Page 3
GEK-113550A (revision V2) but are not included in the current F35 operations. The following functions and items are not yet available with the current version of the F35 relay: • N/A.
1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-6 1.3.2 INSTALLATION....................1-6 1.3.3 CONFIGURING THE F35 FOR SOFTWARE ACCESS ........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............. 1-10 1.3.5 CONNECTING TO THE F35 RELAY ............... 1-16 1.4 UR HARDWARE 1.4.1...
Page 8
7.1.2 VIRTUAL INPUTS ....................7-1 7.1.3 CLEAR RECORDS .....................7-2 7.1.4 SET DATE AND TIME ..................7-2 7.1.5 RELAY MAINTENANCE ..................7-3 7.2 TARGETS 7.2.1 TARGETS MENU ....................7-4 7.2.2 TARGET MESSAGES ..................7-4 7.2.3 RELAY SELF-TESTS ..................7-4 viii F35 Multiple Feeder Protection System GE Multilin...
Page 9
OBTAINING RELAY FILES VIA MODBUS ............B-6 B.3.2 MODBUS PASSWORD OPERATION ...............B-7 B.4 MEMORY MAPPING B.4.1 MODBUS MEMORY MAP .................B-8 B.4.2 DATA FORMATS .....................B-65 C. IEC 61850 C.1 OVERVIEW COMMUNICATIONS C.1.1 INTRODUCTION....................C-1 C.1.2 COMMUNICATION PROFILES .................C-1 GE Multilin F35 Multiple Feeder Protection System...
Page 10
BINARY INPUT POINTS ................... E-8 E.2.2 BINARY AND CONTROL RELAY OUTPUT............E-9 E.2.3 COUNTERS..................... E-10 E.2.4 ANALOG INPUTS.................... E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY..................F-1 F.1.2 CHANGES TO THE MANUAL ................F-2 F35 Multiple Feeder Protection System GE Multilin...
Page 11
TABLE OF CONTENTS F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-8 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-10 INDEX GE Multilin F35 Multiple Feeder Protection System...
Page 12
TABLE OF CONTENTS F35 Multiple Feeder Protection System GE Multilin...
Product disassembly and repairs are not permitted. All service needs to be conducted by the factory. This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial environments. Not to be used near electronic devices rated for Class B levels. GE Multilin F35 Multiple Feeder Protection System...
• Mounting screws. For product information, instruction manual updates, and the latest software updates, please visit the GE Grid Solutions website. If there is any noticeable physical damage, or any of the contents listed are missing, contact GE Multilin immedi- ately. NOTE...
This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. GE Multilin...
(dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. F35 Multiple Feeder Protection System GE Multilin...
Employing OOD/OOP in the software architecture of the F35 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes.
Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the F35 and the EnerVista UR Setup software. • US Robotics external 56K FaxModem 5686 •...
OVERVIEW The user can connect remotely to the F35 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The F35 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
Page 20
• To configure the F35 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ethernet communications.
Page 21
SERIAL PORTS 10. Click the Read Order Code button to connect to the F35 device and upload the order code. If an communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the F35 from a laptop through Ethernet, first assign an IP address to the relay from the front panel keyboard.
Page 23
Now, assign the laptop computer an IP address compatible with the relay’s IP address. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window. Right-click the Local Area Connection icon and select Properties. GE Multilin F35 Multiple Feeder Protection System 1-11...
Page 24
Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the F35 relay and the last number dif- ferent (in this example, 1.1.1.2).
Page 25
Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: Verify the physical connection between the F35 and the laptop computer, and double-check the programmed IP address in setting, then repeat step 2 in the above procedure.
Page 26
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the F35 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gegridsolutions.com/multilin). See the Software Installation section for installation details.
Page 27
Set the computer to “Obtain a relay address automatically” as shown below. If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the F35 relay. AUTOMATIC DISCOVERY OF ETHERNET DEVICES The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether- net network.
The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using F35 relays. From the online window, users can select which relay to interro- gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func- tions are available: •...
Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the F35 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the F35 rear communications port.
LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed 1-18 F35 Multiple Feeder Protection System GE Multilin...
See the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. GE Multilin F35 Multiple Feeder Protection System 1-19...
1 GETTING STARTED 1.5.7 COMMISSIONING The F35 requires a minimum amount of maintenance when it is commissioned into service. Since the F35 is a microproces- sor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus TCP, and TFTP protocols, and allows access to the relay via any standard web browser (F35 web pages). The IEC 60870- 5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
2.1.2 ORDERING a) OVERVIEW The F35 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Page 35
2.1 INTRODUCTION b) ORDER CODES WITH TRADITIONAL CTS AND VTS The order codes for the horizontal mount units with traditional CTs and VTs are shown below. Table 2–3: F35 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount...
Page 36
2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below. Table 2–4: F35 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
Page 37
RS422, 2 Channels The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–6: F35 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face- plate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the F35 relay. Only the modules specified in the order codes are available as replacement modules.
Page 39
4 dcmA inputs, 4 dcmA outputs (only one 5A or 5D module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5A or 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs GE Multilin F35 Multiple Feeder Protection System...
Page 40
4 dcmA inputs, 4 dcmA outputs (only one 5A or 5D module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5A or 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs F35 Multiple Feeder Protection System GE Multilin...
Timing accuracy: Operate at < 0.90 × pickup ±3.5% of operate time or ±4 ms (which- ever is greater) Operate time: <30 ms at 0.9 pickup at 60 Hz for Defi- nite Time mode GE Multilin F35 Multiple Feeder Protection System...
Time delay: 0 to 65535 ms in steps of 1 NAND (2 to 16 inputs), latch (reset-domi- nant), edge detectors, timers Inputs: any logical variable, contact, or virtual input Number of timers: 2-10 F35 Multiple Feeder Protection System GE Multilin...
FlexLogic™ equa- put change of state; self-test events tion Data storage: in non-volatile memory Data: AC input channels; element state; digital input state; digital output state Data storage: in non-volatile memory GE Multilin F35 Multiple Feeder Protection System 2-11...
±2.0% of reading mum measured currents Range: ±0 to 1 × 10 Mvarh 3-Phase Power (P, Q, and S) present and maximum measured currents Parameters: three-phase only Accuracy: ±2.0% Update rate: 50 ms 2-12 F35 Multiple Feeder Protection System GE Multilin...
Duration of auto-burnish impulse: 25 to 50 ms No. of remote devices: Default states on loss of comms.: On, Off, Latest/Off, Latest/On Ring configuration: Data rate: 64 or 128 kbps CRC: 32-bit GE Multilin F35 Multiple Feeder Protection System 2-13...
95% voltage drop across the load impedance. Trickle current: approx. 1 to 2.5 mA Operate time: < 0.6 ms FORM-A CURRENT MONITOR Internal Limiting Resistor: 100 Ω, 2 W Threshold current: approx. 80 to 100 mA 2-14 F35 Multiple Feeder Protection System GE Multilin...
Page 47
±300 Vpk Internal fuse: 5 A / 350 V AC, Ceramic, Axial SLO REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE) BLO; Standard output points: 32 Manufacturer: Conquer; Part number: SCD-A 005 User output points: GE Multilin F35 Multiple Feeder Protection System 2-15...
Shielded twisted pair: 150 m (492 ft.) MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS 10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) 2-16 F35 Multiple Feeder Protection System GE Multilin...
At extreme temperatures these values deviate based on component tolerance. On average, the output power decreases as the temperature is increased by a factor 1dB / 5°C. GE Multilin F35 Multiple Feeder Protection System 2-17...
Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-18 F35 Multiple Feeder Protection System GE Multilin...
Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin F35 Multiple Feeder Protection System 2-19...
Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors. NOTE 2-20 F35 Multiple Feeder Protection System GE Multilin...
HORIZONTAL UNITS The F35 Multiple Feeder Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
Page 54
VERTICAL UNITS The F35 Multiple Feeder Protection System is available as a reduced size (¾) vertical mount unit, with a removable face- plate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate con- tains additional user-programmable pushbuttons and LED indicators.
Page 55
RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.015” 7.482” 1.329” 13.560” 15.000” 14.025” 4.000” 9.780” 843809A1.CDR Figure 3–4: F35 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin F35 Multiple Feeder Protection System...
Page 56
UR S RI S UR S RI S Figure 3–5: F35 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting F35 devices with the enhanced front panel, refer to the following documents available online from the GE Grid Solutions website. •...
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the F35. F35 Multiple Feeder Protection System...
Page 59
All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con- nectors must be individually disconnected from the module before it can be removed from the chassis. NOTE GE Multilin F35 Multiple Feeder Protection System...
3.1 DESCRIPTION 3 HARDWARE The 4.0x release of the F35 relay includes new hardware modules.The new CPU modules are specified with codes 9E and higher. The new CT/VT modules are specified with the codes 8F and higher. NOTE The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old CPUs.
Page 61
(rows 1 to 8), use a minimum of 17 inch-pounds. During manufacturing, the power supply and CPU modules are installed in slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. GE Multilin F35 Multiple Feeder Protection System...
No. 10AWG MODULE ARRANGEMENT Minimum GROUND BUS MODULES MUST BE Inputs/ CT/VT Inputs/ Inputs/ Power GROUNDED IF outputs outputs outputs Supply TERMINAL IS PROVIDED (Rear View) Figure 3–12: TYPICAL WIRING DIAGRAM 3-10 F35 Multiple Feeder Protection System GE Multilin...
(see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the F35 has a redundant option in which two F35 power supplies are placed in parallel on the bus.
Figure 3–13: CONTROL POWER CONNECTION When using an SH/SL power supply module or a F35 with the HardFiber system, before powering off the F35, save data in the compact flash memory using Commands > Relay Maintenance > Save Non-Volatile Data. When not NOTE saved or the relay loses power, up to the last two minutes of data is not saved to the compact flash memory.
Page 65
NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING GE Multilin F35 Multiple Feeder Protection System 3-13...
