31 Automatic Reset - ABB ACS150 series User Manual

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

112
Parameters in the Long parameter mode
Index Name/Selection
3023
WIRING FAULT
0 = DISABLE
1 = ENABLE

31 AUTOMATIC RESET

3101
NR OF TRIALS
0...5
3102
TRIAL TIME
1.0...600.0 s
3103
DELAY TIME
0.0...120.0 s
3104
AR OVERCURRENT
0 = DISABLE
1 = ENABLE
3105
AR OVERVOLTAGE
0 = DISABLE
1 = ENABLE
3106
AR UNDERVOLTAGE
0 = DISABLE
1 = ENABLE
Actual signals and parameters
Description
Selects how the drive reacts when incorrect input power and motor cable
connection is detected (that is the input power cable is connected to the
motor connection of the drive).
Note: Disabling wiring fault (ground fault) may void the warranty.
No action
The drive trips on fault
OUTP WIRING
Automatic fault reset. Automatic resets are possible only for certain fault
types and when the automatic reset function is activated for that fault type.
Defines the number of automatic fault resets the drive performs within the
time defined by parameter
If the number of automatic resets exceeds the set number (within the trial
time), the drive prevents additional automatic resets and remains stopped.
The drive must be reset from the control panel or from a source selected by
parameter
1604
FAULT RESET SEL.
Example: Three faults have occurred during the trial time defined by
parameter
3102
TRIAL TIME. Last fault is reset only if the number defined
by parameter 3101 NR OF TRIALS is 3 or more.
Trial time
X
X X
Number of the automatic resets
Defines the time for the automatic fault reset function. See parameter
NR OF TRIALS.
Time
Defines the time that the drive waits after a fault before attempting an
automatic reset. See parameter
zero, the drive resets immediately.
Time
Activates/deactivates the automatic reset for the overcurrent fault.
Automatically resets fault
OVERCURRENT
by parameter
3103
DELAY TIME.
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault. Automatically resets fault
after the delay set by parameter
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
undervoltage fault. Automatically resets fault
F0006) after the delay set by parameter
Inactive
Active
(code F0035).
3102
TRIAL TIME.
t
x = Automatic reset
3101
NR OF TRIALS. If delay time is set to
(code: F0001) after the delay set
DC OVERVOLT
3103
DELAY TIME.
DC UNDERVOLT
3103
DELAY TIME.
Def
1 = ENABLE
0
3101
30.0 s
0.0 s
0 = DISABLE
0 = DISABLE
(code: F0002)
0 = DISABLE
(code: