Performing Leak Test & Insulation (Continued)
Insulation
Gas pipe
10mm
10mm
Gas pipe
18
E-
2
Select the insulation of the refrigerant pipe.
 Insulate the gas side and liquid side pipe referring to the thickness
according to the pipe size.
 The thickness according to the pipe size is a standard of the indoor tem-
perature of 27°C and humidity of 80%.
If installing in an unfavorable conditions, use thicker one.
 Insulation's heat-resistance temperature should be more than 120℃.
Ø 6.35~ Ø15.88
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
 You can contact the gas side and liquid side pipes but the pipes
Insulation
should not be pressed.
When contacting the gas side and gas side pipe, use 1 grade thicker
insulation.
Liquid pipe
Refrigerant pipe after EEV kit and MCU
Install the gas side and liquid side pipes, leave 10mm of space.
10mm
When contacting the gas side and liquid side pipe, use 1 grade
thicker insulation.
Liquid pipe
Install the insulation not to get wider and use the adhesives
on the connection part of it to prevent moisture from entering.
Wind the refrigerant pipe with insulation tape if it is exposed to
outside sunlight.
Install the refrigerant pipe respecting that the insulation does not
get thinner on the bent part or hanger of pipe.
Add the additional insulation if the insulation plate gets thinner.
Additional insulation
Minimum thickness
Pipe size
of insulation
(mm)
(mm)
PE foam
EPDM foam
13
10
-
25
19
Hanger
a
Refrigerant pipe insulation
a×3
Remarks
If you install the pipe underground,
at the seaside, a spa or on the lake,
use 1 grade thicker one according
to the pipe size.