Installation - Fisher 128-PQC Instruction Manual

Table of Contents

Advertisement

FLOWING
FLOWING
PRESSURE
ACTUATOR
SEATING
SEATING
ACTION
ACTION
TENDS TO:
Open valve
Spring
S ring
closes valve
Close valve
Metal
Spring
Close valve
opens valve
Open valve
S ring
Spring
closes valve
Close valve
Soft
Spring
Close valve
opens valve
24B1860-B / DOC

Installation

WARNING
To avoid personal injury or property
damage resulting from the sudden re-
lease of pressure, do not install the
valve assembly where service condi-
tions could exceed the limits given in
this manual or on the appropriate name-
plates. The leakoff and spring case
vents must be kept open. Avoid danger
Table 3. Maximum Allowable Shutoff Pressure Drops
PORT
PORT
DIAMETER
0 to 20 Psig (0 or
1.4 Bar) Actuator
1.4 Bar) Actuator
DROP
DROP
Springs Required)
Inches
Inches
mm
mm
1/4
6.4
1510
3/8
9.5
1/2
12.7
3/4
19.1
1/4
6.4
3/8
9.5
1130
1/2
12.7
1330
3/4
19.1
2030
1/4
6.4
3/8
9.5
1/2
12.7
3/4
19.1
1400
1/4
6.4
1000
3/8
9.5
1/2
12.7
3/4
19.1
1/4
6.4
3/8
9.5
1000
1/2
12.7
1000
3/4
19.1
1000
1/4
6.4
3/8
9.5
1/2
12.7
3/4
19.1
1000
Figure 2. Typical Nameplate
CADMIUM COLORED MAIN
SPRING 14A8831X012
0 to 35 Psig (0 or
2.4 Bar) Actuator
2.4 Bar) Actuator
Input Signal (2
Input Signal (4
Springs Required)
Psi
Bar
Psi
104
3370
520
36
1340
220
15
690
30
2.1
240
940
65
1860
78
2450
92
2920
140
3600
170
12
350
530
36
610
540
37
1150
96
2910
69
1000
710
49
1000
400
28
830
160
11
350
940
65
1000
69
1000
69
1000
69
1000
560
39
660
480
33
960
540
37
1000
69
1000
of fire or explosion from venting of flam-
mable or otherwise hazardous fluid into
a closed or poorly vented location by
providing adequate ventilation.
1. Before installing the valve, inspect the valve body
and associated equipment for any damage and for any
foreign material.
2. The control valve may be installed in any orienta-
tion. However, the normal method is with the actuator
above the valve, especially for an angle configuration.
128-PQC
RED MAIN SPRING 14A9077X012
0 to 20 Psig (0 or
1.4 Bar) Actuator
1.4 Bar) Actuator
Input Signal (2
Springs Required)
Bar
Psi
Bar
232
3380
233
92
1340
92
47
700
48
16
240
16
128
1370
94
169
1540
106
201
1710
118
248
2320
160
24
42
Valve will not shut off with this
79
combination of spring and application
200
69
1000
69
69
1000
69
57
830
57
24
360
25
69
1000
69
69
1000
69
69
1000
69
69
1000
69
45
66
Valve will not shut off with this
69
combination of spring and application
69
0 to 35 Psig (0 or
2.4 Bar) Actuator
2.4 Bar) Actuator
Input Signal (4
Springs Required)
Psi
Bar
3600
248
3120
215
1720
118
710
49
2920
201
3300
227
3600
248
3600
248
1000
69
1000
69
1000
69
790
54
1000
69
1000
69
1000
69
1000
69
3