DHMSHA
High Wall Ductless System
Sizes 09 to 36
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MODEL/SERIAL NUMBER NOMENCLATURES
SPECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPATIBILITY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIMENSIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEARANCES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL DATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WIRING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTION DIAGRAMS
WIRING DIAGRAMS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERATION CYCLE DIAGRAMS
REFRIGERANT LINES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSTEM EVACUATION AND CHARGING
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INDOOR UNIT DIAGNOSTIC GUIDE
DIAGNOSIS AND SOLUTION
APPENDIX
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISASSEMBLY INSTRUCTIONS
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air−conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start−up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by
trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read this manual thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local building
codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety−alert symbol
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION.
Service Manual
PAGE
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
These words are used with the safety−alert symbol. DANGER
identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
1
could result in personal injury or death. CAUTION is used to
1
identify unsafe practices which may result in minor personal injury
2
or product and property damage. NOTE is used to highlight
3
suggestions which will result in enhanced installation, reliability, or
operation.
3
4
!
4
5
ELECTRICAL SHOCK HAZARD
5
Failure to follow this warning could result in personal
6
injury or death.
7
Before installing, modifying, or servicing system, main
9
electrical disconnect switch must be in the OFF
9
position. There may be more than 1 disconnect switch.
10
Lock out and tag switch with a suitable warning label.
15
16
!
17
34
38
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
! !
.
refrigerant slugging and could possibly damage the
compressor at start−up.
INTRODUCTION
This Service Manual provides the necessary information to service,
repair, and maintain the indoor units. Section 2 of this manual has an
appendix with data required to perform troubleshooting. Use the Table
of Contents to locate a desired topic.
WARNING
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION

Advertisement

Table of Contents
loading

Summary of Contents for Carrier DHMSHAQ09XA1

  • Page 1 DHMSHA High Wall Ductless System Sizes 09 to 36 Service Manual TABLE OF CONTENTS These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe PAGE personal injury or death. WARNING signifies hazards which SAFETY CONSIDERATIONS .
  • Page 2: Model/Serial Number Nomenclatures

    MODEL/SERIAL NUMBER NOMENCLATURES Table 1—Unit Sizes SYSTEM TONS VOLTAGE/PH/HZ INDOOR MODEL DHMSHAQ09XA1 115/1/60 DHMSHAQ12XA1 DHMSHAQ09XA3 DHMSHAQ12XA3 DHMSHAQ18XA3 208-230/1/60 DHMSHAQ24XA3 DHMSHAQ30XA3 DHMSHAQ36XA3 INDOOR UNIT DH = FAN COIL UNIT VOLTAGE 1 =115-1-60 3 = 208/230-1-60 MS = MODEL VARIATIONS A = STANDARD...
  • Page 3: Specifications

    SPECIFICATIONS Table 2—Specifications HEAT PUMP SIZE System Indoor Model DHMSHAQ09XA1 DHMSHAQ12XA1 DHMSHAQ09XA3 DHMSHAQ12XA3 DHMSHAQ18XA3 DHMSHAQ24XA3 DHMSHAQ30XA3 DHMSHAQ36XA3 Voltage, V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Phase, Cycle Electrical Power Supply Indoor unit powered from outdoor unit 0.27 Wireless Remote...
  • Page 4: Dimensions

    DIMENSIONS Table 4—Dimensions HIGH WALL UNIT SIZE Voltage (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) Height In (mm) 11.02 (280) 11.02 (280) 11.02 (280) 11.02 (280) 12.40 (315) 13.39 (343) 13.39 (343) 13.39 (343) Width In (mm) 32.87 (835) 32.87 (835) 32.87 (835) 32.87 (835)
  • Page 5: Electrical Data

    ELECTRICAL DATA Table 5—Electrical Data Indoor High Wall HIGH WALL INDOOR FAN MAX FUSE CB AMP UNIT SIZE V-Ph-Hz 0.33 0.053 115-1-60 0.33 0.053 0.33 0.053 0.33 0.053 Refer to outdoor unit installation instructions – Indoor unit powered by the outdoor unit 0.49 0.067 208/230-1-60...
  • Page 6: Connection Diagrams

