SINGLE OUTPUT MONITORED MODULE
GENERAL DESCRIPTION
The single output monitored module is designed to control external devices for the fire alarm system
IFS 7000 by means of potential output "Open collector" in case of detecting fire conditions.
The single output monitored module (fig.1) consists of a printed circuit board (pos.2) and an unit
carrier (pos.4), fixed in a plastic box with bottom (pos.1) and a cover (pos.3).The terminals for
connecting the signal loop SL (pos.1), the power loop PL (pos.3), and the external devices OUT
(pos.2) are located on the printed circuit board (fig 2).
The communication between the Fire Control Panel and the single output monitored module is
completed via the signal loop by the specialized data exchange protocol UniTALK. The single output
monitored module is power supplied by the power loop. Two built-in isolators are provided for short
circuit protection – one on the signal loop and one on the power loop.
Both LED indicators (fig.1, pos.6) provide information for the current status:
- Duty mode - red and yellow LEDs flash briefly every 16s;
- Activated output - the red LED produces continuous light, the yellow LED is not lit;
- Fault condition (activated isolator on the signal loop) - the yellow LED flashes briefly every 1s,
the red LED is not lit;
- Fault condition (activated isolator on the power loop) - the yellow LED flashes briefly every 2s,
the red LED is not lit.
TECHNICAL DATA
Supply voltage:
- signal loop
- power loop
Current consumption in Duty mode:
- signal loop
- power loop
Current consumption in Activated output:
- signal loop
- power loop
Output:
- type
- voltage
- maximum current
Cross section of connecting wires
Type of the connecting cables:
- of the signal loop
- of the power loop
- of the external devices
Degree of protection
Operational temperature range
Relative humidity resistance
Dimensions
Weight
INSTALLATION
Install it according to fig.1 in the following sequence:
1.Dismantle the single output monitored module by unscrewing screws pos.7 and pos.5.
2.Installation holes and connecting wires holes are drilled on the designated places on the bottom.
3.Fix the bottom on the desired place by means of pins and screws. The connecting wires are
threaded in advance in the box.
4.Install the unit carrier to the bottom by using screws pos.5.
5.The electrical connection is done according to fig.2. Connect the wires of the signal loop to the
terminals pos.1, of the power loop - to pos.3 and the external devices - to pos.2. Connect the negative
leads to "-", the positive - to "+", and the shields - to "Å". It is not necessary to take into consideration
the conditional beginnings and ends of the loops. It is recommended cable shoes to be used.
6.Place the cover to the bottom by using screws pos.7.
TESTING
The single output monitored module is tested after installation as a part of the site's fire alarm
system or with maintenance activities.
The output of the module is tested by the Fire Control Panel. It should be activated and the
respective indication to be on. When the menu is quitted, the single output monitored module should
be enter Duty mode.
SERVICE SCHEDULE
It is done by authorized personnel and includes the following activities:
1.Inspection for visible physical damage
2.Testing in real conditions
WARRANTY
The warrant period is 36 months from the date of sale.
The manufacturer guarantees the normal operation of the unit providing that the requirements set
herein have been observed.
The manufacturer does not bear warranty liabilities for damages caused through accidental
mechanical damage, misuse, adaptation or modification after production. The manufacturer bears
warranty liabilities for damages in the unit caused through manufacturer's fault only.
Manufacturer: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, R. Bulgaria, http://www.unipos-bg.com
ADDRESSABLE
FD 7203OC
TYPE
INSTRUCTION MANUAL 02-7203OC
(15-30)V DC
(12-30)V DC
300 µÀ
2 mA
3 mA
up to 200 mA
1 pc.
potential, "Open collector"
(11-30)V DC
200 mÀ
(0,8-2,5) mm²
two-wire, shielded
two-wire
two-wire
IP 50
minus 10ºÑ - plus 55ºÑ
(93±3)% at 40ºÑ
120x164x74 mm
0,250 kg
- monthly
- monthly
051-2
1293

Advertisement

loading

Summary of Contents for UniPOS FD 7203OC

  • Page 1 The manufacturer does not bear warranty liabilities for damages caused through accidental mechanical damage, misuse, adaptation or modification after production. The manufacturer bears warranty liabilities for damages in the unit caused through manufacturer's fault only. Manufacturer: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, R. Bulgaria, http://www.unipos-bg.com...