MODBUS PROTOCOL
6

6.8 Holding registers

Some parameters of the device can be accessed as Modbus holding registers.
Function code 03 (0x03) for "Read" operations and function code 16 (0x10) for "Write" operations.
The holding registers are grouped into the following different sections.
6.8.1 Counter parameters
INFORMATION!
Counter 3 parameters are only available for converter with IO 2.
Modbus protocol
Description and settings
address
40000
counter 1 function
counter 1 function
counter 1 function
counter 1 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
40001
measurement counter 1
measurement counter 1
measurement counter 1
measurement counter 1
21 = volume flow
22 = mass flow
40002
counter 2 function
counter 2 function
counter 2 function
counter 2 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
40003
measurement counter 2
measurement counter 2
measurement counter 2
measurement counter 2
21 = volume flow
22 = mass flow
40004
counter 3 function
counter 3 function
counter 3 function
counter 3 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
40005
measurement counter 3
measurement counter 3
measurement counter 3
measurement counter 3
21 = volume flow
22 = mass flow
41000
low flow cutoff value counter 1 [m
low flow cutoff value counter 1
low flow cutoff value counter 1
low flow cutoff value counter 1
or [kg/s]
41002
time constant counter 1 [s]
time constant counter 1
time constant counter 1
time constant counter 1
41004
set counter 1 or read counter 1 [m
set counter 1 or read counter 1
set counter 1 or read counter 1
set counter 1 or read counter 1
41006
low flow cutoff value counter 2
low flow cutoff value counter 2 [m
low flow cutoff value counter 2
low flow cutoff value counter 2
or [kg/s]
41008
time constant counter 2 [s]
time constant counter 2
time constant counter 2
time constant counter 2
41010
set counter 2 or read counter 2 [m
set counter 2 or read counter 2
set counter 2 or read counter 2
set counter 2 or read counter 2
41012
low flow cutoff value counter 3 [m
low flow cutoff value counter 3
low flow cutoff value counter 3
low flow cutoff value counter 3
or [kg/s]
41014
time constant counter 3 [s]
time constant counter 3
time constant counter 3
time constant counter 3
41016
set counter 3 or read counter 3 [m
set counter 3 or read counter 3
set counter 3 or read counter 3
set counter 3 or read counter 3
18
Converter Fct.
No.
C3.1.1
C3.1.2
C3.2.1
C3.2.2
C3.3.1
C3.3.2
3
C3.1.3
/s]
C3.1.4
C3.1.7
3
] or [kg]
3
C3.2.3
/s]
C3.2.4
C3.2.7
3
] or [kg]
C3.3.3
3
/s]
C3.3.4
3
C3.3.7
] or [kg]
www.honeywell.com/ps
TWM 9000
Type
Number of
registers
byte
1
word
1
byte
1
word
1
byte
1
word
1
float
2
float
2
float
2
float
2
float
2
float
2
float
2
float
2
float
2
34-VF-25-22 iss.1 GLO Nov 09 US