A 60-second start-up period occurs during initial installation and after a power failure of 5 minutes or more. After applying power to the
sensor wait at least 60 seconds for the sensor to begin detecting occupancy and the load to turn ON. It may turn ON during the start-up
period, depending on the state of the relay when power was off.
• If the sensor detects occupancy during the start-up, when the load turns ON it stays ON as long as the sensor continues to detect
motion, plus the Time Delay.
• If no occupancy is detected during the 60-second start-up, the load may come on anyway during the start-up. If no occupancy is
detected by the time the start-up is complete, the relay opens and the load turns OFF.
If you suspect improper operation, review the Start-Up information. After start-up, the sensor will open or close the relay to correspond to
the occupancy status of the area. When power to the sensor is lost, the relay(s) close, turning on the load if the load still has power.
To quickly test the unit, set the time delay to minimum. Wait for the start-up period to end. Move out of the sensor's view. Lights should
turn OFF after 15 seconds. Move into the sensor's view. The sensor's Red LED should blink and the lights should turn ON.
Red LED on power module does not blink:
Check sensor wire connections. Verify the neutral wire is tightly secured.
Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least one minute, then
a. Turn OFF power to the sensor. The relay will close.
b. Turn ON power to the sensor. The load should come ON. If not, continue with step 2.
2. Check power connections to the light fixture.
3. Check all sensor wire connections. Verify the load wire is tightly secured.
4. Make sure the sensor is not continuously triggered (LED Flashing) during the time delay duration.
Lights will not turn OFF:
1. If there is no motion from people or equipment in the sensor's view but the red LED blinks, look for any nearby source of infrared
energy (heat) in motion, such as turbulent air from a heating or cooling supply, or other sources such as heat from the fluorescent
lamps in the fixture.
• Mount the sensor so that it's lens is below the edge of the fixture and does not directly view the lamps.
• Divert the air supply away from the sensor, or move the sensor.
2. Verify time delay set in switches 3-7. The time delay can be set from 15 seconds to 30 minutes. Ensure that the time delay is set to
the desired delay and that there is no movement within the sensor's view for that time period.
3. Check PIR and Light Level Override DIP switch settings. If all control functions are overridden the load stays ON.
4. Check sensor wire connections. Verify load and neutral wires are secure.
Catalog #
Description
HB340B-L1
High Bay Sensor 347/480 VAC with coverage @ 40' mounting height, 60' x 20'.
HB340B-L3
High Bay Sensor 347/480 VAC with coverage @ 20' mounting height, 24' diameter.
HB340B-L7
High Bay Sensor 347/480 VAC with coverage @ 40' mounting height, 100' diameter.
HB3EM3
Extender module with 2 chase nipples and nuts 1 short (0.88") for connection to plastic, 1 long (1.24") for
connection to metal
All units are White.
WARRANTY INFORMATION
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
No. 24162 – 2/17 rev. 1
© Copyright 2017 Legrand All Rights Reserved.
© Copyright 2017 Tous droits réservés Legrand.
© Copyright 2017 Legrand Todos los derechos reservados.
IMPORTANT START-UP INFORMATION

TROUBLESHOOTING

ORDERING INFORMATION

INFORMATIONS RELATIVES À LA GARANTIE
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l'utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d'enlèvement,
d'installation ou de réinstallation.
INFORMACIÓN DE LA GARANTÍA
Wattstopper
garantiza
que
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de
extracción,
instalación
800.879.8585
www.legrand.us/wattstopper
sus
productos
o
reinstalación.

Advertisement

loading

This manual is also suitable for:

Hb340b-l7Hb340b-l3