3.2.5 PROCESS BUS MODULES The F35 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
Page 67
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number sign “#” appears, substitute the contact number NOTE GE Multilin F35 Multiple Feeder Protection System 3-15...
Page 69
~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin F35 Multiple Feeder Protection System 3-17...
Page 70
3.2 WIRING 3 HARDWARE Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 F35 Multiple Feeder Protection System GE Multilin...
Page 71
CONTACT IN COMMON SURGE 842763A2.CDR Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) Observe correct polarity for all contact input and solid state output connections for proper functional- ity. GE Multilin F35 Multiple Feeder Protection System 3-19...
Page 72
F35 input even when the output is open, if there is a substantial distributed capacitance (represented by C1) present in the wiring between the output and the F35 input and the debounce time setting in the F35 relay is low enough.
Page 73
This operation of contact inputs also can be prevented by using the Auto-Burnish contact inputs or contact inputs with active impedance. Figure 3–21: CONTACT INPUT CONNECTED TO A CONTACT OUTPUT WITH RESISTOR (R2) ACROSS THE INPUT GE Multilin F35 Multiple Feeder Protection System 3-21...
Page 74
(EQ 3.2) The 2 mA current is used in case the contact input is connected across the GE Form A contact output with voltage monitoring. Otherwise use the amperage of the active circuit connected to the contact input when its contact output is open and the voltage across the contact input is third trigger threshold to calculate the resistor value.
Page 75
(refer to the Contact Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources. Con- sequently, the threshold voltage setting is also defined per group of two contact inputs. GE Multilin F35 Multiple Feeder Protection System 3-23...
Page 76
Contact inputs susceptible to parasitic capacitance caused by long cable runs affected by switching surges from external circuits can result in inadvertent activation of contact inputs with the external contact open. In this case, GE recommends using the digital I/O module with active impedance circuit.
Page 77
3 HARDWARE 3.2 WIRING Figure 3–24: ACTIVE IMPEDANCE CONTACT INPUT V-I CHARACTERISTIC GE Multilin F35 Multiple Feeder Protection System 3-25...
(5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–25: TRANSDUCER INPUT/OUTPUT MODULE WIRING 3-26 F35 Multiple Feeder Protection System GE Multilin...
3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the F35 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
Page 80
For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–” terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared 3-28 F35 Multiple Feeder Protection System GE Multilin...
Page 81
This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the F35 COM terminal (#3); others function cor- rectly only if the common wire is connected to the F35 COM terminal, but insulated from the shield.
Page 82
In order to engage or disengage the ST type connec- tor, only a quarter turn of the coupling is required. 3-30 F35 Multiple Feeder Protection System GE Multilin...
UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–30: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping. NOTE GE Multilin F35 Multiple Feeder Protection System 3-31...
3.3.1 DESCRIPTION The F35 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the communications channels provided by these modules to exchange digital state information between relays.
Page 85
These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules may be applicable to the F35 relay. Only the modules specified in the order codes are available as direct input and output communications modules.
Page 86
Channel 1: G.703, channel 2: 1300 nm, single-mode, laser G.703, 1 channel G.703, 2 channels RS422, 1 channel RS422, 2 channels, 2 clock inputs RS422, 2 channels Observing any fiber transmitter output can cause eye injury. 3-34 F35 Multiple Feeder Protection System GE Multilin...
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. GE Multilin F35 Multiple Feeder Protection System 3-35...
Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. 3-36 F35 Multiple Feeder Protection System GE Multilin...
Page 89
For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). GE Multilin F35 Multiple Feeder Protection System 3-37...
Page 90
G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–41: G.703 DUAL LOOPBACK MODE 3-38 F35 Multiple Feeder Protection System GE Multilin...
1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin F35 Multiple Feeder Protection System 3-39...
Page 92
Figure 3–44: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the F35 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer.
When using a laser interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–47: G.703 AND FIBER INTERFACE CONNECTION GE Multilin F35 Multiple Feeder Protection System 3-41...
5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of F35 communi- cation for two and three terminal applications.
Page 95
Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. GE Multilin F35 Multiple Feeder Protection System 3-43...
Page 96
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE Figure 3–48: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-44 F35 Multiple Feeder Protection System GE Multilin...
5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of F35 communi- cation for two and three terminal applications.
Page 98
Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-46 F35 Multiple Feeder Protection System GE Multilin...
Page 99
3 HARDWARE 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS Figure 3–49: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin F35 Multiple Feeder Protection System 3-47...
The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod- ules with revisions 5.5x and higher. The modules communicate to the F35 through an internal Ethernet port (referred to as the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST 100Base-FX ports.
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net- work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified. Do not connect to network while configuring the switch module. GE Multilin F35 Multiple Feeder Protection System 3-49...
Page 102
SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE The F35 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con- tains the advanced configuration details for the switch not contained within the standard F35 settings file.
Page 103
Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open. The settings file will be transferred to the Ethernet switch and the settings uploaded to the device. GE Multilin F35 Multiple Feeder Protection System 3-51...
NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
Page 105
Select the firmware file to be loaded on to the Switch, and select the Open option. The following window will pop up, indicating that the firmware file transfer is in progress. If the firmware load was successful, the following window will appear: Note GE Multilin F35 Multiple Feeder Protection System 3-53...
No setting required; the F35 EQUIPMENT The F35 has not detected the The F35 failed to see the switch module will read the state of a general MISMATCH: Card XXX presence of the Ethernet on power-up, because switch won’t...
To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV- ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the F35 section in Chapter 1 for details.
Page 108
Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a F35 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. 842786A3.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin F35 Multiple Feeder Protection System...
(settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the F35 firmware are at ver- sions 5.40 or higher.
Page 111
ADDING PASSWORD PROTECTION TO A TEMPLATE GE recommends that templates be saved with password protection to maximize security. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
Page 112
Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F35 Multiple Feeder Protection System GE Multilin...
Page 113
Once a settings template is removed, it cannot be reapplied and a new settings template needs to be defined before use. Right-click the device in the Online or Offline Window area and select the Template Mode > Remove Template option. Enter the template password and click OK to continue. GE Multilin F35 Multiple Feeder Protection System...
Select the Template Mode > View In Template Mode option to view the template. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode > Pass- word Protect Template option. F35 Multiple Feeder Protection System GE Multilin...
Page 115
A serial number is viewable under Actual Values > Product Info > Model Information, the inside front panel, and the rear of the device. GE Multilin F35 Multiple Feeder Protection System...
When a settings file is transfered to a F35 device, the date, time, and serial number of the F35 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the F35 actual values at any later date to determine if security has been compromised.
Page 117
With respect to the above diagram, the traceability feature is used as follows. The transfer date of a setting file written to a F35 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
Page 118
ONLINE DEVICE TRACEABILITY INFORMATION The F35 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin F35 Multiple Feeder Protection System 4-13...
The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 F35 Multiple Feeder Protection System GE Multilin...
Page 121
Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every F35, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
Page 122
LEDs on these panels. USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS 842782A1.CDR Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE) DEFAULT LABELS FOR LED PANEL 2: The default labels are intended to represent: 4-16 F35 Multiple Feeder Protection System GE Multilin...
EnerVista UR Setup software is installed and operational. • The F35 settings have been saved to a settings file. • The F35 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed. •...
Page 124
Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the F35 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
Page 125
4.3 FACEPLATE INTERFACE Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the F35 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
Page 126
Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the F35 enhanced front panel and insert the custom labels.
Page 127
Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin F35 Multiple Feeder Protection System 4-21...
Page 128
The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
4.3.6 BREAKER CONTROL a) INTRODUCTION The F35 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 F35 Multiple Feeder Protection System GE Multilin...
Page 131
Display Properties. TIME: 1.0 s To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% GE Multilin F35 Multiple Feeder Protection System 4-25...
Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. 4-26 F35 Multiple Feeder Protection System GE Multilin...
When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The F35 supports password entry from a local or remote connection. GE Multilin F35 Multiple Feeder Protection System...
Page 134
When an incorrect command or setting password has been entered via the faceplate interface three times within a 3-minute time span, the FlexLogic™ operand will be set to “On” and the F35 will not allow settings or com- LOCAL ACCESS DENIED...
Page 135
FlexLogic™ operand will be set to “On” and REMOTE ACCESS DENIED the F35 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
Page 136
4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-30 F35 Multiple Feeder Protection System GE Multilin...
See page 5-59. TELEPROTECTION See page 5-67. INSTALLATION See page 5-67. SETTINGS AC INPUTS See page 5-70. SYSTEM SETUP POWER SYSTEM See page 5-71. GE Multilin F35 Multiple Feeder Protection System...
SELECTOR SWITCH See page 5-135. UNDERFREQUENCY See page 5-141. AUTORECLOSE See page 5-142. DIGITAL ELEMENTS See page 5-148. DIGITAL COUNTERS See page 5-151. F35 Multiple Feeder Protection System GE Multilin...
Page 139
IEC 61850 See page 5-180. GOOSE UINTEGERS SETTINGS DCMA INPUTS See page 5-181. TRANSDUCER I/O RTD INPUTS See page 5-182. DCMA OUTPUTS See page 5-184. GE Multilin F35 Multiple Feeder Protection System...
FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all options become available. • NAME setting: This setting is used to uniquely identify the element. F35 Multiple Feeder Protection System GE Multilin...
BACKGROUND The F35 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail- ure element.
Page 142
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > F35 Multiple Feeder Protection System GE Multilin...
Page 143
CTs on each of two breakers is required to measure the winding current flow. GE Multilin F35 Multiple Feeder Protection System...
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F35, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
Page 145
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the Settings > Product Setup > Password Security menu item to open the remote password settings window. Figure 5–2: REMOTE PASSWORD SETTINGS WINDOW GE Multilin F35 Multiple Feeder Protection System...
Page 146
INVALID ATTEMPS BEFORE LOCKOUT The F35 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
Page 147
ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time- out is restarted. The status of this timer is updated every 5 seconds. GE Multilin F35 Multiple Feeder Protection System 5-11...
DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. 5-12 F35 Multiple Feeder Protection System GE Multilin...
