Operating Warnings; Electrical Installation - Dimplex XLE050 Instruction Manual

Xle series heater
Hide thumbs Also See for XLE050:
Table of Contents

Advertisement

OPERATING WARNINGS

IMPORTANT: Remember to observe all safety warnings and precautions when operating the
heater on the automatic or timer modes, either attended or unattended since a fi re risk exists
when the heater is accidentally covered or obstructed.
Mains cables are not provided with this heater.
CAUTION: Do not use if either of the heater's mains power leads become damaged. If the supply
cord is damaged it must be replaced by the installer or an approved Dimplex service partner.
Curtains must not come to within 250mm of the top of the heater.
Do not sit or stand on the heater
Do not place objects in contact with the heater.
To maintain stability, it is essential that the heater is placed on a level surface and care should
be taken to avoid irregular surfaces, such as may result from carpets or tiled surrounds
partially protruding under the heater.

ELECTRICAL INSTALLATION

The installation of the heater should be carried out by trained personnel.
WARNING - If the heater is installed in a room containing a bath or shower, in accordance
with the current wiring regulations, minimum clearances and IP zone requirements must
be adhered to. This product is IPX4 rated.
WARNING - The electrical installation of this heater must be carried out by a suitably qualifi ed or
trained electrician, and be in strict accordance with current wiring Regulations. The peak supply
must be connected via a switched fused spur with a fuse rated suitably for the appliances fl ex,
the off -peak supply , via a 20A double pole switch. Failure to follow these instructions will mean
that the manufacturer's instructions have not been adhered to. THERE ARE NO EXCEPTIONS.
• This heater must be earthed
• Not suitable for connection via a plug top
• Do not locate the heater immediately above or below a fi xed electrical point i.e. socket outlet.
This appliance is intended for installation to a single phase supply only.
The heater is not fi tted with a mains cable, this should be fi tted by the installer. Cable type
(minimum size) H05VV-F 1.5mm² three core for peak and 2.5mm² three core for off -peak for
connection to the fi xed wiring of the premises through suitable isolation devices positioned
adjacent to the heater. The supply circuits to the heater must incorporate a double pole isolating
switch having a contact separation of at least 3mm.
In installation the supply cord may be cut to the appropriate length for the electrical connection
point. Excess cable should not be inserted or stored behind the heater.
If, during reassembly of the heater, a part of the thermal insulation shows damage or deterioration,
it should be replaced by an identical part.
WARNING: All electrical connections to the terminal block must be secure to prevent risk of
ignition. Tighten to 0.5 Nm.
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xle100Xle070Xle125Xle150

Table of Contents