5.10 Program Status

While a program is running the home display shows 3 values:
Top:
Measured temperature
Centre: Program setpoint (PSP)
Bottom: Power output percentage
To see more detail:
Press page  once to go to the program status page. The top and centre values from the
home page remain on the display. The lower half of the screen now shows:
Current program number (P10 and P25 only)
Current segment number
Time remaining for that segment
Further presses of the scroll  key while a program is running will reveal additional
information:
Status. This can be changed to Hold, Reset or Run by pressing up  or down .
Program setpoint (PSP)
Current Segment Type. Step and Call segments are instant, so are only flashed on the
screen, unless Holdback is operating on that segment.
Target Setpoint
Segment Rate
Cycles left
Program Time Left
Program hold with holdback
If a holdback value has been set (see "Programming") and the program goes into a hold
state, the green HLD indicator will flash, until the measured temperature catches up.
If while in this condition the program itself is put into hold by pressing the RUN/HLD button,
the "HLD" indicator will stop flashing and remain on with the "RUN" indicator. When the
program is started again by pressing the "RUN/HLD" button, the "HLD" indicator will flash
again if the measured temperature has not caught up with the program.
Programming note:
For P10 and P25 models you can create or change other programs while the current
program is running, go to operator Page 3.
5.11 Power Failure Recovery
If there is a power interruption to the controller during a program, when power is restored
the controller pauses the program, then ramps the temperature back up to the current
Program Setpoint (PSP) before continuing the program.
 Power fail during ramp segments: The ramp rate will be that of the current ramp
segment.
 Power fail during Dwell segments: The ramp rate will be that of the previous ramp
segment. If a previous ramp segment does not exist, then the dwell will continue at
the current measured temperature.