Connections
6 7 8
9 10
+11-
STATUS
COM
POWER
WISE Parasol EX with factory-fitted components
• WISE CU (Controller Unit)
• Temp. sensor (WISE DPS Modbus)
• Motor, air damper
Factory fitted components as an option
• Sensor Module Advanced (WISE SMA), (Optional)
• Sensor Module Basic (WISE SMB), (Optional) **
• Valves and actuators for cooling *
• Valves and actuators for heating *
• Temp. sensor
• Condensation sensor
* Supplied connected but require installing on the pipes
** Supplied but requires easy installation on the face plate.
Cable for connection of WISE SMB is prefitted on the base
module and connected on WISE CU, but requires the cable to be
connected on WISE SMB on the face plate
LED - Explanation
Not paired
Colour
Energized
White
Selected in TuneWISE
White
Prepared to be added
White
to the system
To be added to the
White
system
Paired
Colour
Normal operation
Green
Restart
Blue
Initiation
Blue
Boosted max. flow
Orange
Boosted min. flow
Orange
Boosted water flow
Violet
Boosted water flow/
Violet/Orange
air flow
WISE DPS Modbus
WISE SMA
(Optional)
WISE SMB
(Optional)
WISE Parasol EX, connection.
There are different types of actuator.
For connection of the thermal actuator
such as Swegon's actuator ACTUATORb,
see figure a.
Type
For connection of actuators with 0-10 V
Permanent
control signal, see figure b.
Flashing, fast
Flashing, slowly
Flashing, fast for 5 s
Type
Permanent
Permanent for 10 s
Flashing
Permanent
Permanent
Permanent
Alternating
23/11/2017
WISE CU
6 7 8
Ground
24 V DC
POWER
0-10 V DC
1
24 V AC
Thermal
actuator
a. Connection of thermal
actuator
Swegon reserves the right to alter specifications.
WISE Parasol EX
Motor
Pressure tube
LED
9 10
+11-
STATUS
COM
2
3
4 5
Temp. sensor
(Optional)
Valve
actuator
Condensation sensor
1 & 2
(Optional)
(Optional)
Actuator with
0-10 V con-
trol signal
b. Connection of actuator
with 0-10 V control signal
NOTE! 24 V DC supply
9