Raco Catalyst Addendum To Owner's Manual page 21

How to configure a catalyst ethernet/ip with rslogix 5000
Hide thumbs Also See for Catalyst:
Table of Contents

Advertisement

For a remote analog (16-bit) channel
Use SNA 1*2*40XXX
Example: 1*2*40101 for Modbus register 40101
Set the alarm condition under channel settings, Alarm Violation Criteria
Set up a "heartbeat" channel to monitor communications (recommended)
Select a channel (for example, channel 56)
SNA 1*2*01992
Alarm on 1 Raw Value, 0 reported as 0
Note:
To reset Catalyst to Factory Defaults
Turn unit off.
Locate jumper JP3 at the very top of the unit. It is just to the right of the crystal.
With the unit still off, short these two pins together and turn the unit on.
When the front panel lights begin to step through the numbers sequentially, release the short and
let the unit continue until it is finishes booting.
Saved: 2014-06-18
Filename: Catalyst Ethernet Addendum 1 1 V1_5 released
where XXX is the 16-bit register
RACO Manufacturing and
Engineering
Page 21 (21)