T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS
1 2 3 4 5 6 7
2-11/16 (68)
3-7/8 (97)
3-15/16 (99)
Fig. 3. T7460A,B,C,D,E,F dimensions in in. (mm)

Mounting Procedure

1. Disassemble the cover as is shown in Fig. 1.
2. (T7460B,C,D,E,F only) Remove the setpoint dial by
pulling it off.
3. a) Mount the wall module onto the wall outlet box,
or
b) bore wall holes as is specified in Fig. 2 and mount
the wall module with appropriate screws.
4. Connect the wires to the terminal block according to the
specifications in the "Wiring" section.
5. (T7460B,C,D,E,F only) Insert the setpoint dial and turn
it clockwise as far as possible.
6. (T7460B,C,D,E,F only) Make sure that the dial's
position is such that the 30 (Celsius absolute scale) or
the +5 (Celsius relative scale) point to the right-hand
side of the wall module (see Fig. 4).
Fig. 4. Mounting position of setpoint dial
EN1B-0291GE51 R1111B
7. (T7460B,C,D,E,F, only) If the dial does not have the
correct position, pull the dial off again and reinsert it
with the correct orientation.
8. Remount the cover as depicted in Fig. 5 and make sure
that the tab on the underside engages.
1-1/16
(27)
Fig. 5. Mounting cover of T7460 wall modules
Wiring
Attach the wires from the device sensor terminals to the
appropriate wall module terminals and set the jumpers
according to the connected controller. See Fig. 6 through
Fig. 8.
1-3/16
IMPORTANT
(30)
Screw type terminal blocks are designed to accept
no more than one 16 AWG (1.5 mm
Wire the terminal blocks as follows:
1. Strip 3/16 in. (5 mm) of insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Verify jumper setting with Fig. 8 and wall module wiring
with Fig. 6 and Fig. 7.
2
) conductor.
2

Advertisement

loading