Loreme PL36 Configuration Handbook

Ac & dc true rms panel wattmeter, voltmeter, ammeter, frequency meter

Advertisement

Quick Links

AC & DC true RMS panel
Wattmeter, Voltmeter, Ammeter, Frequency meter
CONFIGURATION HANDBOOK
IPL36
IPL36L
LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3
Phone 03.87.76.32.51 - Telefax 03.87.76.32.52
Contact : Commercial@Loreme.fr - Technique@Loreme.fr
Download manual at : www.loreme.fr
REV 0.7 - 05/09/17
E 1

Advertisement

Table of Contents
loading

Summary of Contents for Loreme PL36

  • Page 1 Wattmeter, Voltmeter, Ammeter, Frequency meter CONFIGURATION HANDBOOK IPL36 IPL36L LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3 Phone 03.87.76.32.51 - Telefax 03.87.76.32.52 Contact : Commercial@Loreme.fr - Technique@Loreme.fr Download manual at : www.loreme.fr...
  • Page 2 2.1) General remarks .......................... p22 2.2) Power Supply ..........................p22 2.3) Inputs / Outputs ........................... p22 IPL36(L) STANDARD WIRING..........................p23 IPL36(L)-Hall WIRING .............................. p24 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 3: Device Presentation

    IPL36(L)../CMTCP : + Ethernet Modbus TCP/SNMP link.  IPL36(L)../CM : + RTU Modbus link. /S, /CM and /CMTCP options are not combinable. The technical data sheets are downloadable at: http://www.loreme.fr/fichtech/IPL36_eng.pdf http://www.loreme.fr/fichtech/IPL36L_eng.pdf 6 digits, 7 segments LED display for the measure. 3 buttons for configuration, re-...
  • Page 4: Energy Counter Reset

    (0.01 s to 60 s, default value is 1 s). Use the buttons to increase or  decrease the value and the button to validate the value. LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 5: Network Configuration

     SOMMAIRE 4.3) Network configuration The wiring options on the network are: - Alternative or Continuous. - Single-phase or balanced three phases with neutral for a alternative network. It is also necessary to configure: - The Potential Transformer ratio (PT ratio). - The Current Transformer ratio (CT ratio) or external current shunt sensibility or the Hall sensor current caliber on a -Hall version.
  • Page 6: Output Configuration

    (yes) button to activate the output limitation, Push the (no) button to deactivate the output limitation. for more details about the output parameters. LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 7: Communication Configuration

     SOMMAIRE 4.6) Communication configuration This rubric is only visible if the unit is equipped with the /CMTCP or /CM option.  COMMUNICATION CONFIG? Push the (yes) button to access to the rubric. 4.6.1) CMTCP option  IP ADDRESS? Push the (yes) button to access to the rubric.
  • Page 8: End Of Configuration

    If during the setting, no buttons are pressed for more than 60 s, the device return automatically to measure mode with- out taking into account the new settled threshold. LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 9: Rs232 Link Setting

    Step 2: Setting of terminal emulation software (PC with windows). The terminal emulation software for PC « HyperTerminal » is resident in windows up to XP version. For later ver- sions, it is downloadable on : www.loreme.fr in download part ( http://www.loreme.fr/HyperTerm/htpe63.exe =>...
  • Page 10: Terminal Mode

    If there is no action on a key during 2 minutes, device goes back in measure mode without taking notice of the modifi- cations made before. E 10 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 11: Language

     SOMMAIRE Configuration 2.2) Language The language possibilities are: - French - English 2.3) Input The input configuration is made of: - Voltage input choice. - Current input choice (only with standard device). - Measure response time. 2.4) Network The wiring options on the network are: - Alternative: single-phase or balanced three phases with neutral.
  • Page 12: Analogical Output

    - Decimal point display mode. - Power units display mode. DISPLAY CONFIGURATION? Press the ‘Y’ key to access display configuration. (Y-N) E 12 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 13: Special Functions

     SOMMAIRE DISPLAY FILTER? Enter the filter value (0 to 60 s). DECIMAL POINT? Press the ‘Y’ key to access decimal point mode configuration. (Y-N) AUTO(Y/N)? (Y-N)YES Press 'Y' key to choose the automatic decimal point display mode or 'N' to choose the fixed mode.
  • Page 14: Modbus Communication

    (register reading function). Data address not allowed Slave busy. The internal communication slot is not in connection with the measure part. E 14 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 15  SOMMAIRE 4) Measure tables 4.1) Floating point format data The register address are the same as the table for MODBUS-TCP communication. The measure are in floating point format number except for the alarm status register (16 bits). 4.1) Integer format data The register address are the same as the table for MODBUS-TCP.
  • Page 16: Modbus Tcp Communication

    - Alarm data in 16bits integer (0 to 15), bit 0 for R1 and bit 1 for R2. Data are transmitted Most significant byte first. Byte 1 Byte 2 E 16 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 17  SOMMAIRE 4) Tables of measures 4.1) 32 bits floating format measures This table lists the measures in 32 bits floating point format and 16 bits register for alarm status (address 4108). Register address in decimal Designation Total (Hexadecimal) words 4096 ($1000) Voltage (V) Word 1...
  • Page 18 For an IPL36L, the Powers and Power Factor measures are at $FFFFFFFF hexadecimal and the energy counter stays equal to $00000000. E 18 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 19: Web Server

     SOMMAIRE WEB server (if option /CMTCP) Click to refresh Tab for SNMP Tab for password version number measures parameters configuration. WEB page overview 1) "Measure" tab Display all measurements of an IPL36 or IPL36L IPL36L (There are no energy, power, power factor IPL36 measurement ) 2) "SNMP"...
  • Page 20: Snmp

    (refer to the page 18, section 4.2, for more details) The MIB file can be downloaded directly on the Web page of the device. E 20 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 21: Firmware Update

    FIRMWARE LOADER Rev3 READY TO TRANSFER... The device is now in the firmware load mode and is waiting for the firmware file. This file is provide by LOREME and contain the firmware code in Intel HEX format. Select the « Transfer », « Send a text file ... » in the HyperTerminal menu.
  • Page 22: Emc Consideration

    - It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling phenomena. - It is also advisable to limit the lengths of data cables as much as possible. E 22 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...
  • Page 23: Ipl36(L) Standard Wiring

     SOMMAIRE IPL36(L) standard Wiring Jumper for voltage output Power supply (20 to 265Vac/dc): terminals L+, N-. Relay 1: terminals common (C1), rest (R1), work (T1) Relay 2: terminals common (C2), rest (R2), work (T2) (/S option) Analogical output mA: terminals analog+ (+), analog- (-), no jumper.
  • Page 24: Ipl36(L)-Hall Wiring

    Current input: terminals Vin, Gnd for the signal. (Hall sensor) terminals +15V & -15V for the sensor power supply. E 24 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-...

This manual is also suitable for:

Ipl36l

Table of Contents