Page 149
Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The F35 applies a cut- off value to the magnitudes and angles of the measured currents.
Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program- mable pushbuttons to clear specific records are typical applications for these commands. Since the F35 responds to rising edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
0 ms The F35 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port.
Page 152
MODBUS SLAVE ADDRESS grammed. For the RS485 ports each F35 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
Page 153
5 SETTINGS 5.2 PRODUCT SETUP Changes to the setting do not take effect until the F35 is restarted. MODBUS TCP PORT NUMBER NOTE e) DNP PROTOCOL PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL Range: see sub-menu below ...
Page 154
TIMEOUT: 120 s The F35 supports the Distributed Network Protocol (DNP) version 3.0. The F35 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the F35 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the F35 at one time.
Page 155
DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the F35 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
Page 156
0 to 32 binary output paired controls. Points not configured as paired operate on POINTS a one-to-one basis. setting is the DNP slave address. This number identifies the F35 on a DNP communications link. Each DNP ADDRESS DNP slave should be assigned a unique address.
Page 157
The F35 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The F35 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
Page 158
IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In F35 releases previous to 5.0x, this name string was repre- sented by the setting.
Page 159
DESTINATION MAC address; the least significant bit of the first byte must be set. In F35 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the F35) and setting the multicast bit.
Page 160
The F35 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
Page 161
Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. GE Multilin F35 Multiple Feeder Protection System 5-25...
Page 162
MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The F35 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
Page 163
IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The F35 must be rebooted (control power removed and re-applied) before these settings take effect.
Page 164
CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the F35. Clients will still be able to connect to the server (F35 relay), but most data values will not be updated.
Page 165
(_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the F35 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
Page 166
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the F35 virtual inputs.
Page 167
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the F35. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the GGIO5 integer inputs.
Page 168
Changes to the report configuration take effect when the F35 is restarted. Disconnect any IEC 61850 client connection to the F35 prior to making setting changes to the report configuration. Disconnecting the rear Ethernet connection from the F35 disconnects the IEC 61850 client connection.
Page 169
NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F35 over a network. The F35 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the F35 contains a list and description of all available files (event records, oscillography, etc.).
Page 170
ENABLED: No The F35 supports the IEC 60870-5-104 protocol. The F35 can be used as an IEC 60870-5-104 slave device connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F35 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the F35 at one time.
Page 171
F35 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the F35 to signal an SNTP self-test error if the server is offline.
Page 172
MESSAGE (Modbus register address range) Fast exchanges (50 to 1000 ms) are generally used in control schemes. The F35 has one fast exchange (Exchange 1) and two slow exchanges (Exchanges 2 and 3). The settings menu for the slow EGD exchanges is shown below: ...
EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any data from the F35 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format.
SNTP, the offset is used to determine the local time for the F35 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the F35 clock can follow the DST rules of the local time zone.
Z0 ANGLE: 75° The F35 relay supports one fault report and an associated fault locator per CT bank to a maximum of 5. The signal source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu.
Page 176
It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). 5-40 F35 Multiple Feeder Protection System GE Multilin...
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. GE Multilin F35 Multiple Feeder Protection System 5-41...
Page 178
IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. 5-42 F35 Multiple Feeder Protection System GE Multilin...
The relay automatically partitions the available memory between the channels in use. Exam- ple storage capacities for a system frequency of 60 Hz are shown in the following table. GE Multilin F35 Multiple Feeder Protection System 5-43...
Page 180
– entering this number via the relay keypad will cause the corresponding parameter to be displayed. • DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to “Off” without over-writing old data. 5-44 F35 Multiple Feeder Protection System GE Multilin...
Start Demand Interval logic input pulses. Each new value of demand becomes available at the end of each pulse. Assign a FlexLogic™ operand to the setting to program the input for the new DEMAND TRIGGER demand interval pulses. GE Multilin F35 Multiple Feeder Protection System 5-45...
LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress. 5-46 F35 Multiple Feeder Protection System GE Multilin...
Page 183
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This is to be performed via user-programmable pushbutton 1. GE Multilin F35 Multiple Feeder Protection System 5-47...
Page 184
“Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com- munications channel, or from any programmed operand, even if the LED operand state de-asserts. 5-48 F35 Multiple Feeder Protection System GE Multilin...
ANY SELF-TEST mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. GE Multilin F35 Multiple Feeder Protection System 5-49...
The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–5: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the F35 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
Page 187
PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled GE Multilin F35 Multiple Feeder Protection System 5-51...
Page 188
5.2 PRODUCT SETUP 5 SETTINGS The F35 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number depends on the front panel ordered.
Page 189
This setting is applicable only if the user-programmable pushbutton is in "Latched" mode. • PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable only if the pushbutton is in “Latched” mode. GE Multilin F35 Multiple Feeder Protection System 5-53...
Page 190
To allow front panel keypad operation, when a keypad button is pressed the message is supressed for 10 seconds. • PUSHBUTTON 1 EVENTS: If this setting is enabled, each user-programmable pushbutton state change is logged as an event into the event recorder. 5-54 F35 Multiple Feeder Protection System GE Multilin...
Page 191
5 SETTINGS 5.2 PRODUCT SETUP The figures show the user-programmable pushbutton logic. Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin F35 Multiple Feeder Protection System 5-55...
Page 192
16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers. 5-56 F35 Multiple Feeder Protection System GE Multilin...
Page 193
INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin F35 Multiple Feeder Protection System 5-57...
Page 194
4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-58 F35 Multiple Feeder Protection System GE Multilin...
Page 195
On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output GE Multilin F35 Multiple Feeder Protection System 5-59...
Page 196
Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. 5-60 F35 Multiple Feeder Protection System GE Multilin...
Page 197
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. GE Multilin F35 Multiple Feeder Protection System 5-61...
Page 198
UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–13: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. 5-62 F35 Multiple Feeder Protection System GE Multilin...
Page 199
The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin F35 Multiple Feeder Protection System 5-63...
Page 200
Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. 5-64 F35 Multiple Feeder Protection System GE Multilin...
Page 201
EVENTS: Disabled The F35 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
Page 202
MESSAGE EVENTS: Disabled The F35 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
Page 203
TERMINAL 1 ID NUMBER 5.2.19 INSTALLATION PATH: SETTINGS PRODUCT SETUP INSTALLATION Range: Not Programmed, Programmed INSTALLATION RELAY SETTINGS: Not Programmed Range: up to 20 alphanumeric characters RELAY NAME: MESSAGE Relay-1 GE Multilin F35 Multiple Feeder Protection System 5-67...
Page 204
This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. 5-68 F35 Multiple Feeder Protection System GE Multilin...
Page 205
Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the F35 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
Page 206
1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-70 F35 Multiple Feeder Protection System GE Multilin...
Page 207
Range: ABC, ACB PHASE ROTATION: MESSAGE Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6 FREQUENCY AND PHASE MESSAGE REFERENCE: SRC 1 Range: Disabled, Enabled FREQUENCY TRACKING: MESSAGE Enabled GE Multilin F35 Multiple Feeder Protection System 5-71...
Page 208
FREQUENCY TRACKING cial variable-frequency applications. NOTE The frequency tracking feature will function only when the F35 is in the “Programmed” mode. If the F35 is “Not Pro- grammed”, then metering values will be available but may exhibit significant errors. NOTE 5.4.3 SIGNAL SOURCES...
Page 209
An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration: INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 GE Multilin F35 Multiple Feeder Protection System 5-73...
Page 210
CT/VT inputs that are used to provide the data. DSP Bank Source 1 Source 2 Amps Amps Source 3 51BF-1 51BF-2 Volts Amps Amps Volts Source 4 UR Relay Figure 5–20: EXAMPLE USE OF SOURCES 5-74 F35 Multiple Feeder Protection System GE Multilin...
Range: 0.000 to 1 000 000.000 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled GE Multilin F35 Multiple Feeder Protection System 5-75...
Page 212
1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the F35. The follow- ing settings are available for each breaker control element.
Page 213
5 SETTINGS 5.4 SYSTEM SETUP Figure 5–21: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin F35 Multiple Feeder Protection System...
Page 214
BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING BREAKER 1 OUT OF SV = Off 842025A1.CDR Figure 5–22: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) 5-78 F35 Multiple Feeder Protection System GE Multilin...
1. • SWITCH 1 MODE: This setting selects “3-pole” mode, where all disconnect switch poles are operated simultaneously, or “1-pole” mode where all disconnect switch poles are operated either independently or simultaneously. GE Multilin F35 Multiple Feeder Protection System 5-79...
Page 216
SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in the local control mode. NOTE 5-80...
Page 217
5 SETTINGS 5.4 SYSTEM SETUP Figure 5–23: DISCONNECT SWITCH SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-81...
1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-82 F35 Multiple Feeder Protection System GE Multilin...
Page 219
The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin F35 Multiple Feeder Protection System 5-83...
Page 220
EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the F35 are displayed in the following graphs. 5-84 F35 Multiple Feeder Protection System...
Page 221
842723A1.CDR Figure 5–27: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–28: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin F35 Multiple Feeder Protection System 5-85...
Page 222
Figure 5–29: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–30: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-86 F35 Multiple Feeder Protection System GE Multilin...
Page 223
Figure 5–31: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–32: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin F35 Multiple Feeder Protection System 5-87...
Page 224
Figure 5–33: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–34: RECLOSER CURVES GE119, GE135, AND GE202 5-88 F35 Multiple Feeder Protection System GE Multilin...
Figure 5–35: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the F35 are represented by flags (or FlexLogic™ operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic™...
Page 226
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–8: F35 FLEXLOGIC™ OPERAND TYPES OPERAND TYPE STATE...
Page 227
5 SETTINGS 5.5 FLEXLOGIC™ The operands available for this relay are listed alphabetically by types in the following table. Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 1 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
Page 228
5.5 FLEXLOGIC™ 5 SETTINGS Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 2 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: BREAKER 1 OFF CMD Breaker 1 open command initiated Breaker control BREAKER 1 ON CMD Breaker 1 close command initiated BREAKER 1 ΦA BAD ST...