    CONNECTION DIAGRAMS Fig. 3 – 115V Fig. 4 – 208−230V Notes: 1. Do not use thermostat wire for any connection between indoor and outdoor units. 2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
  • Page 7: Wiring Diagrams

    WIRING DIAGRAMS BLUE(BLACK) L-IN YELLOW CN11 CN16 OPTIONAL L N S Wi-Fi INDOOR UNIT Contoller 8(7) OUTDOOR UNIT INDOOR WIRING DIAGRAM OPTIONAL Wire Contoller Fig. 5 – Wiring Diagram Sizes 09−12 (115V) Table 6—INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage: AC115V CN11...
  • Page 8 WIRING DIAGRAMS (CONT) BLUE(BLACK) L-IN YELLOW CN11 CN16 OPTIONAL L1L2 S Wi-Fi INDOOR UNIT Contoller 8(7) OUTDOOR UNIT INDOOR WIRING DIAGRAM OPTIONAL Wire Contoller Fig. 6 – Wiring Diagram Sizes 09−36 (208−230V) Table 7—INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage: AC230V CN11...
  • Page 9: Refrigeration Cycle Diagrams

    REFRIGERATION CYCLE DIAGRAMS Fig. 7 – Heat Pumps REFRIGERANT LINES IMPORTANT: Both refrigerant lines must be insulated separately. Table 2 lists the pipe sizes for the indoor unit. Refer to the outdoor unit installation instructions for other allowed piping lengths and refrigerant information.
  • Page 10: System Evacuation And Charging

    Deep Vacuum Method SYSTEM EVACUATION AND The deep vacuum method requires a vacuum pump capable of CHARGING pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method CAUTION is the most positive way of assuring a system is free of air and liquid water (see Fig.
  • Page 11 COOLING Mode Main Protection Indoor Fan Running Rules Fan Speed is Out of Control In the COOLING mode, the indoor fan runs all the time and the When the indoor fan speed remains too low (300RPM) or too high speed can be selected as high, medium, low and auto. When the (1500RPM) for a certain time, the unit stops and the LED displays setting temperature is reached, if the compressor stops running, the the failure.
  • Page 12 HEATING Mode Evaporator Coil Temperature Protection Indoor Fan Running Rules When the compressor is on, the indoor fan can be set to high/med/low/auto/mute. When the indoor unit coil temperature is low, the anti−cold air function starts and the indoor fan motor runs at a low speed and the speed can not be changed.
  • Page 13 Evaporator Anti−Freezing Protection Refrigerant Leakage Detection evaporator anti−freezing protection condenser high With this new technology, the display area displays “EC” when the temperature protection and outdoor unit frequency limit are active outdoor unit detects a refrigerant leak. This function is only active and the same as that in the COOLING mode.
  • Page 14 Table 8—Information Enquiry ENQUIRY INFORMATION DISPLAYING CODE MEANING T1 temp. T2 temp. T3 temp. T4 temp. T2B temp. TP temp. TH temp. Targeted Frequency Targeted Frequency Actual Frequency Actual Frequency Indoor Fan Speed Indoor fan speed Outdoor Fan Speed Outdoor fan speed EXV Opening Angle EXV opening angle Compressor continuous running time...
  • Page 15: Troubleshooting

    TROUBLESHOOTING Safety Electricity power is kept in capacitors even if the power supply is shut off. NOTE: Remember to discharge the electricity power in capacitor. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) Fig. 19 – Electrolytic Capacitors For other models, please connect discharge resistance (approximately 100 40W) or a soldering iron (plug) between the +, −...
  • Page 16: Indoor Unit Diagnostic Guide

