Outdoor Temperature Sensor Installation
Outdoor Temperature Sensor
(Optional)
Outdoor Temperature Sensor Installation
Separate the sensor body from the sensor cap.
Attach the sensor body to the wall using the provided screws.
Run the wires into the device body through the grommet
opening
Connect the wires to the terminal block.
Attach the cap to the sensor body.
Outdoor Temperature Sensor Installation
Guidelines
Avoid installing the temperature sensor in a location where the
temperature may change due to direct sunlight or a location
where the representative outdoor temperature is not indicated.
The best place to install the temperature sensor is to the north
or northeast of the eaves, where direct sunlight can be avoided.
Do not install the sensor near a heat source that may affect
sensing of a correct temperature (fans, exhaust vents, lights).
Avoid installing the sensor in a location with a high amount of
moisture.
Use 18gauge wiring with no splices
Before attaching the cap, ensure the wiring is fixed firmly.
The sensor is a water resistant device.
Outdoor Reset Control
(Available with Optional
Outdoor Temperature Sensor)
The outdoor reset control can be used in order to improve the
energy efficiency. With the Outdoor Reset Control, the space
heating temperature setting automatically changes according to
the outdoor temperature and the current space heating system
application (system load)
Notice
The outdoor reset control can be used only when the outdoor
temperature sensor is installed. In addition, it only works when the
boiler is running in the normal operation mode. It does not work when
the boiler is running in either the Minimum(MIN) or Maximum(MAX)
mode, or When the boiler's front panel displays a fault.
The following tables list the default space heating temperature
range by system heat load and the applicable outdoor temperature
ranges.
Minimum
Maximum
Heat load
set-point
set-point
Finned
tube heat
118°F(48°C)
180°F(82°C)
load types
Fan coil
120°F(60°C)
180°F(82°C)
Cast iron
100°F(38°C)
170°F(77°C)
baseboard
Low mass
82°F(28°C)
140°F(60°C)
radiant
High mass
82°F(28°C)
122°F(50°C)
radiant
118°F(48°C)
170°F(77°C)
Radiator
Custom
Outdoor Temperature Sensor Installation
Out temperature
Min-maximum
Minimum out
temperature: 14°F(-10°C)
Maximum out
temperature: 68°F(20°C)
User define
61