Page 229
5 SETTINGS 5.5 FLEXLOGIC™ Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 3 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: NEG SEQ IOC1 PKP Negative-sequence instantaneous overcurrent 1 has picked up Negative-sequence NEG SEQ IOC1 OP Negative-sequence instantaneous overcurrent 1 has operated...
Page 230
5.5 FLEXLOGIC™ 5 SETTINGS Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 4 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SELECTOR 1 POS Y Selector switch 1 is in Position Y (mutually exclusive operands) Selector switch SELECTOR 1 BIT 0...
Page 231
5 SETTINGS 5.5 FLEXLOGIC™ Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 5 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: TELEPRO CH1 FAIL Channel 1 failed Teleprotection TELEPRO CH2 FAIL Channel 2 failed channel tests TELEPRO CH1 ID FAIL The ID check for a peer relay on channel 1 has failed...
Page 232
5.5 FLEXLOGIC™ 5 SETTINGS Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 6 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on. Fixed front panel LED TROUBLE Asserted when the front panel TROUBLE LED is on.
Page 233
5 SETTINGS 5.5 FLEXLOGIC™ Table 5–9: F35 FLEXLOGIC™ OPERANDS (Sheet 7 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position...
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during testing, for exam- ple, it is suggested to power the unit down and then back up. 5-98 F35 Multiple Feeder Protection System GE Multilin...
Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–37: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin F35 Multiple Feeder Protection System 5-99...
Page 236
Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-100 F35 Multiple Feeder Protection System GE Multilin...
Page 237
87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin F35 Multiple Feeder Protection System 5-101...
Page 238
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-102 F35 Multiple Feeder Protection System GE Multilin...
TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin F35 Multiple Feeder Protection System 5-103...
Page 240
5.5 FLEXLOGIC™ 5 SETTINGS • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". 5-104 F35 Multiple Feeder Protection System GE Multilin...
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin F35 Multiple Feeder Protection System 5-105...
Page 242
The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-106 F35 Multiple Feeder Protection System GE Multilin...
Page 244
“Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-108 F35 Multiple Feeder Protection System GE Multilin...
LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–46: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin F35 Multiple Feeder Protection System 5-109...
5.6.3 PHASE CURRENT a) INVERSE TIME OVERCURRENT CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
Page 249
= characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–18: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
Page 250
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The F35 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. 5-114...
Page 251
‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. GE Multilin F35 Multiple Feeder Protection System 5-115...
Page 252
5.6 GROUPED ELEMENTS 5 SETTINGS Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage 818784A4.CDR Figure 5–47: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC Figure 5–48: PHASE TIME OVERCURRENT 1 SCHEME LOGIC 5-116 F35 Multiple Feeder Protection System GE Multilin...
Page 253
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing curves are shown below for form-A contacts in a 60 Hz system. GE Multilin F35 Multiple Feeder Protection System 5-117...
Page 254
5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–49: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES Figure 5–50: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC 5-118 F35 Multiple Feeder Protection System GE Multilin...
RESET: NEUTRAL TOC1 PKP NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–51: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-119...
Page 256
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection): -- - × (EQ 5.17) – injected 5-120 F35 Multiple Feeder Protection System GE Multilin...
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion range of a standard channel is from 0.02 to 46 times the CT rating. NOTE GE Multilin F35 Multiple Feeder Protection System 5-121...
Page 258
0.02 to 46 times the CT rating. NOTE This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is from 0.002 to 4.6 times the CT rating. NOTE 5-122 F35 Multiple Feeder Protection System GE Multilin...
See page 5–125. The F35 relay provides two (2) negative-sequence time overcurrent elements and two (2) negative-sequence instanta- neous overcurrent elements. For additional information on the negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier.
The time delay is adjustable from 0 to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char- acteristic. 5-126 F35 Multiple Feeder Protection System GE Multilin...
Page 263
V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–57: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting. NOTE GE Multilin F35 Multiple Feeder Protection System 5-127...
Page 264
FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–58: PHASE UNDERVOLTAGE1 SCHEME LOGIC 5-128 F35 Multiple Feeder Protection System GE Multilin...
Page 265
“Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–59: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-129...
Page 266
AUX UV1 EVENTS: MESSAGE Disabled The F35 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
Page 267
AUX OV1 EVENTS: MESSAGE Disabled The F35 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-132 F35 Multiple Feeder Protection System GE Multilin...
Page 269
TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–63: TRIP BUS LOGIC GE Multilin F35 Multiple Feeder Protection System 5-133...
The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-134 F35 Multiple Feeder Protection System GE Multilin...
Page 272
SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-136 F35 Multiple Feeder Protection System GE Multilin...
Page 273
The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin F35 Multiple Feeder Protection System 5-137...
Page 274
3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–65: TIME-OUT MODE 5-138 F35 Multiple Feeder Protection System GE Multilin...
Page 275
Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin F35 Multiple Feeder Protection System 5-139...
Page 276
SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–67: SELECTOR SWITCH LOGIC 5-140 F35 Multiple Feeder Protection System GE Multilin...
≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–68: UNDERFREQUENCY SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-141...
4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE 5-142 F35 Multiple Feeder Protection System GE Multilin...
Page 279
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). GE Multilin F35 Multiple Feeder Protection System 5-143...
Page 280
‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE 5-144 F35 Multiple Feeder Protection System GE Multilin...
Page 281
5 SETTINGS 5.7 CONTROL ELEMENTS To sheet 2 Figure 5–69: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) GE Multilin F35 Multiple Feeder Protection System 5-145...
Page 282
5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–70: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) 5-146 F35 Multiple Feeder Protection System GE Multilin...
Page 283
5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–71: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT GE Multilin F35 Multiple Feeder Protection System 5-147...
DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. 5-148 F35 Multiple Feeder Protection System GE Multilin...
Page 285
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–73: TRIP CIRCUIT EXAMPLE 1 GE Multilin F35 Multiple Feeder Protection System 5-149...
Page 286
In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). 5-150 F35 Multiple Feeder Protection System GE Multilin...
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter. GE Multilin F35 Multiple Feeder Protection System 5-151...
Page 288
If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation. 5-152 F35 Multiple Feeder Protection System GE Multilin...
Page 290
FLEXLOG C OPE AND Off = 0 8BIT SW 1 ARG B7: 8BIT SWITCH 1 BIT 7 Off = 0 ETT NG 8BIT SW 1 CONTROL: Off = 0 842017A1.CDR Figure 5–76: 8-BIT SWITCH LOGIC 5-154 F35 Multiple Feeder Protection System GE Multilin...
MESSAGE See page 5–158. INCIPIENT FAULT 4 MESSAGE See page 5–158. INCIPIENT FAULT 5 MESSAGE See page 5–158. INCIPIENT FAULT 6 MESSAGE See page 5–158. GE Multilin F35 Multiple Feeder Protection System 5-155...
Page 292
• BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. 5-156 F35 Multiple Feeder Protection System GE Multilin...
Page 293
Contacts Initiate Extinguished Part Total Area = Breaker Arcing Current (kA·cycle) Programmable 100 ms Start Delay Start Stop Integration Integration Figure 5–77: ARCING CURRENT MEASUREMENT Figure 5–78: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin F35 Multiple Feeder Protection System 5-157...
Page 294
B current (red). The superimposed current shows two fault current blips as the data slides through the two-cycle memory window. During the actual fault, the neutral current and the superimposed phase B currents closely correspond, confirming the incipient fault hypothesis and identifying the affected phase. 5-158 F35 Multiple Feeder Protection System GE Multilin...
Page 295
INCIPNT FLT 1 DETECT WINDOW: This setting specifies a time window for “Counts per window” mode of operation. • INCIPIENT FAULT 1 RESET DELAY: This setting specifies a reset time for the output after the trip is initiated. GE Multilin F35 Multiple Feeder Protection System 5-159...
Page 296
INCIPIENT FAULT 1 PH A FAULTS INCIPIENT FAULT 1 PH B FAULTS COMMAND INCIPIENT FAULT 1 PH C FAULTS CLEAR INCIPIENT FAULT COUNTERS RESET = Yes 832028A1.CDR Figure 5–80: INCIPIENT CABLE FAULT DETECTOR SCHEME LOGIC 5-160 F35 Multiple Feeder Protection System GE Multilin...
Range: 1 to 20 s in steps of 1 PID 1 DEAD TIME: MESSAGE 1.00 sec Range: FlexLogic™ operand PID 1 BLK: MESSAGE Range: Self-reset, Latched, Disabled PID 1 MESSAGE TARGET: Self-reset Range: Enabled, Disabled PID 1 MESSAGE EVENTS: Disabled GE Multilin F35 Multiple Feeder Protection System 5-161...
Page 298
AW is a flag which enables anti-windup. The incremental form of the above equation is: Du k ( ) u k ( ) u k 1 – – (EQ 5.21) Dp k ( ) Di k ( ) Dd k ( ) Where: 5-162 F35 Multiple Feeder Protection System GE Multilin...
Page 299
, N, Antiwindup: ACTUAL VALUE Enabled = 1 PID 1 DELTA OUT SETTING SETTING Process: max, min Setpoint: ACTUAL VALUE Tracking: Out=MAX(min,MIN(max,u)) PID 1 OUT ACTUAL VALUE SETPOINT Figure 5–82: PID REGULATOR LOGIC GE Multilin F35 Multiple Feeder Protection System 5-163...
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the F35 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
Page 301
Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin F35 Multiple Feeder Protection System 5-165...
The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the F35 using the FlexLogic™ operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
Page 304
5 SETTINGS The F35 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin F35 Multiple Feeder Protection System 5-169...
The remote input/output facility provides for 32 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a F35 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the F35 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) GE Multilin F35 Multiple Feeder Protection System 5-173...
APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. 5-174 F35 Multiple Feeder Protection System GE Multilin...
Page 311
5 SETTINGS 5.8 INPUTS AND OUTPUTS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A F35 RELAY Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.