    INDOOR UNIT DIAGNOSTIC GUIDE Table 10—Indoor Unit Error Display OPERATION LAMP TIMER LAMP DISPLAY LED STATUS Indoor unit EEPROM parameter error 1 time Indoor / outdoor units communication error 2 times Zero-crossing signal detection error 3 times Indoor fan speed has been out of control 4 times Indoor room temperature sensor T1 open circuit or short circuit 5 times...
  • Page 17: Diagnosis And Solution

    DIAGNOSIS AND SOLUTION EEPROM Parameter Error Diagnosis and Solution (E0/F4) Error Code E0/F4 Malfunction decision conditions Indoor or outdoor PCB main chip does not receive feedback from the EEPROM chip. ·Installation mistake Supposed causes ·PCB faulty Troubleshooting Power off, then restart the unit 2 minutes later.
  • Page 18 DIAGNOSIS AND SOLUTION (CONT) Indoor / outdoor unit’s communication diagnosis and solution (E1) Error Code Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition Malfunction Decision Conditions happens four times continuously. ·Wiring mistake Supposed Causes ·Indoor or outdoor PCB faulty Troubleshooting...
  • Page 19 DIAGNOSIS AND SOLUTION (CONT) Fig. 23 – Test the DC Voltage Use a multimeter to test the DC voltage between L2 port and S port of the outdoor unit. The red pin of the multimeter connects with the L2 port while the black pin is for the S port. When air conditioner is running normal, the voltage moves alternately between −50V to 50V. If the outdoor unit has a malfunction, the voltage will move alternately with positive value.
  • Page 20 DIAGNOSIS AND SOLUTION (CONT) Zero crossing detection error diagnosis and solution (E2) Error Code When the PCB does not receive a zero crossing signal feedback for 4 minutes or the zero crossing Malfunction decision conditions signal time interval is abnormal. ·Connection mistake Supposed causes ·PCB faulty...
  • Page 21 DIAGNOSIS AND SOLUTION (CONT) Fan speed has been out of control diagnosis and solution (E3/F5) Error Code E3/F5 When indoor fan speed remains too low (300RPM) for certain time, the unit stops and the LED Malfunction decision conditions displays the failure. ·Wiring mistake ·Fan assembly faulty Supposed causes...
  • Page 22 DIAGNOSIS AND SOLUTION (CONT) Index 1 1 Indoor or Outdoor DC Fan Motor (control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1−pin3, pin4−pin3 in fan motor connector. If the voltage value is not in the range shown in Table 11 or Table 12, the PCB has an issue and needs to be replaced.
  • Page 23 DIAGNOSIS AND SOLUTION (CONT) Open circuit or short circuit of temperature sensor diagnosis and solution (E4/E5/F1/F2/F3) Error Code E4/E5/F1/F2/F3 Malfunction decision conditions If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure. ·Wiring mistake Supposed causes ·Sensor faulty ·PCB faulty...
  • Page 24 DIAGNOSIS AND SOLUTION (CONT) Refrigerant Leakage Detection diagnosis and solution (EC) Error Code Define the evaporator coil temp.T2 of the compressor. It starts running in Tcool. At first, 5 minutes after the compressor starts up, if T2 <Tcool-35.6 F (Tcool-2 C) does not Malfunction decision conditions run for 4 seconds and this situation occurs 3 times, the display area displays“EC”and the air...
  • Page 25 DIAGNOSIS AND SOLUTION (CONT) Overload current protection diagnosis and solution (F0) Error Code Malfunction decision conditions An abnormal current rise is detected by checking the specified current detection circuit. ·Power supply problems ·System blockage Supposed causes ·PCB faulty ·Wiring mistake ·Compressor malfunction Troubleshooting Stop the unit...
  • Page 26 DIAGNOSIS AND SOLUTION (CONT) IPM malfunction or IGBT over−strong current protection diagnosis and solution (P0) Error Code When the voltage signal, that the IPM sends to the compressor drive chip is abnormal, the display Malfunction decision conditions LED displays P0”and the air conditioner turns off. ·Wiring mistake ·IPM malfunction Supposed causes...
  • Page 27 DIAGNOSIS AND SOLUTION (CONT) Fig. 27 – P−U Fig. 28 – P−V...
  • Page 28 DIAGNOSIS AND SOLUTION (CONT) Fig. 29 – P−W Fig. 30 – N−U...
  • Page 29 DIAGNOSIS AND SOLUTION (CONT) Fig. 31 – N−V Fig. 32 – N−W...
  • Page 30 DIAGNOSIS AND SOLUTION (CONT) Over voltage or too low voltage protection diagnosis and solution (P1) Error Code Malfunction decision conditions An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit. ·Power supply problems Supposed causes ·System leakage or block ·PCB faulty Troubleshooting...
  • Page 31 DIAGNOSIS AND SOLUTION (CONT) High temperature protection of compressor top diagnosis and solution (P2) Error Code Malfunction decision conditions If the sampling voltage is not 5V, the LED displays the failure. ·Power supply problems ·System leakage or block Supposed causes ·PCB faulty Troubleshooting Check the air flow system...
  • Page 32 DIAGNOSIS AND SOLUTION (CONT) Inverter compressor drive error diagnosis and solution (P4) Error Code An abnormal inverter compressor drive is detected by a special detection circuit, including Malfunction decision conditions communication signal detection, voltage detection, compressor rotation speed signal detection, etc.. ·Wiring mistake ·IPM malfunction Supposed causes...
  • Page 33 Main Parts Check Temperature Sensor Checking Disconnect the temperature sensor from the PCB, measure the resistance value with a tester. Fig. 34 – Tester Temperature sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor.
  • Page 34: Appendix

