Drain pipe and Drain hose Installation (Continued)
20
E-
Drainpipe Connection
Without the drain pump
1
Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger
space of 1.0~1.5m.
2
Install U-trap at the end of the drainpipe to prevent a nasty smell to reach
the indoor unit.
3
Do not install the drainpipe to upward position. It may cause water flow back
to the unit.
1~1.5m
Flexible hose
Horizontal drainpipe
Ceiling
more than 1/100 slope
Hanger