Page 312
DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: 5-176 F35 Multiple Feeder Protection System GE Multilin...
Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-2 MESSAGE DEFAULT: Off ↓ Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-16 MESSAGE DEFAULT: Off GE Multilin F35 Multiple Feeder Protection System 5-177...
Page 314
(teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. 5-178 F35 Multiple Feeder Protection System GE Multilin...
GOOSE analog input value. GOOSE Analogs are floating-point values, with no units. The GOOSE UNIT and PU base settings allow the user to configure GOOSE Analog, so that it can be used in a FlexElement. GE Multilin F35 Multiple Feeder Protection System 5-179...
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log™ values in other F35 features, such as FlexElements™. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
Page 317
–20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin F35 Multiple Feeder Protection System 5-181...
1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-182 F35 Multiple Feeder Protection System GE Multilin...
– MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–91: DCMA OUTPUT CHARACTERISTIC 5-184 F35 Multiple Feeder Protection System GE Multilin...
Page 321
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: GE Multilin F35 Multiple Feeder Protection System 5-185...
Page 322
1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-186 F35 Multiple Feeder Protection System GE Multilin...
Page 323
TEST MODE FORCING: MESSAGE The F35 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
Page 324
Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a F35 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu: SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin F35 Multiple Feeder Protection System 5-189...
Page 326
5.10 TESTING 5 SETTINGS 5-190 F35 Multiple Feeder Protection System GE Multilin...
GOOSE UINTEGERS EGD PROTOCOL See page 6-8. STATUS TELEPROT CH TESTS See page 6-9. INCIPIENT FAULT See page 6-9. ETHERNET SWITCH See page 6-10. GE Multilin F35 Multiple Feeder Protection System...
Page 328
DATA LOGGER See page 6-23. MAINTENANCE See page 6-24. ACTUAL VALUES MODEL INFORMATION See page 6-25. PRODUCT INFO FIRMWARE REVISIONS See page 6-25. F35 Multiple Feeder Protection System GE Multilin...
The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin F35 Multiple Feeder Protection System...
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. F35 Multiple Feeder Protection System GE Multilin...
The present state of up to 16 programmed remote devices is shown here. The message indi- ALL REMOTE DEVICES ONLINE cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin F35 Multiple Feeder Protection System...
PATH: ACTUAL VALUES STATUS FLEX STATES Range: Off, On FLEX STATES PARAM 1: Off Range: Off, On PARAM 2: Off MESSAGE ↓ Range: Off, On PARAM 256: Off MESSAGE F35 Multiple Feeder Protection System GE Multilin...
The UNRETURNED MSG COUNT CRC FAIL values can be cleared using the command. COUNT CLEAR DIRECT I/O COUNTERS values represent the state of each direct input. DIRECT INPUT 1 DIRECT INPUT (32) GE Multilin F35 Multiple Feeder Protection System...
UINT INPUT 16 MESSAGE The F35 Multiple Feeder Protection System is provided with optional IEC 61850 communications capabil- ity. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values can be reset to zero with the command. COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT COUNTERS GE Multilin F35 Multiple Feeder Protection System...
SWITCH MAC ADDRESS: MESSAGE 00A0F40138FA These actual values appear only if the F35 is ordered with an Ethernet switch module (type 2S or 2T). The status informa- tion for the Ethernet switch is shown in this menu. • SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on the Ethernet switch.
WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin F35 Multiple Feeder Protection System 6-11...
Page 338
ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 F35 Multiple Feeder Protection System GE Multilin...
Page 339
The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the F35 displays are always referenced as specified under SETTINGS ...
Page 344
The signal used for frequency estimation is low-pass filtered. The SYSTEM SETUP POWER SYSTEM final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and transients. 6-18 F35 Multiple Feeder Protection System GE Multilin...
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the setting in the menu. Refer to the FREQUENCY AND PHASE REFERENCE SETTINGS SYSTEM SETUP POWER SYSTEM Power System section of chapter 5 for additional details. GE Multilin F35 Multiple Feeder Protection System 6-19...
MESSAGE 0.000 The F35 Multiple Feeder Protection System is provided with optional IEC 61850 communications capabil- ity. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
RTD INPUT xx -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin F35 Multiple Feeder Protection System 6-21...
If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the menu for clearing event records. COMMANDS CLEAR RECORDS 6-22 F35 Multiple Feeder Protection System GE Multilin...
It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the menu for clearing data logger records. COMMANDS CLEAR RECORDS GE Multilin F35 Multiple Feeder Protection System 6-23...
BKR 1 ARCING AMP menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-24 F35 Multiple Feeder Protection System GE Multilin...
6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE order code format; MODEL INFORMATION ORDER CODE LINE 1: example order code shown F35-E00-HCH-F8F-H6G Range: standard GE order code format ORDER CODE LINE 2:...
Page 352
6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-26 F35 Multiple Feeder Protection System GE Multilin...
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin F35 Multiple Feeder Protection System...
24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. F35 Multiple Feeder Protection System GE Multilin...
Various self-checking diagnostics are performed in the background while the F35 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the F35 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE F35 Multiple Feeder Protection System GE Multilin...
Page 357
Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the F35 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
Page 358
How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures • What to do: Check the F35 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on the Ethernet switch. Check the power to the switch.
Page 359
What to do: Check direct input and output configuration and wiring. REMOTE DEVICE FAIL: COMM Path Incomplete • Latched target message: No. • Description of problem: One or more GOOSE devices are not responding. GE Multilin F35 Multiple Feeder Protection System...
Page 360
Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the F35 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
Page 361
Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. GE Multilin F35 Multiple Feeder Protection System...
Page 362
7.2 TARGETS 7 COMMANDS AND TARGETS 7-10 F35 Multiple Feeder Protection System GE Multilin...
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F35, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both commands and settings. NOTE F35 Multiple Feeder Protection System GE Multilin...
SUPERVISION TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min GE Multilin F35 Multiple Feeder Protection System...
INVALID ATTEMPS BEFORE LOCKOUT The F35 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
Page 367
If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin F35 Multiple Feeder Protection System...
(settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the F35 firmware are at ver- sions 5.40 or higher.
Page 369
ADDING PASSWORD PROTECTION TO A TEMPLATE GE recommends that templates be saved with password protection to maximize security. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
Page 370
Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F35 Multiple Feeder Protection System GE Multilin...
Page 371
Once a settings template is removed, it cannot be reapplied and a new settings template needs to be defined before use. Right-click the device in the Online or Offline Window area and select the Template Mode > Remove Template option. Enter the template password and click OK to continue. GE Multilin F35 Multiple Feeder Protection System...
Select the Template Mode > View In Template Mode option to view the template. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode > Pass- word Protect Template option. 8-10 F35 Multiple Feeder Protection System GE Multilin...
Page 373
A serial number is viewable under Actual Values > Product Info > Model Information, the inside front panel, and the rear of the device. GE Multilin F35 Multiple Feeder Protection System 8-11...
When a settings file is transfered to a F35 device, the date, time, and serial number of the F35 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the F35 actual values at any later date to determine if security has been compromised.
Page 375
With respect to the above diagram, the traceability feature is used as follows. The transfer date of a setting file written to a F35 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
Page 376
ONLINE DEVICE TRACEABILITY INFORMATION The F35 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin F35 Multiple Feeder Protection System 8-15...
The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 F35 Multiple Feeder Protection System GE Multilin...
Page 379
When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin F35 Multiple Feeder Protection System 8-17...
Page 380
8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 F35 Multiple Feeder Protection System GE Multilin...
Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 9.7) GE Multilin F35 Multiple Feeder Protection System...
Page 382
-- - V (EQ 9.14) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 F35 Multiple Feeder Protection System GE Multilin...
Page 383
FAULT TYPE FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 9–2: FAULT LOCATOR SCHEME GE Multilin F35 Multiple Feeder Protection System...
Page 384
9.1 FAULT LOCATOR 9 THEORY OF OPERATION F35 Multiple Feeder Protection System GE Multilin...
Injection to a particular F35 frequency element must be to its configured source and to the channels the source uses for fre- quency measurement.
Page 386
1 second from test set time reading of ramp start to relay operation. Note that the F35 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude 6241 SRC 2 I_2 Angle Amps Source 2 negative-sequence current angle 6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude GE Multilin F35 Multiple Feeder Protection System...
Page 388
SRC 4 I_2 Angle Amps Source 4 negative-sequence current angle 6370 SRC 4 Igd Mag Degrees Source 4 differential ground current magnitude 6372 SRC 4 Igd Angle Amps Source 4 differential ground current angle F35 Multiple Feeder Protection System GE Multilin...
Page 389
SRC 6 Igd Mag Degrees Source 6 differential ground current magnitude 6500 SRC 6 Igd Angle Amps Source 6 differential ground current angle 6656 SRC 1 Vag RMS Volts Source 1 phase AG voltage RMS GE Multilin F35 Multiple Feeder Protection System...
Page 390
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS 6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude 6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle F35 Multiple Feeder Protection System GE Multilin...
Page 391
SRC 4 Vca RMS Volts Source 4 phase CA voltage RMS 6869 SRC 4 Vab Mag Volts Source 4 phase AB voltage magnitude 6871 SRC 4 Vab Angle Degrees Source 4 phase AB voltage angle GE Multilin F35 Multiple Feeder Protection System...
Page 392
SRC 6 Vag Angle Degrees Source 6 phase AG voltage angle 6985 SRC 6 Vbg Mag Volts Source 6 phase BG voltage magnitude 6987 SRC 6 Vbg Angle Degrees Source 6 phase BG voltage angle F35 Multiple Feeder Protection System GE Multilin...
Page 393
Source 2 phase C reactive power 7216 SRC 2 S Source 2 three-phase apparent power 7218 SRC 2 Sa Source 2 phase A apparent power 7220 SRC 2 Sb Source 2 phase B apparent power GE Multilin F35 Multiple Feeder Protection System...
