Summary of Contents for Minco TT211

  • Page 1 TT211 and TT711 2-Wire Temperature Transmitter Installation and Operating Instructions INTRINSICALLY SAFE NON-INCENDIVE TT211 / TT711 Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com• Doc. #1116290(D)
  • Page 2 Description Models TT211 and TT711 are 2-wire temperature transmitters for 2-lead 100 ohm or 1000 ohm platinum RTD's. These transmitters are FM-approved for use in Class I, Divisions 1 & 2, Groups A, B, C, and D hazardous locations and appear in the approval guide as IS/I/1/ABCD and NI/I/2/ABCD.
  • Page 3: Wiring Diagram

    1.1 Accessibility - The transmitters must be installed within the enclosure so that its circuits are accessible by the use of a tool only. A part is accessible when a) the IEC Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 4 10 degrees with the horizontal and then turned to the position (with all doors, drawers and other openable and sliding parts in the least stable position) most likely to cause tip-over. Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 5 3. Voc, Vt, Isc, It, Ca and La are parameters of the associated apparatus where: Voc,Vt = maximum open circuit voltage Isc,It = maximum short circuit current Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 6 Division 2 hazardous (classified) locations. 8. For Division 2 installations, the transmitters must be mounted within an enclosure meeting the requirements of ANSI/ISA S82. Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 7 PEPPERL & FUCHS KHD3-ICR/EX130 200 (TWINSBURG, OH KHD3-ICR/EX130 240 216-425-3555) KHP-103/EX-1A KHP-104/EX-2A KHP-105/EX-2A KHZ-428/EX3 KHZ-487/EX3 KHZ-907/EX Z130/EX Z428/EX Z479/EX Z487/EX MINCO PRODUCTS, INC. INST. 704(A) PAGE 2 OF 3 Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com 1116290(D)
  • Page 8 SIMPLE APPARATUS MODELS TT176, TT190, TT216, TT230 OR TT676 SIMPLE APPARATUS ASSOCIATED APPARATUS MODELS TT220, TT221, OR TT720 MINCO PRODUCTS, INC. INST. 704(A) PAGE 3 OF 3 Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 9 5. Set decade box resistance to simulate the 20 mA temperature. 6. Adjust SPAN potentiometer on the transmitter until the meter reads 20 mA. 7. Repeat steps 3 - 7 until no further adjustment is necessary. Minco Tel: 763. 571.3121 • Fax: 763. 571.0927 • www.minco.com • Doc. #1116290(D)
  • Page 10: Specifications

    Warranty Items returned within one year from the date of sale, transportation prepaid, which Minco Products, Inc. (The "Seller") reasonably determines to be faulty by reason of defective materials or faulty workmanship will be replaced or repaired at the Seller's discretion, free of charge.
  • Page 11 PW = 1000 ohm platinum (.00375) 1 Output: 4 to 20 mA DC C Temperature Range: Use one of the over 175 range codes in the MINCO Temptran sales bulletin. Note: A range that is available for a particular Temptran model is not automatically available for the TT211/TT711;...