LEGRAND HB340B-L1 Installation Instructions page 3

High bay line voltage passive infrared occupancy sensor

Advertisement

HBEM3
Extender
Module
Back
Box
HB340
Sensor
Module
HBLx
Lens
Using the back box and HBEM3 Extender Module
Sensor factory pre-sets are as follows (default settings are bold):
Factory Switch Settings (N/A = not applicable, no effect)
1
2
3
4
ON OFF OFF OFF OFF ON ON OFF N/A N/A
PIR Sensitivity (switches 1&2) ........... Medium 85%
Time Delay (switches 3-7) .................... 15 minutes
Override (switch 8) ........Controlled by occupancy
PIR Sensitivity (Switches 1-2)
The factory setting (Normal) is suitable for most
applications, but it may be necessary to adjust the PIR
sensitivity if there is any environmental interference
causing false triggers or if sensitivity needs to be
increased for your particular application. Use DIP
switches 1 & 2 to adjust sensitivity.
Switch 1
2
PIR SENSITIVITY
OFF
OFF 100% High
ON
OFF 85% (MEDIUM)
OFF
ON
75% (LOW)
ON
ON
60% (LOW)
o r
Alignment Guides
5
6
7
8
9
Light Level
Adjustment
Trimpot
Surface
Mounting
Screw Hole
Detection
Indicator LED
ADJUSTMENTS
Time Delay (Switches 3-7)
Use DIP switches 3 to 7 to adjust the time delay.
Switch 3
10
PIR Override (Switch 8)
A value of OFF enables occupancu control. A value of ON sets
the load ON all the time (used for testing load).
NOTE: Switches 9 and 10 are not used in this model.
3
4
5
6
ON
ON
ON
ON
OFF ON
ON
ON
OFF OFF ON
ON
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF OFF OFF
DIP Switches
Surface
Mounting
Screw Hole
PIR Sensor
(do not touch)
7
TIME DELAY
ON
15 seconds
ON
5 minutes
ON
10 minutes
ON
15 minutes
ON
20 minutes
OFF 30 minutes