Page 394
Source 5 phase B reactive power 7310 SRC 5 Qc Vars Source 5 phase C reactive power 7312 SRC 5 S Source 5 three-phase apparent power 7314 SRC 5 Sa Source 5 phase A apparent power F35 Multiple Feeder Protection System GE Multilin...
Page 395
7720 SRC 3 Demand var Vars Source 3 reactive power demand 7722 SRC 3 Demand Va Source 3 apparent power demand 7728 SRC 4 Demand Ia Amps Source 4 phase A current demand GE Multilin F35 Multiple Feeder Protection System...
Page 396
Brk 4 Op Time C Breaker 4 operating time phase C 8711 Brk 4 Op Time Breaker 4 operating time 9024 Prefault Ia Mag [0] Amps Fault 1 pre-fault phase A current magnitude A-10 F35 Multiple Feeder Protection System GE Multilin...
Page 397
Fault 2 post-fault phase A voltage angle 9092 Postfault Vb Mag [1] Volts Fault 2 post-fault phase B voltage magnitude 9094 Postfault Vb Ang [1] Degrees Fault 2 post-fault phase B voltage angle GE Multilin F35 Multiple Feeder Protection System A-11...
Page 398
Fault 4 post-fault phase B current magnitude 9161 Postfault Ib Ang [3] Degrees Fault 4 post-fault phase B current angle 9162 Postfault Ic Mag [3] Amps Fault 4 post-fault phase C current magnitude A-12 F35 Multiple Feeder Protection System GE Multilin...
Page 399
9 actual value 13522 DCMA Inputs 10 Value dcmA input 10 actual value 13524 DCMA Inputs 11 Value dcmA input 11 actual value 13526 DCMA Inputs 12 Value dcmA input 12 actual value GE Multilin F35 Multiple Feeder Protection System A-13...
Page 400
RTD input 32 actual value 13584 RTD Inputs 33 Value RTD input 33 actual value 13585 RTD Inputs 34 Value RTD input 34 actual value 13586 RTD Inputs 35 Value RTD input 35 actual value A-14 F35 Multiple Feeder Protection System GE Multilin...
Page 401
GOOSE Analog In 13 IEC 61850 GOOSE analog input 13 45610 GOOSE Analog In 14 IEC 61850 GOOSE analog input 14 45612 GOOSE Analog In 15 IEC 61850 GOOSE analog input 15 GE Multilin F35 Multiple Feeder Protection System A-15...
Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin F35 Multiple Feeder Protection System...
No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC F35 Multiple Feeder Protection System GE Multilin...
Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The F35 interpretation allows either function code to be used for reading one or more consecutive data registers. The data starting address will determine the type of data being read.
DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high F35 Multiple Feeder Protection System GE Multilin...
PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin F35 Multiple Feeder Protection System...
Last Cleared Date" to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT F35 Multiple Feeder Protection System GE Multilin...
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F35, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
0418 Virtual Input 25 State 0 to 1 F108 0 (Off) 0419 Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) F35 Multiple Feeder Protection System GE Multilin...
Page 411
...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 FlexStates (Read Only) 0900 FlexState Bits (16 items) 0 to 65535 F001 Element States (Read Only) 1000 Element Operate States (64 items) 0 to 65535 F502 GE Multilin F35 Multiple Feeder Protection System...
Page 412
0 to 65535 F500 160A Field Latching Output Close Driver States 0 to 65535 F500 160B Field Latching Output Physical States 0 to 65535 F500 160C Field Unit Online/Offline States 0 to 65535 F500 B-10 F35 Multiple Feeder Protection System GE Multilin...
Page 413
Source 1 Differential Ground Current Magnitude 0 to 999999.999 0.001 F060 1824 Source 1 Differential Ground Current Angle -359.9 to 0 degrees F002 1825 Reserved (27 items) F001 1840 ...Repeated for Source 2 GE Multilin F35 Multiple Feeder Protection System B-11...
Page 414
Source 1 Phase B Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C0E Source 1 Phase C Reactive Power -1000000000000 to 0.001 F060 1000000000000 1C10 Source 1 Three Phase Apparent Power -1000000000000 to 0.001 F060 1000000000000 B-12 F35 Multiple Feeder Protection System GE Multilin...
Page 415
Source 1 Demand Ib Maximum 0 to 999999.999 0.001 F060 1E86 Source 1 Demand Ib Maximum Date 0 to 4294967295 F050 1E88 Source 1 Demand Ic Maximum 0 to 999999.999 0.001 F060 GE Multilin F35 Multiple Feeder Protection System B-13...
Page 416
Fault 1 Prefault Phase A Voltage Angle -359.9 to 0 degrees F002 234C Fault 1 Prefault Phase B Voltage Magnitude 0 to 999999.999 0.001 F060 234E Fault 1 Prefault Phase B Voltage Angle -359.9 to 0 degrees F002 B-14 F35 Multiple Feeder Protection System GE Multilin...
Page 418
Fault Report 12 Time 0 to 4294967295 F050 3048 Fault Report 13 Time 0 to 4294967295 F050 304A Fault Report 14 Time 0 to 4294967295 F050 304C Fault Report 15 Time 0 to 4294967295 F050 B-16 F35 Multiple Feeder Protection System GE Multilin...
Page 419
°C F002 34FD RTD Input 14 Value -32768 to 32767 °C F002 34FE RTD Input 15 Value -32768 to 32767 °C F002 34FF RTD Input 16 Value -32768 to 32767 °C F002 GE Multilin F35 Multiple Feeder Protection System B-17...
Page 420
Field Unit Process Card Ports (Read/Write Setting) 3878 Field Unit 1 Process Card Port 0 to 7 F244 6 (H1a) 3879 Field Unit 2 Process Card Port 0 to 7 F244 4 (H2a) B-18 F35 Multiple Feeder Protection System GE Multilin...
Page 421
...Repeated for Field Contact Input 16 39B0 ...Repeated for Field Contact Input 17 39BB ...Repeated for Field Contact Input 18 39C6 ...Repeated for Field Contact Input 19 39D1 ...Repeated for Field Contact Input 20 GE Multilin F35 Multiple Feeder Protection System B-19...
Page 422
...Repeated for Field Contact Output 7 3D2A ...Repeated for Field Contact Output 8 Field Unit Latching Outputs (Read/Write Setting) (8 modules) 3D60 Field Latching Output 1 ID 0 to 1 F205 "FLO Ux /LO" B-20 F35 Multiple Feeder Protection System GE Multilin...
Page 423
Field Unit Transducer 1 Max Value -9999.999 to 9999.999 0.001 F004 100000 3EDC Field Unit Transducer 1 Units F206 (none) 3EDF ...Repeated for Field Unit Transducer 2 3EEE ...Repeated for Field Unit Transducer 3 GE Multilin F35 Multiple Feeder Protection System B-21...
Page 424
0.1 to 1 F001 Communications (Read/Write Setting) 407D COM2 Selection 0 to 3 F601 0 (RS485) 407E COM1 Minimum Response Time 0 to 1000 F001 407F COM2 Minimum Response Time 0 to 1000 F001 B-22 F35 Multiple Feeder Protection System GE Multilin...
Page 425
IEC 60870-5-104 Energy Default Threshold 0 to 100000000 F003 30000 40EC IEC 60870-5-104 Power Default Threshold 0 to 100000000 F003 30000 40EE IEC 60870-5-104 Other Default Threshold 0 to 100000000 F003 30000 GE Multilin F35 Multiple Feeder Protection System B-23...
Page 426
0 to 11 F237 0 (January) 41AB Daylight Savings Time (DST) Start Day 0 to 6 F238 0 (Sunday) 41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 F239 0 (First) B-24 F35 Multiple Feeder Protection System GE Multilin...
Page 427
...Repeated for User-Programmable LED 29 42BA ...Repeated for User-Programmable LED 30 42BC ...Repeated for User-Programmable LED 31 42BE ...Repeated for User-Programmable LED 32 42C0 ...Repeated for User-Programmable LED 33 42C2 ...Repeated for User-Programmable LED 34 GE Multilin F35 Multiple Feeder Protection System B-25...
Page 428
Source Settings (Read/Write Setting) (6 modules) 4580 Source 1 Name 0 to 1 F206 “SRC 1" 4583 Source 1 Phase CT 0 to 63 F400 4584 Source 1 Ground CT 0 to 63 F400 B-26 F35 Multiple Feeder Protection System GE Multilin...
Page 429
0 to 1 F102 0 (Disabled) 4718 Reserved 0 to 65535 F001 4719 ...Repeated for Breaker 2 4732 ...Repeated for Breaker 3 474B ...Repeated for Breaker 4 4764 ...Repeated for Breaker 5 GE Multilin F35 Multiple Feeder Protection System B-27...
Page 430
4E19 Raw Field Data DC2 0 to 0.001 0.001 F002 4E1A Raw Field Data DC3 0 to 0.001 0.001 F002 4E1B Raw Field Data FCI States (2 items) 0 to 1 F500 B-28 F35 Multiple Feeder Protection System GE Multilin...
Page 431
...Repeated for RTD Input 23 55B5 ...Repeated for RTD Input 24 55C8 ...Repeated for RTD Input 25 55DB ...Repeated for RTD Input 26 55EE ...Repeated for RTD Input 27 5601 ...Repeated for RTD Input 28 GE Multilin F35 Multiple Feeder Protection System B-29...
Page 432
...Repeated for FlexLogic™ Timer 25 58C8 ...Repeated for FlexLogic™ Timer 26 58D0 ...Repeated for FlexLogic™ Timer 27 58D8 ...Repeated for FlexLogic™ Timer 28 58E0 ...Repeated for FlexLogic™ Timer 29 58E8 ...Repeated for FlexLogic™ Timer 30 B-30 F35 Multiple Feeder Protection System GE Multilin...
Page 433
Neutral Time Overcurrent 1 Block 0 to 65535 F300 5B08 Neutral Time Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 5B09 Neutral Time Overcurrent 1 Events 0 to 1 F102 0 (Disabled) GE Multilin F35 Multiple Feeder Protection System B-31...
