page 37

K4 series. adjustable frequency drives for 3-phase ac motor nema-4x / ip-65
Table of Contents

Advertisement

FUNCTION GROUP 8 – MULTI-FUNCTION OUTPUT RELAYS AND
OUTPUT SIGNAL OPERATION (IODA OPTION BOARD REQUIRED)
Function
No.
Description
Multi-Function Output Relay 1
8.00*
(Terms. 23 – 25)
Multi-Function Output Relay 2
8.01*
(Terms. 26 – 28)
Multi-Function Open Collector Output 1
8.02*
(Terms. 11, 12)
Multi-Function Open Collector Output 2
8.03*
(Terms. 13, 14)
8.04*
Frequency Set Point (Hz)
8.05*
Frequency Bandwidth (± Hz)
Analog Output 1 Mode (Terms. 15, 16)
8.06*
(0 – 5 VDC)
8.07*
Analog Output 1 Gain (%)
Analog Output 2 Mode (Terms. 17, 18)
8.08*
(See Function No. 8.09)
8.09*
Analog Output 2 Type
8.10*
Analog Output 2 Gain (%)
Notes: (1) The Multi-Function Output Relays and Open Collector Outputs will change state due to all Faults and Recovered Faults. (2) The
relay will activate above the setting in 8.04 and deactivate below the setting of 8.04 – 8.05. (3) The relay will activate below the setting in
8.04 and deactivate above the setting of 8.04 + 8.05. (4) The Output Relay will change state when the I
Output 2 Type: For 0 – 5 VDC (code "0000"), set Jumpers J2 and J3, on the IODA, to the "VOLT" Position (factory setting). For 0 – 20 mA DC
(code "0001") or 4 – 20 mA DC (code "0002"), set Jumpers J2 and J3, on the IODA, to the "CUR" position.
*Functions which can only be changed while the drive is in the Stop Mode.
(5)
Range/Code
0000: Run
(1)
0001: Fault
0002: Target Frequency
(Function No. 8.04 ± Function No. 8.05)
0003: Frequency Threshold Level
(> Function No. 8.04 – Function No. 8.05)
0004: Frequency Threshold Level
(< Function No. 8.04 + Function No. 8.05)
0005: I 2 t or I•t Fault
0006: Load Loss (See Function No. 5.03)
0007: External Fault
(4)
0008: Motor Overload
0.00 – 240.0
0.00 – 30.00
0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0 – 200
0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0000: 0 – 5 VDC
0001: 0 – 20 mA DC
0002: 4 – 20 mA DC
0 – 200
Factory
Setting
0000
0001
(2)
(3)
0002
0004
0.00
1.00
0000
0000
0000
2
t or I•t Timer starts. (5) Analog
100
100
37