Mitsubishi Electric MELSEC iQ-F FX5 Reference page 11

Programmable controller, analog input module / output module / multiple input module function block
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

No.
Variable name
Name
(6)
i_uLogCycleVal
Logging cycle setting
value
(7)
i_uLogCycleUnit
Logging cycle unit
setting
(8)
i_uLogPoints
Number of
posttrigger logging
points
(9)
i_uLogTrigCond
Level trigger
condition setting
(10)
i_uLogTrigData
Trigger data
(11)
i_wLogTrigValue
Trigger setting value
(12)
i_uUnitType
Module type
■Output label
No.
Variable name
Name
(13)
o_bENO
Execution status
(14)
o_bOK
Normal completion
(15)
o_bErr
Error completion
(16)
o_uErrId
Error code
Data type
Range
■FX5-4AD
Word [Unsigned]
When the logging
cycle unit setting is 0:
80 to 32767
When the logging
cycle unit setting is 1:
1 to 32767
When the logging
cycle unit setting is 2:
1 to 3600
■FX5-8AD
When the logging
cycle unit setting is 1
(current/voltage
range): 1 to 32767
When the logging
cycle unit setting is 1
(resistance
temperature
detector/
thermocouple
range): 40 to 32767
When the logging
cycle unit setting is 2:
1 to 3600
Word [Unsigned]
■FX5-4AD
0: s
1: ms
2: s
■FX5-8AD
1: ms
2: s
Word [Unsigned]
1 to 10000
Word [Unsigned]
0: Disable
1: Rise
2: Fall
3: Rise and fall
Word [Unsigned]
0 to 9999
Word [Signed]
-32768 to +32767
Word [Unsigned]
■FX5-4AD
0: FX5-4AD
■FX5-8AD
0: FX5-8AD
Data type
Default value
Bit
OFF
Bit
OFF
Bit
OFF
Word [Unsigned]
0
2 ANALOG INPUT MODULE, MULTIPLE INPUT MODULE FB
Description
Sets the interval of cycles at which data is stored.
Specifies the unit of cycles at which data is stored.
Specifies the number of data to be logged after a hold
trigger occurs by one point.
Sets the condition in which a level trigger is to be used.
Set 0 if using no lever trigger.
Specifies a buffer memory address to be monitored by
level trigger.
Sets the level at which a level trigger is generated.
Specifies a module type.
Description
ON: The execution command is ON.
OFF: The execution command is OFF.
The on state indicates that the setting of the logging
function parameters is completed.
The on state indicates that an error has occurred in the
FB.
The error code of an error occurred in the FB is stored.
2.3 M+Model_SetLoggingParam