Creating An Rs485 Connection; Using The Optional Zigbee Communication Option - SolarEdge P300 Quick Installation Manual

P-series power optimizer
Table of Contents

Advertisement

Color
RJ45 Pin #
T568B Standard
1
2
3
4 and 5
6
7 and 8
Aluminum shield
3
Use a pre-crimped cable to connect via gland no.1 to the RJ45 plug on the inverter's communication board, or, if using a cable drum,
connect as follows:
Insert the cable through gland no.1.
Insert the eight wires into an RJ45 connector, as described in the figure above.
Use a crimping tool to crimp the connector.
Connect the Ethernet connector to the RJ45 plug on the inverter's communication board.
4
For the switch/router side, use a pre-crimped cable or use a crimper to prepare an RJ45 communication connector: Insert the eight wires
into the RJ45 connector, maintaining the same color coding and pinout on both sides of the Ethernet cable.
5
Connect the cable's RJ45 connector to the RJ45 port of the Ethernet switch or router.
6
Inverters are configured by default to LAN. If reconfiguration is required:
Turn ON the AC to the inverter by turning ON the circuit breaker on the main distribution panel.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed.
RISQUE D'ÉLECTROCUTION. Ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré.
Use the user buttons to configure the connection.

Creating an RS485 connection

If a revenue grade meter is connected to your inverter, it uses the RS485 port and therefore an RS485 communication bus cannot be created.
1
Make sure that the ON/OFF switch at the bottom of the inverter is turned OFF, and the AC/DC Safety Switch is turned OFF.
2
Remove the seal from one of the openings in communication gland #2 and insert the wire through the opening.
3
Pull out the 9-pin RS485/RS232 terminal block connector, and loosen the
screws of pins B, A and G on the left of the RS-485 terminal block.
4
Insert the ends of wires into the G, A and B pins. Use four- or six-wire
twisted pair cable for this connection. You can use any color wire for
each of the A, B and G connections, as long as the same color wire is
used for all A pins, the same color for all B pins and the same color for all
G pins.
5
For creating an RS485 bus - connect all B, A and G pins in all inverters.
6
Tighten the terminal block screws, and push it firmly all the way into the
communication board.
7
Terminate the first and last inverters in the chain by switching a termination dipswitch inside the inverter to ON (move the left switch to
the top). The switch is located on the communication board and is marked SW7.
8
To connect to the server, designate a single inverter as the connection point between the RS485 bus and the SolarEdge monitoring portal.
This inverter will serve as the master inverter. Connect the master to the SolarEdge monitoring portal via one of the communication
options.

Using the optional ZigBee communication option

Refer to the ZigBee kit user manual.
Refer to the SolarEdge Installation Guide for detailed installation and safety instructions.
T568A Standard
White/Orange
Orange
White/Green
White/Orange
Blue + White/Blue
Blue + White/Blue
Green
Brown + White/Brown
Brown + White/Brown
YOUR
DISTRIBUTOR
SOLARIS
720-474-6050
www.solaris-shop.com
White/Green
Green
Orange
Support and Contact Information
If you have technical problems concerning our products, please contact us:
USA and Canada:
Worldwide:
Fax:
Email to
support@solaredge.us
7
RS485-2 (not in use)
G
A (Data+)
B (Data-)
+1 (0) 877 360 5292
+972 (0) 73 240-3118
+1 (0) 530 273-2769

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P370P500P505P405P404P600 ... Show all

Table of Contents