W7763C,D,E CHILLED CEILING CONTROLLERS
1. STRIP 1/2 IN. (13 MM) FROM WIRES
TO BE ATTACHED AT ONE
TERMAINAL
CHILLED WATER TEMP
OCCUPANCY SENSOR
CHANGEOVER CONTACT
AIRFLOW CONTACT
WINDOW CONTACT
MOTION SENSOR
T7560B connection to W7763
8
7
DWM
6
T7560B
5
with
integrated
4
humidity
3
sensor
2
1
Output type
Floating
1-stage
2-stage
3-stage
PWM
Thermal
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524
USA
http://www.honeywell.com
95-7485-3 Rev. 01-01
7157 286
2. TWIST WIRES TOGETHER WITH
PLIERS (A MINIMUM OF THREE
TURNS).
Fig. 7. Attaching two or more wires at terminal blocks.
HUMIDITY
24 VAC
24 VAC
24 VAC
0-10V
COM
11
1
W7763
Chilled
6
Ceiling
Wall module setpoint connection for W7763E only.
7
1
Controller
8
Wall module bypass and LED connections for W7763D and E only.
2
9
There is no logic between input 1 and 2; for example, only one of the inputs can be used for the
3
10
window contact, not both. This feature is available only with firmware version 1.0.4 or higher.
Fig. 8. Chilled Ceiling Controller terminal assignments.
Table 1. Output assignments for various actuator types.
Out 1 Terminal
13
24 Vac
open
24 Vac
on/off
24 Vac
stage 1
24 Vac
stage 1
24 Vac
PWM
24 Vac
on/off
Home and Building Control
Honeywell Limited-Honeywell Limitee
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Canada
http://www.honeywell.ca
printed in Germany
Проектирование. Монтаж. Продажа. - http://vskd.ru
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE
INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN
PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD
MECHANICAL CONNECTION.
W7763 CHILLED
CEILING CONTROLLER
1
24 VAC
2
24 VAC COM
3
OUT 1 COM
3
4
OUT 1 OPEN
3
5
OUT 1 CLOSE
6
LED
OUT 2 COM
2
BYPASS
7
OUT 2 OPEN
2
OUT 2 CLOSE
8
SETPT
1
SENSOR
9
E-BUS (LON)
GND
10
E-BUS (LON)
14
15
16
close
24 Vac
24 Vac
stage 2
24 Vac
stage 2
24 Vac
stage 3
24 Vac
24 Vac
Home and Building Control Products
Honeywell AG
Böblinger Straβe 17
D-71101 Schönaich
Germany
http://europe.hbc.honeywell.com
24 VAC
24 VAC COM
11
12
HEAT
COM
+
13
OPEN
14
CLOSE
15
16
17
18
19
L
W
ON
ORKS
20
L
W
ON
ORKS
Out 2 Terminal
17
18
open
close
on/off
stage 1
stage 2
stage 1
stage 2
stage 3
PWM
on/off
Subject to change without notice
120/240 VAC
COOL
COM
-
OPEN
CLOSE
NETWORK IN
NETWORK OUT