12. Installation Instruction

12.1 Select the Best Location

12.1.1
Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 2.5 m.
12.1.2
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Table A
Piping size
Capa-
Std.
city
Model
Lengt
W
h (m)
Gas Liquid
(HP)
MTZ16*** 1/2HP
Refer to installation manual at outdoor unit
TZ20***
3/4HP 9.52
mm
TZ25***
1.0HP
6.35
"
(3/8
)
mm
5
TZ35***
1.5HP
"
(1/4
)
TZ42*** 1.75HP 12.7
mm
TZ50***
2.0HP
"
(1/2
)
* Table "A" only applicable for single split connection.
* In case of connection to outdoor multi inverter, refer
to installation manual at outdoor unit.
Example: For TZ25***
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 25 g .... (10-7.5) m x
10 g/m = 25 g.
AMP Air Conditioning
Piping
Addi-
Min.
Max.
Length
Max
tional
Piping
Piping
for
Eleva-
Refri-
Length
Length
add.
tion (m)
gerant
(m)
(m)
gas
(g/m)
(m)
15
3
15
10
7.5
15
3
15
10
7.5
15
3
15
10
7.5
15
3
15
10
7.5
15
3
20
15
7.5
A
= (M / (2.5 × (LFL)
min
A
= Required minimum room area, in m
min
M
= Refrigerant charge amount in appliance, in kg
LFL = Lower flammable limit (0.306 kg/m
h
= Installation height of the appliance (1.8 m for
0
wall mounted)
12.1.3
Indoor/Outdoor Unit Installation
Diagram
P
p i
n i
g
i d
e r
t c
o i
n
(Front side)
Right
Right
Rear
Left
Right
Rear
bottom
Left bottom
50 mm
or more
(Left and right are identical)
Insulation of piping connections
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Attaching the remote control holder to the wall
Remote control holder fi xing screws 6
Remote
control 3
Floor
Indoor
A
min
2
(m
)
It is advisable to
avoid more than 2
blockage directions.
For better ventilation
& multiple-outdoor
installation, please
0.41
consult authorized
dealer/specialist.
0.53
0.68
0.83
This illustration is for explanation purposes only.
1.68
The indoor unit will actually face a different way.
42
www.ampair.co.uk | sales@ampair.co.uk
(5/4)
× h
))
0
t A
e t
t n
o i
n
n
t o
o t
b
e
n
d
WARNING
up drain hose
Flare connection only
at outside of building
Left
Installation parts you
should purchase ( )
Installation plate 1
Bushing-Sleeve ( )
Sleeve ( )
Putty ( )
(Gum Type Sealer)
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesn't break.
Vinyl tape (wide) ( )
Vinyl tape
• Apply after carrying
• To carry out the
Saddle
Remote control holder 5
Power supply cord
Connection cable
Liquid side piping
Gas side piping
Additional drain hose
2
2
3
)
out a drainage test.
drainage test,
remove the air filters
and pour water into
the heat exchanger.
(
)
(
)
(
)
(
)
(
)