1.0 Quick-Start Guide

1.1
Upon Receipt of Equipment
All equipment shipped by General Monitors is packaged in shock absorbing containers,
which provides considerable protection against physical damage. The contents should
be carefully removed and checked against the packing slip. If any damage has
occurred or if there is any discrepancy in the order, notify General Monitors as soon as
possible. All subsequent correspondence with General Monitors must specify the
equipment part and serial numbers.
Each Model 4802A is completely checked at the factory; however, a complete checkout
is necessary upon initial installation and start-up to ensure system integrity.
1.2
Sensor Location Considerations
There are no standard rules for sensor placement, since the optimum sensor location is
different for each application. The customer must evaluate conditions at the sensor site
in order to make this determination.
WARNING – Installation and Maintenance must be carried out by suitably skilled and
competent personnel only.
1.2.1 General Sensor Location Considerations
• The sensor should be easily accessible for calibration checks. Ensure that sufficient
clearance exists to allow the use of field calibration devices.
• The sensor head should always be pointing down to prevent water build up on the
sensing element. Remember that some combustible gases are heavier than air;
however, do not rely too heavily on this fact when selecting a sensor position.
• The sensor should be located in areas where leaks are suspected (i.e. near valves
& pipe connections, etc.).
• The sensor should not be placed where contaminating substances may coat it.
1.3

Sensor Poisons

Sensors may be adversely affected by prolonged exposure to certain atmospheres.
The more important poisons are:
• Prolonged exposure to Hydrogen Sulfide (H
• Halides (compounds containing Fluorine, Chlorine, Bromine and Iodine)
• Heavy Metals (e.g. Tetraethyl lead)
Silicones contained in greases or aerosols are the most common "coating" agents.
These are not true sensor poisons, but reduce sensor response. Other damaging
materials, which attack the sensor physically, include mineral acids and caustic vapors.
The presence of such poisons and vapors does not exclude the use of General
Monitors Catalytic Bead Sensors. A careful analysis of ambient conditions should be
undertaken and the customer should be aware that sensor calibration might need to
occur at more frequent intervals.