    APPENDIX Table 13—Temperature Sensor Resistance Value Table for T1, T2, T3, T4 ( C−−K) K Ohm ° C ° F K Ohm ° C ° F K Ohm ° C ° F K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517...
  • Page 35 APPENDIX (CONT) Table 14—Temperature Sensor Resistance Value Table for T1,T2,T3,T4 ( C−−K) ° C ° F K Ohm ° C ° F K Ohm ° C ° F K Ohm ° C ° F K Ohm 542.7 68.66 13.59 3.702 511.9 65.62 13.11...
  • Page 36 APPENDIX (CONT) Δ Δ Table 15— F)=9 C)/5 ° ° ° C ° F ° C ° F ° C ° F ° C ° F ° C ° F 69.8 123.8 179.6 235.4 24.8 71.6 125.6 181.4 237.2 26.6 73.4 127.4 183.2...
  • Page 37 IPM Continuity Check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N. Table 16—Digital Tester NORMAL RESISTANCE NORMAL RESISTANCE DIGITAL TESTER DIGITAL TESTER VALUE...
  • Page 38: Disassembly Instructions

    DISASSEMBLY INSTRUCTIONS NOTE: This part is for reference, the photos may have slight difference with your unit. Parts name Procedures Remarks Front panel How to remove the front Overview: panel Pull the bottom side of the panel and release the clips. Then One screw Panel remove the front...
  • Page 39 DISASSEMBLY INSTRUCTIONS (CONT) Electrical How to remove the Room temp. parts electrical parts. sensor Grounding screws After removing the front panel (see section 1), pull out the Swing motor room temperature sensor and evaporator coil sensor. Remove the grounding screws. Pull out the clip toward the left side and open the cover.
  • Page 40 DISASSEMBLY INSTRUCTIONS (CONT) Evaporator How to remove the evaporator. 1) After removing the front panel assembly and electrical parts (sections 1 and 2), remove the pipe holder at the rear side of the unit. 2) Remove the two screws on the evaporator at the base bearing side.
  • Page 41 DISASSEMBLY INSTRUCTIONS (CONT) Fan and How to remove the fan motor and motor. After removing the evaporator assembly (see sections 1 - 3), remove the three (3) screws securing the cover. Remove the screw securing the motor and then pull out the Three screws motor.
  • Page 42 Catalog No: SG-DHMSHA-01 Copyright 2017 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 11/17 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: NEW...