Setting Of Unit Address - JVL FBG10 User Manual

Field bus gateway
Table of Contents

Advertisement

2.5
For setting of the unit address there is a DIP-switch on the front panel of the FBG10
All of the unit adresses from 0 .. 127 can be set by means of the switches A6 .. A0 . The
setting of the switch designated "VALID" determines if the address set is valid.
Function:
— FBG10 contains an EEPROM, where the last set unit address is stored.
— DIP-switches are read at each "power on".
— If VALID = 1, then FBG10 will get the address which A6 .. A0 to indicate and this
address is at the same time stored in the EEPROM.
— If VALID = 0, then FBG10 will get the address which is stored in the EEPROM.
— Setting of the unit address is therefore made by:
1. Set A6 .. A0 to the required address.
2. Set VALID = 1.
3. Connect supply voltage and wait 1 sec.
4. Set VALID = 0.
The set addres is now stored in the EEPROM, and will be used by the following "power
on".
12
JVL Industri Elektronik A/S — User Manual — Field Bus Gateway FBG-10

Setting of Unit address