KB Electronics KBDA-24D Installation And Operation Manual page 32

K4 series. adjustable frequency drives for 3-phase ac motor nema-4x / ip-65
Table of Contents

Advertisement

KBDA PROGRAMMABLE FUNCTION SUMMARY LIST (REV. 100.1)
PROGRAMMABLE FUNCTION GROUPS
Function
Group No.
Description
0
Motor and Drive Parameters
1
Run/Stop Mode
2
Frequency Control
3
Drive Operating Parameters
4
Digital Display Modes
5
Onboard Multi-Function Output Relay Operating Mode
6
Drive Status and Reset
7
Multi-Function Input Terminals
8
Multi-Function Output Relays and Output Signal Operation
9
Analog Input Signal Operation
10
Communication Mode
11
Reserved Functions
Note: (1) IODA Option Board required. (2) DIAC Option Board required.
FUNCTION GROUP 0 – MOTOR AND DRIVE PARAMETERS
Function
No.
Description
0.00*
Rated Motor Frequency (Hz)
0.01*
Motor Nameplate Current (Amps)
0.02*
Motor Type
0.03*
Torque Mode
0.04*
GFCI Operation
0.05*
Motor Frequency (Hz)
0.06*
Motor Nameplate Voltage (% Drive Output)
Notes: (1) Factory Setting is the drive rated output current. See Table 3, on page 10. This function is used to enter the Motor Nameplate
Rated Current, which allows proper operation of the I 2 t Motor Overload Protection. (2) GFCI operation overrides the Switching Frequency set
by Function No. 3.15. (3) When the drive is set for 50 Hz motors (Function No. 0.00 set to "0001"), the Motor Frequency factory setting will
automatically reset to 50 Hz. (4) The Motor Frequency for standard 50 Hz or 60 Hz motors is set by Function No. 0.00. For custom motors
(e.g., 100 Hz) set Function No. 0.00 to "0002" and Function No. 0.05 to the Motor Nameplate Rated Frequency. (5) This function is used for
motors with non-standard nameplate rated voltage (e.g., 80 Volts AC). (6) The factory set output of the drive is 100% of the AC line input
voltage. In 60 Hz Mode (Function No. 0.00 set to "0000") the drive output will be 230 Volts, maximum, for 230 Volt motors and 460 Volts,
maximum, for 460 Volt Motors. In 50 Hz Mode (Function No. 0.00 set to "0001") the drive output will be 220 Volts, maximum, for 220 Volt
motors and 400 Volts, maximum, for 400 Volt Motors.
* Functions which can only be changed while the drive is in the Stop Mode.
32
(1)
(1)
(2)
(2)
(3), (4)
(1)
0000: 60 Hz
0001: 50 Hz
0002: Special (Set by Function No. 0.05)
0000: Inverter Duty, TEFC
0001: External Fan Cooled
0000: Constant Torque (Machinery)
0001: Variable Torque (HVAC)
0000: GFCI Operation Disabled
0001: GFCI Operation with Standard GFCI
0002: GFCI Operation with Sensitive GFCI
30 – 240
(5)
0 – 100.0
Range/Code
Factory
Setting
0000
(1)
0000
0000
0000
60, 50
(6)
100