Page 434
5E06 Ground Instantaneous Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 5E07 Ground Instantaneous Overcurrent 1 Events 0 to 1 F102 0 (Disabled) 5E08 Reserved (8 items) 0 to 1 F001 B-32 F35 Multiple Feeder Protection System GE Multilin...
Page 435
6247 Autoreclose 1 Reset Lockout On Manual Close 0 to 1 F108 0 (Off) 6248 Autoreclose 1 Breaker Closed 0 to 65535 F300 6249 Autoreclose 1 Breaker Open 0 to 65535 F300 GE Multilin F35 Multiple Feeder Protection System B-33...
Page 436
F001 7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 0.001 F001 7006 Phase Undervoltage 1 Block 0 to 65535 F300 7007 Phase Undervoltage 1 Target 0 to 2 F109 0 (Self-reset) B-34 F35 Multiple Feeder Protection System GE Multilin...
Page 437
...Repeated for DCmA Inputs 20 74E0 ...Repeated for DCmA Inputs 21 74F8 ...Repeated for DCmA Inputs 22 7510 ...Repeated for DCmA Inputs 23 7528 ...Repeated for DCmA Inputs 24 Disconnect (Breaker) Switch (Read/Write Settings) (24 modules) GE Multilin F35 Multiple Feeder Protection System B-35...
Page 438
User Programmable Pushbutton 1 Target 0 to 2 F109 0 (Self-reset) 7B81 User Programmable Pushbutton 1 Events 0 to 1 F102 0 (Disabled) 7B82 User Programmable Pushbutton 1 LED Operand 0 to 65535 F300 B-36 F35 Multiple Feeder Protection System GE Multilin...
Page 439
0 to 65535 F001 7F10 ...Repeated for Neutral Overvoltage 2 7F20 ...Repeated for Neutral Overvoltage 3 Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules) 7F30 Auxiliary Overvoltage 1 Function 0 to 1 F102 0 (Disabled) GE Multilin F35 Multiple Feeder Protection System B-37...
Page 440
EGD Slow Producer Exchange 1 Signature 0 to 65535 F001 83F1 EGD Slow Producer Exchange 1 Configuration Time 0 to 4294967295 F003 83F3 EGD Slow Producer Exchange 1 Size 0 to 65535 F001 B-38 F35 Multiple Feeder Protection System GE Multilin...
Page 441
...Repeated for Digital Element 23 8BCC ...Repeated for Digital Element 24 8BE0 ...Repeated for Digital Element 25 8BF4 ...Repeated for Digital Element 26 8C08 ...Repeated for Digital Element 27 8C1C ...Repeated for Digital Element 28 GE Multilin F35 Multiple Feeder Protection System B-39...
Page 442
...Repeated for Trip Bus 5 8EA0 ...Repeated for Trip Bus 6 FlexElement (Read/Write Setting) (16 modules) 9000 FlexElement™ 1 Function 0 to 1 F102 0 (Disabled) 9001 FlexElement™ 1 Name F206 “FxE 1” B-40 F35 Multiple Feeder Protection System GE Multilin...
Page 443
...Repeated for Fault Report 5 DCmA Outputs (Read/Write Setting) (24 modules) 9300 DCmA Output 1 Source 0 to 65535 F600 9301 DCmA Output 1 Range 0 to 2 F522 0 (–1 to 1 mA) GE Multilin F35 Multiple Feeder Protection System B-41...
Page 444
...Repeated for Direct Input/Output 22 9508 ...Repeated for Direct Input/Output 23 9514 ...Repeated for Direct Input/Output 24 9520 ...Repeated for Direct Input/Output 25 952C ...Repeated for Direct Input/Output 26 9538 ...Repeated for Direct Input/Output 27 B-42 F35 Multiple Feeder Protection System GE Multilin...
Page 445
Teleprotection Output 1-n Operand (16 items) 0 to 65535 F300 9B70 Teleprotection Output 2-n Operand (16 items) 0 to 65535 F300 Teleprotection Inputs/Outputs Commands (Read/Write Command) 9B90 Teleprotection Clear Lost Packets 0 to 1 F126 0 (No) GE Multilin F35 Multiple Feeder Protection System B-43...
Page 446
PID 1 Block 0 to 4294967295 F300 A512 PID 1 Target 0 to 2 F109 0 (Self-reset) A513 PID 1 Events 0 to 1 F102 0 (Disabled) A514 ...Repeated for PID 2 B-44 F35 Multiple Feeder Protection System GE Multilin...
Page 447
0 to 65535 F300 A815 Reserved (11 items) F001 A820 ...Repeated for Digital Counter 2 A840 ...Repeated for Digital Counter 3 A860 ...Repeated for Digital Counter 4 A880 ...Repeated for Digital Counter 5 GE Multilin F35 Multiple Feeder Protection System B-45...
Page 448
Command to clear XCBR6 OpCnt (operation counter) 0 to 1 F126 0 (No) IEC 61850 LN Name Prefixes (Read/Write Settings) AB30 IEC 61850 Logical Node LPHD1 Name Prefix 0 to 65534 F206 (none) B-46 F35 Multiple Feeder Protection System GE Multilin...
Page 449
AF15 IEC 61850 GGIO4 Analog Input 1 Maximum –1000000000000 to 0.001 F060 1000000 1000000000000 AF17 ...Repeated for IEC 61850 GGIO4 Analog Input 2 AF1E ...Repeated for IEC 61850 GGIO4 Analog Input 3 GE Multilin F35 Multiple Feeder Protection System B-47...
Page 450
0.001 to 100 0.001 F003 10000 B0C4 IEC 61850 MMXU TotVA Deadband 1 0.001 to 100 0.001 F003 10000 B0C6 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 0.001 F003 10000 B-48 F35 Multiple Feeder Protection System GE Multilin...
Page 451
...Repeated for Received Analog 19 B236 ...Repeated for Received Analog 20 B238 ...Repeated for Received Analog 21 B23A ...Repeated for Received Analog 22 B23C ...Repeated for Received Analog 23 B23E ...Repeated for Received Analog 24 GE Multilin F35 Multiple Feeder Protection System B-49...
Page 452
...Repeated for Module 7 B88D ...Repeated for Module 8 IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules) B900 IEC 61850 Configurable GOOSE Dataset Items for 0 to 197 F233 0 (None) Transmission (64 items) B-50 F35 Multiple Feeder Protection System GE Multilin...
Page 453
...Repeated for Contact Input 39 BC38 ...Repeated for Contact Input 40 BC40 ...Repeated for Contact Input 41 BC48 ...Repeated for Contact Input 42 BC50 ...Repeated for Contact Input 43 BC58 ...Repeated for Contact Input 44 GE Multilin F35 Multiple Feeder Protection System B-51...
Page 454
...Repeated for Contact Input 95 BDF8 ...Repeated for Contact Input 96 Contact Input Thresholds (Read/Write Setting) BE00 Contact Input n Threshold, n = 1 to 48 (48 items) 0 to 3 F128 1 (33 Vdc) B-52 F35 Multiple Feeder Protection System GE Multilin...
Page 455
...Repeated for Virtual Input 44 C040 ...Repeated for Virtual Input 45 C04C ...Repeated for Virtual Input 46 C058 ...Repeated for Virtual Input 47 C064 ...Repeated for Virtual Input 48 C070 ...Repeated for Virtual Input 49 GE Multilin F35 Multiple Feeder Protection System B-53...
Page 456
...Repeated for Virtual Output 31 C228 ...Repeated for Virtual Output 32 C230 ...Repeated for Virtual Output 33 C238 ...Repeated for Virtual Output 34 C240 ...Repeated for Virtual Output 35 C248 ...Repeated for Virtual Output 36 B-54 F35 Multiple Feeder Protection System GE Multilin...
Page 457
...Repeated for Virtual Output 85 C3D8 ...Repeated for Virtual Output 86 C3E0 ...Repeated for Virtual Output 87 C3E8 ...Repeated for Virtual Output 88 C3F0 ...Repeated for Virtual Output 89 C3F8 ...Repeated for Virtual Output 90 GE Multilin F35 Multiple Feeder Protection System B-55...
Page 458
...Repeated for Contact Output 27 C584 ...Repeated for Contact Output 28 C590 ...Repeated for Contact Output 29 C59C ...Repeated for Contact Output 30 C5A8 ...Repeated for Contact Output 31 C5B4 ...Repeated for Contact Output 32 B-56 F35 Multiple Feeder Protection System GE Multilin...
Page 459
Clear Breaker 4 Arcing Current Operand 0 to 65535 F300 C779 Clear Breaker 5 Arcing Current Operand 0 to 65535 F300 C77A Clear Breaker 6 Arcing Current Operand 0 to 65535 F300 GE Multilin F35 Multiple Feeder Protection System B-57...
Page 460
...Repeated for Direct Input 30 C908 ...Repeated for Direct Input 31 C90C ...Repeated for Direct Input 32 Platform Direct Outputs (Read/Write Setting) (96 modules) CA10 Direct Output 1 Operand 0 to 65535 F300 B-58 F35 Multiple Feeder Protection System GE Multilin...
Page 461
Direct I/O Ch 2 Unreturned Messages Alarm Threshold 1 to 1000 F001 CAEB Direct I/O Channel 2 Unreturned Messages Alarm Events 0 to 1 F102 0 (Disabled) CAEC Reserved (4 items) 1 to 1000 F001 GE Multilin F35 Multiple Feeder Protection System B-59...
Page 462
...Repeated for Remote Input 24 D090 ...Repeated for Remote Input 25 D09A ...Repeated for Remote Input 26 D0A4 ...Repeated for Remote Input 27 D0AE ...Repeated for Remote Input 28 D0B8 ...Repeated for Remote Input 29 B-60 F35 Multiple Feeder Protection System GE Multilin...
Page 463
...Repeated for Remote Output 8 D2C0 ...Repeated for Remote Output 9 D2C4 ...Repeated for Remote Output 10 D2C8 ...Repeated for Remote Output 11 D2CC ...Repeated for Remote Output 12 D2D0 ...Repeated for Remote Output 13 GE Multilin F35 Multiple Feeder Protection System B-61...
