Back-Up Protection Functions - ABB RED670 Product Manual

Line differential protection ansi customized, relion 670 series
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

Line differential protection RED670 ANSI
Customized
Product version: 1.2

Back-up protection functions

IEC 61850
ANSI
Current protection
PHPIOC
50
OC4PTOC
51_67
EFPIOC
50N
EF4PTOC
51N_67
N
NS4PTOC
46I2
SDEPSDE
67N
LPPTR
26
CCRBRF
50BF
STBPTOC
50STB
CCRPLD
52PD
GUPPDUP
37
GOPPDOP
32
BRCPTOC
46
Voltage protection
UV2PTUV
27
OV2PTOV
59
ROV2PTOV
59N
OEXPVPH
24
VDCPTOV
60
LOVPTUV
27
Frequency protection
SAPTUF
81
SAPTOF
81
SAPFRC
81
Multipurpose protection
CVGAPC
ABB
Function description
Instantaneous phase overcurrent protection
Four step phase overcurrent protection
Instantaneous residual overcurrent protection
Four step residual overcurrent protection
Four step directional negative phase sequence overcurrent protection
Sensitive directional residual overcurrent and power protection
Thermal overload protection, one time constant
Breaker failure protection
Stub protection
Pole discordance protection
Directional underpower protection
Directional overpower protection
Broken conductor check
Two step undervoltage protection
Two step overvoltage protection
Two step residual overvoltage protection
Overexcitation protection
Voltage differential protection
Loss of voltage check
Underfrequency protection
Overfrequency protection
Rate-of-change frequency protection
General current and voltage protection
1MRK505226-BUS D
Line Differential
RED670
0-3
0-1
0-1
0-1
0-1
0-1
0–2
0-2
0-2
0-2
0-2
0-2
1
0-2
0-2
0-2
0-1
0-2
1
0-2
0-2
0-2
0-4
5