Troubleshooting - Toshiba VN-M150HE Installation Manual

Air to air heat exchanger
Hide thumbs Also See for VN-M150HE:
Table of Contents

Advertisement

Air to Air Heat Exchanger
14

Troubleshooting

Confirmation and check
When an error occurred in the Air to Air Heat
Exchanger, the check code and the unit No. of Air to Air
Heat Exchanger appear on the display part of the
remote controller.
The check code is only displayed during the operation.
If the display disappears, operate the Air to Air Heat
Exchanger according to the following "Confirmation of
error history" for confirmation.
* Unit No. of Air to Air Heat Exchanger is 31-OO.
Check code
Unit No. of the Air to Air Heat
Exchanger with a problem
Confirmation of error history
When an error occurred on the Air to Air Heat
Exchanger, the error history can be confirmed with the
following procedure. (The error history is stored in
memory up to 4 troubles.)
The error can be confirmed from both operating status
and stop status.
2
3
1
When pushing
and
buttons at the
same time for 4 seconds or more, the
following display appears.
If [Service check]
is displayed, the mode
enters in the trouble history mode.
• [01: Order of error history] is displayed in CODE
No. window.
• [Check code] is displayed in CHECK window.
• [Air to Air Heat Exchanger address in which an
error occurred] is displayed in Unit No.
* Unit No. of Air to Air Heat Exchanger is 31-OO.
47-EN
AMP Air Conditioning
Installation Manual
2
Every pushing of
button used to set
temperature, the error history stored in
memory is displayed in order.
The numbers in CODE No. indicate CODE No.
[01] (latest) → [04] (oldest).
REQUIREMENT
Do not push
button because all the error history of
the Air to Air Heat Exchanger will be deleted.
3
After confirmation, push
button to return
to the usual display.
1
Air to Air Heat Exchanger
Check codes and parts to be checked
Wired remote
controller
Main defective parts
display
No header remote
Remote
controller
controller
E01
Remote controller
communication error
Remote controller
Remote
E02
transmission error
controller
Indoor unit-remote
Indoor
E03
controller regular
communication error
Duplicated indoor
Indoor
E08
addresses
Duplicated header
Remote
remote controllers
controller
E09
Header indoor unit-indoor
Indoor
E18
follower unit regular
communication error
Air to Air Heat Exchanger
Air to Air Heat
F17
(TOA) error
Exchanger
Air to Air Heat Exchanger
Air to Air Heat
F18
(TRA) error
Exchanger
Indoor unit, other P.C.
Indoor
F29
board error
Duplicated header indoor
Indoor
L03
units
Indoor group address not
Indoor
L08
set
L09
Indoor power level not set Indoor
LAN communication error Indoor
L20
Other indoor unit error
Indoor
P31
* "Indoor" in "Judging device" refers to the Air to Air Heat Exchanger or the air conditioner.
– 24 –
Installation Manual
Judging
Parts to be checked / error description
device
Incorrect remote controller setting --- The header remote
controller has not been set (including two remote controllers).
No signal can be received from the indoor unit.
System interconnecting wires, indoor P.C. board, remote
controller --- No signal can be sent to the indoor unit.
Remote controller, network adapter, indoor P.C. board --- No
data is received from the remote controller or network adapter.
Indoor address setting error --- The same address as the self-
address was detected.
Remote controller address setting error --- Two remote
controllers are set as header in the double-remote controller
control.
(* The header indoor unit stops raising alarm and follower indoor
units continue to operate.)
Indoor P.C. board --- Regular communication is not possible
between header and follower indoor units or between twin
header (main) and follower (sub) units.
Outdoor Air sensor (TOA), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TOA) was detected.
Return Air sensor (TRA), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TRA) was detected.
Indoor P.C. board --- EEPROM error
Indoor address setting error --- There are two or more header
units in the group.
Indoor address setting error --- Indoor address group has not
been set.
Indoor power level has not been set.
Address setting, central control remote controller, network
adapter --- Duplication of address in central control
communication
Another indoor unit in the group is raising an alarm.
E03/L07/L03/L08 alarm check locations and error description