5.1.1 minimum clearance to combustible enclosures

single-sided
1" [25mm] minimum
to sides for vertical
venting.
When passing through
a ceiling, use firestop
spacer W500-0028
(not supplied)
0" to side standoffs
1/2" finishing flange
0" to bottom of the
appliance
note:
The LVX series requires a minimum inside enclosure height of 73" measured from the bottom of the
appliance. For temperature requirements, this area must be left unobstructed. It is mandatory to venti-
late the enclosure according to these instructions.
minimum
Ref
L
rough framing - before appliance installation
L
LVX38
LVX50
73" (185.4cm)
73" (185.4cm)
6" [152mm] minimum
0" to back standoffs
LVX62
LVX74
91" (231.1cm)
91" (231.1cm)
EN
3" [76mm] to top
2" [51mm] to sides /
bottom
When passing through
a wall, use firestop
spacer assembly
W010-4178 (supplied)
0" to non-combustible
finishing such as brick
and stone. When using
non-combustible finish-
ing, only use firestop
spacer (W615-0162)
included in the firestop
assembly (W010-4178)