Volume Control; Trouble Shooting - Vingtor CTB-100V Installation & User Manual

Command talk back & public address system
Table of Contents

Advertisement

Installation & User Manual

Volume control

Pos.
Operation Requirement
32
Adjust sound pressure level, to convenient level if necessary
Master volume line 1-5, 6-10, 11-15, 16-20
Ref. chapter 3.8 and dwg.CU-100:lo and CU-200_lo
5.8

Trouble shooting.

Most faults can be related to following problems
Important! Use this trouble shooting together with chapter 3 Installation and Configuration Procedure
Problems when operating from operation panels.
Pos.
Failure event
1
The whole system is shut
down.
No light indication in CTB-
panels.
2
SPS-4 power supply failure
3
Operation from CTB-panels
failed 1.
3.1
Operation from CTB-panels
failed 2
4
Priority do not fulfil
requirement for actual
operation panel
5
Receive call from substation
do not fulfil requirement for
actual station.
6
Public address operation does
not fulfil the requirement for
operation of SPA public
address system.
7
Level for signal from auxiliary
does not fulfil the requirement.
Level for output PA-Signal
7.1
does not fulfil the requirement.
Description / Indication
No voltage measured on terminal block
X7 no.1-2 in the CU-unit
Correct voltage 24 – 32VDC measured
on terminal block X7 no.1-2 in the CU-
unit
Indication from failure contact X2
No.5-6(NO)or. X2 No.6-7 (NC)
No light in "DC ok"
Two possibilities
1. 230V AC or 115V AC failed and
have been switched to 24V DC
Emergency.
2.The power supply module has failed.
No audio message received in any
substation no. 1-10 or 11-20.
One or more operation panels failed.
One or more Indication light is active ,
one for each operation panel marked
"indication for panels" on central
unit.ref.dwg.CU-100_lo
System CTB-100V
Tested, ok
Recommended Action
1.Check 24V DC mains power
supply or power supply SPS-4
2. Check fuse marked F3 1AT
(Ref. dwg CU-100_lo)
1. Check main power supply
2. Check fuse 5.0AT , terminal
marked 3
2.1 If not success, the power
module have to be repaired./
replaced.
Check fuse marked "fuse 2"1.0AT
for line 1-10 and "fuse 4"1.0AT
for line 11-20
Check all connection for actual
panel(s) The panel operate correct
when light is turned off.
Try to replace the position, if
current panels then work correct
the fault must be in the central
unit. The main board have to be
replaced or repaired.
Check if DIP switches in the
central unit marked "set priority"
is set according to chapter 3.5
Check if DIP switches in the
central unit marked "set receive
call" is set according to chapter
3.6
Check if DIP switches in the
central unit marked "selector for
PA-zones" is set according to
chapter 3.7
Adjust trim potentiometer in the
central unit marked "adj. aux.
input signal" to satisfactorily
level.see chapter 3.8.2
Adjust trim potentiometer in the
central unit marked "adj. PA-
output signal" to satisfactorily
level. See chapter 3.8.2
43