Download Print this page

Honeywell T4360G Installation Instructions

Line voltage thermostat

Advertisement

Quick Links

APPLICATION
The T4360G thermostat with on/off switch provides control of 240Vac heat only (16A) or cool only (10A)
systems with the optional indicator light operating on temperature fall. The T6360D thermostat with on/off
switch provides control of 240Vac cool only or heat only systems with the optional indicator light operating
on temperature rise. The T6360E thermostats provide control of 240Vac heat pump systems with or without
fan control.
INSTALLATION
When Installing this Product...
1.
Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a
hazardous condition.
2.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3.
Installer must be a trained, registered electrician or
service technician.
4.
After completing installation, use these instructions to
check out the product operation.
AU4360I-01
T4360G, T6360D, T6360E
Line Voltage Thermostat

INSTALLATION INSTRUCTIONS

Location
Install the thermostat about 5 ft (1.5m) above the floor in an
area with good air circulation at average temperature. See
Fig. 1.
Do not install the thermostat where it can be affected by:
— Drafts, or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
1

Advertisement

loading

Summary of Contents for Honeywell T4360G

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS APPLICATION The T4360G thermostat with on/off switch provides control of 240Vac heat only (16A) or cool only (10A) systems with the optional indicator light operating on temperature fall. The T6360D thermostat with on/off switch provides control of 240Vac cool only or heat only systems with the optional indicator light operating on temperature rise.
  • Page 2 T4360G, T6360D,E Line Voltage Thermostat Sub Base Installation The thermostat can be mounted horizontally or vertically on the wall or a wall plate/box. Refer to Figs 2 and 3. Position the sub base over the holes, pulling wires Position and level the sub base (for appearance through the wiring opening.
  • Page 3: Wiring Diagrams

    T4360G, T6360D,E Line Voltage Thermostat Wiring All wiring must comply with local electrical codes and ordinances. Refer to Figs. 4 - 8 for typical wiring. A number code is located near each terminal for identification. CAUTION 1. Loosen the terminal screws on the subbase and Disconnect power before wiring to prevent connect the fan wires (T6360E fan models only).
  • Page 4 Fig 7: T6360E1013 (Heat Pump Heat/Off/Cool Cont/Auto Fan) wiring diagram T6360E1021 SUBBASE LEADS LINE (240Vac) REVERSING COMP. VALVE OPTIONAL - LAMP CONNECTION Fig 8: T6360E1021 (Heat Pump Heat/Off/Cool Lo/Med/Hi Fan) wiring diagram Environmental Controls Honeywell 2 Richardson Place North Ryde NSW 2113 AU4360I-01...

This manual is also suitable for: