7. Re-fit the terminal cover to the drive. (For removal / re-fitting instructions, see
Unidrive SP Solutions Module Installation Sheet provided with the Solutions
Module.)
8. Connect the AC supply to the drive.
9. Set Pr 0.49 to L2 to unlock read only security.
10. Check that Menu 15 (slot 1), 16 (slot 2), or 17 (slot 3) parameters are now available.
11. Check that Pr 15.01, Pr 16.01 or Pr 17.01 shows the correct code for the SM-
Encoder Plus (code = 104).
12. If the checks in steps 10 and 11 fail, either the SM-Encoder Plus is not fully inserted,
or the Solutions Module is faulty.
13. If a trip code is now present refer to Chapter 7 Diagnostics on page 32.
SM-Encoder Plus User Guide
Issue Number: 3
Figure 4-2 Fitting the SM-Encoder Plus