Setup & Setup Check Modes
The Setup Check Mode allows the operator to view the selected options for the module
without allowing any changes to be made. Once this mode has been entered, the
module will automatically display each of the selected options for a short period of time
and then it will return to normal operation. The Setup Mode allows the operator to
change the operating parameters by making choices for selected options.
The Setup Check & Setup Modes display identical information with the following
exceptions:
• The Setup Check Mode allows the user to view the operating parameters of the
Model 4802A, whereas the Setup Mode allows the user to change the operating
parameters of the Model 4802A.
• Entering the optional Password is only available in the Setup Mode.
• The Inhibit Mode may only be entered from the Setup Mode. If the Inhibit Mode is
entered, the A1 & A2 outputs will be inhibited until the Mode/Select switch is
pressed.
NOTE - The Setup and Setup Check Modes cannot be entered if the unit is in alarm or
fault.
During the Setup Mode the operator will be allowed to select options.
The selection procedure is the same for most of the options. Pressing the Mode/Select
Switch toggles the available choices. When the display has indicated a choice for five
consecutive seconds, without the operator pressing the Mode/Select Switch, the Setup
routine will accept that selection and move on to the next option available.
NOTE - Before entering the Setup Mode to make changes, the user should fill out the
form and become familiar with the block diagram, Section 5.6, of this manual. This will
aid the user during the selection process in the Setup Mode.
The Password, the A1 & A2 Alarm set points and the calibration level options offer the
operator more than two choices. While these options are being selected, pressing the
Mode/Select Switch repeatedly will sequence the display to the next available choice
for that option.
To Enter the Setup Check Mode or the Setup Mode. Press and hold the Mode/Select
switch until the SETUP LED begins flashing (about twenty seconds). When the SETUP
LED is flashing, release the Mode/Select switch to enter the Setup Check Mode
(Figure 47). Continuing to press and hold the Mode/Select switch until the SETUP LED
stops flashing (about five seconds more) will allow the operator to enter the Setup
Mode. When the SETUP LED stops flashing and stays on, release the Mode/Select
switch and the unit will enter the Setup Mode (Figure 47).