3 Rack mounting

Install the recorder in an EIA standard 19-inch rack (Depth:
550 mm or more).
Note:
• Use four M5 × 12 screws (locally procured) to install the
recorder in a rack.
• The illustration on this page is schematic. Details of the
shape are omitted.
Installation procedure
Step 1
Remove the four rubber feet from the bottom of the
recorder using a flathead screwdriver.
Use a screwdriver to remove the screws holding the rubber feet.
Step 2
Place the provided rack mount brackets (WV-Q202:
option) on both sides of the recorder and fix them with
the rack mount bracket fixing screw (provided) (x6).
Secure them using the rack mount bracket fixing screw
(Provided with the rack mount bracket) (x4).
Tightening torque: 0.88 N·m ~ 1.08 N·m (0.65 lbf·ft ~ 0.80 lbf·ft)
Rack mount bracket fixing screws (M4×10 provided with the bracket)
Rack mount brackets (option)
Note:
• The rack mounting brackets has two types of screw
stoppers to adjust the position of the recorder on the
front side. Use them according to the installation.
Remove rubber feet
Step 3
Install the recorder in the rack by using four rack
mounting screws.
Secure using the rack mounting screws (x4).
Tightening torque: 2.0 N·m ~ 2.4 N·m (1.48 lbf·ft ~ 1.78 lbf·ft)
Rack mounting screws (M5 x 12, locally procured)
Important:
• When installing the recorder in the rack, make a space
of 1U (44 mm {1-23/32 inches}) above and below the
recorder for ventilation.
• Keep the temperature in the rack below +45 °C {113 °F}.
• It is recommended to install cooling fans or equivalents to
keep the temperature in the rack below +30 °C {86 °F}.
• Do not block the ventilation holes or slots to prevent the
recorder from overheating.