Page 464
IEC 61850 GGIO2.CF.SPCSO31.ctlModel Value 0 to 2 F001 D33F IEC 61850 GGIO2.CF.SPCSO32.ctlModel Value 0 to 2 F001 D340 IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value 0 to 2 F001 D341 IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value 0 to 2 F001 B-62 F35 Multiple Feeder Protection System GE Multilin...
Page 465
...Repeated for Remote Device 17 D3C4 ...Repeated for Remote Device 18 D3C8 ...Repeated for Remote Device 19 D3CC ...Repeated for Remote Device 20 D3D0 ...Repeated for Remote Device 21 D3D4 ...Repeated for Remote Device 22 GE Multilin F35 Multiple Feeder Protection System B-63...
Page 466
FlexLogic™ Displays Active 0 to 1 F102 1 (Enabled) ED01 Reserved (6 items) F205 (none) ED07 Last Settings Change Date 0 to 4294967295 F050 ED09 Template Bitmask (750 items) 0 to 65535 F001 B-64 F35 Multiple Feeder Protection System GE Multilin...
Page 471
RTD Input 35 Digital Element 37 RTD Input 36 Digital Element 38 RTD Input 37 Digital Element 39 RTD Input 38 Digital Element 40 RTD Input 39 Digital Element 41 RTD Input 40 GE Multilin F35 Multiple Feeder Protection System B-69...
Page 472
0 = 5 min, 1 = 10 min, 2 = 15 min, 3 = 20 min, 4 = 30 min, Disconnect switch 22 5 = 60 min Disconnect switch 23 Disconnect switch 24 F133 Breaker 1 ENUMERATION: PROGRAM STATE Breaker 2 Breaker 3 0 = Not Programmed, 1 = Programmed B-70 F35 Multiple Feeder Protection System GE Multilin...
Page 473
A bit value of 0 = no error, 1 = error Unit Not Programmed System Exception Latching Output Discrepancy F144 Ethernet Switch Fail ENUMERATION: FORCED CONTACT INPUT STATE Maintenance Alert 01 0 = Disabled, 1 = Open, 2 = Closed GE Multilin F35 Multiple Feeder Protection System B-71...
Page 474
4 = Group 4, 5 = Group 5, 6 = Group 6 Test Mode Isolated Test Mode Forcible Test Mode Disabled F155 Temperature Warning On ENUMERATION: REMOTE DEVICE STATE Temperature Warning Off 0 = Offline, 1 = Online B-72 F35 Multiple Feeder Protection System GE Multilin...
Page 475
0 = A, 1 = B, 2 = C ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca GE Multilin F35 Multiple Feeder Protection System B-73...
Page 476
TEXT40: 40-CHARACTER ASCII TEXT 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB F185 ENUMERATION: PHASE A,B,C, GROUND SELECTOR 0 = A, 1 = B, 2 = C, 3 = G B-74 F35 Multiple Feeder Protection System GE Multilin...
Page 477
0 = Test Enumeration 0, 1 = Test Enumeration 1 MMXU1.MX.W.phsB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU1.MX.VAr.phsA.cVal.mag.f F226 ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER MMXU1.MX.VAr.phsB.cVal.mag.f METHOD MMXU1.MX.VAr.phsC.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f 0 = None, 1 = GSSE, 2 = GOOSE MMXU1.MX.VA.phsB.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f GE Multilin F35 Multiple Feeder Protection System B-75...
Page 481
Wednesday None Thursday U1/AC1..3 Friday U1/AC5..7 Saturday U2/AC1..3 U2/AC5..7 U3/AC1..3 F239 U3/AC5..7 ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS U4/AC1..3 TIME START DAY INSTANCE U4/AC5..7 value instance U5/AC1..3 First U5/AC5..7 Second U6/AC1..3 Third GE Multilin F35 Multiple Feeder Protection System B-79...
Page 482
[0] Off(0) – this is boolean FALSE value [0] On (1) – this is boolean TRUE value Value Description [2] CONTACT INPUTS (1 to 96) [3] CONTACT INPUTS OFF (1 to 96) None [4] VIRTUAL INPUTS (1 to 32) B-80 F35 Multiple Feeder Protection System GE Multilin...
Page 483
First register indicates input/output state with bits 0 (MSB) to 15 (LSB) corresponding to input/output state 1 to 16. The second reg- ister indicates input/output state with bits 0 to 15 corresponding to GE Multilin F35 Multiple Feeder Protection System B-81...
Page 484
UR_UINT16: FLEXANALOG PARAMETER Corresponds to the Modbus address of the value used when this parameter is selected. Only certain values may be used as Flex- Analogs (basically all metering quantities used in protection). B-82 F35 Multiple Feeder Protection System GE Multilin...
The F35 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the F35 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the F35 to have an IP address to establish communications. These addresses are located in the ...
C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the F35 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a F35 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...
Page 488
The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the F35 protection elements, these flags take their values from the pickup and operate FlexLogic™ operands for the corresponding element.
C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the F35. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
A built-in TCP/IP connection timeout of two minutes is employed by the F35 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the F35. This frees up the con- nection to be used by other clients.
MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the F35 will use the source Ether- net MAC address as the destination, with the multicast bit set.
Page 492
The F35 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The F35 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the F35 is configured to use an automated multicast MAC scheme. If the F35 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
An ICD file is generated for the F35 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the F35 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
Page 498
Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 F35 Multiple Feeder Protection System GE Multilin...
Page 499
Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin F35 Multiple Feeder Protection System C-15...
Page 500
BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 F35 Multiple Feeder Protection System GE Multilin...
The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline F35 settings file is typically much quicker than create an ICD file directly from the relay.
Page 502
Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 F35 Multiple Feeder Protection System GE Multilin...
Page 503
IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin F35 Multiple Feeder Protection System C-19...
Figure 0–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the F35 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
Page 505
The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
Page 509
NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin F35 Multiple Feeder Protection System C-25...
RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 F35 Multiple Feeder Protection System GE Multilin...
Page 511
T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin F35 Multiple Feeder Protection System C-27...
Page 512
ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 F35 Multiple Feeder Protection System GE Multilin...
Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin F35 Multiple Feeder Protection System...
Page 514
<18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 <20> := Packed single-point information with status change detection M_SP_NA_1 F35 Multiple Feeder Protection System GE Multilin...
Page 515
<103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin F35 Multiple Feeder Protection System...
Page 516
•Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 F35 Multiple Feeder Protection System GE Multilin...
Page 518
F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization: Remote initialization Cyclic Data Transmission: Cyclic data transmission Read Procedure: Read procedure F35 Multiple Feeder Protection System GE Multilin...
Page 519
Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously Counter read Counter freeze without reset GE Multilin F35 Multiple Feeder Protection System...
Page 520
Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs F35 Multiple Feeder Protection System GE Multilin...
The IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin F35 Multiple Feeder Protection System...
Page 522
D.1 IEC 60870-5-104 PROTOCOL APPENDIX D D-10 F35 Multiple Feeder Protection System GE Multilin...
Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Fixed at 3 Configurable Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable GE Multilin F35 Multiple Feeder Protection System...
Page 524
FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. F35 Multiple Feeder Protection System GE Multilin...
Page 525
16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Point-by-point list attached Other Value: _____ Point-by-point list attached Sends Multi-Fragment Responses: Yes No GE Multilin F35 Multiple Feeder Protection System...
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. F35 Multiple Feeder Protection System GE Multilin...
Page 527
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. GE Multilin F35 Multiple Feeder Protection System...
Page 528
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. F35 Multiple Feeder Protection System GE Multilin...
Page 529
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F35 is not restarted, but the DNP process is restarted. GE Multilin F35 Multiple Feeder Protection System...
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 F35 Multiple Feeder Protection System GE Multilin...
Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. F35 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin F35 Multiple Feeder Protection System E-11...
Page 534
E.2 DNP POINT LISTS APPENDIX E E-12 F35 Multiple Feeder Protection System GE Multilin...
Page 540
F.1 CHANGE NOTES APPENDIX F Table F–11: MAJOR UPDATES FOR F35 MANUAL REVISION R1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (P2) (R1) Update Updated RELAY SELF-TESTS section Added FAULT TYPE DETERMINATION section Update Updated MODBUS PASSWORD OPERATION section...
Page 541
APPENDIX F F.1 CHANGE NOTES Table F–14: MAJOR UPDATES FOR F35 MANUAL REVISION N2 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (N1) (N2) Remove Removed CONNECTING THE ENERVISTA UR SETUP SOFTWARE WITH THE F35 section Added CONFIGURING THE F35 FOR SOFTWARE ACCESS section...
MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B ... MegaVolt-Ampere (phase B) FLA....Full Load Current MVA_C... MegaVolt-Ampere (phase C) FO ....Fiber Optic F35 Multiple Feeder Protection System GE Multilin...
Page 543
RSTR ..... Restrained WRT....With Respect To RTD....Resistance Temperature Detector RTU....Remote Terminal Unit X .....Reactance RX (Rx) ..Receive, Receiver XDUCER..Transducer XFMR....Transformer s ..... second S..... Sensitive Z......Impedance, Zone SAT ....CT Saturation GE Multilin F35 Multiple Feeder Protection System...
F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Grid Solutions Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...
Page 552
WATT-HOURS ............2-12, 6-17 UNIT NOT PROGRAMMED ........5-68, 7-5 WEB SERVER PROTOCOL ..........5-33 UNPACKING THE RELAY ........... 1-2 WEBSITE ................1-2 UNRETURNED MESSAGES ALARM ......... 5-66 UPDATING ORDER CODE ..........7-3 viii F35 Multiple Feeder Protection System GE Multilin...
Page 553
INDEX ZERO SEQUENCE CORE BALANCE ........ 3-13 GE Multilin F35 Multiple Feeder Protection System...
Page 554
INDEX F35 Multiple Feeder Protection System GE Multilin...