Download Print this page

CAC / BDP KSACN0301AAA Owner's Manual page 7

Wired controller for ducted and cassette ductless systems

Advertisement

BLOW SETTING
S
BLOW Function: After the unit turns off, the water in
the indoor unit's evaporator automatically evaporates to
avoid mildew.
In the COOLING or DRY modes, press FUNCTION until the unit
enters the BLOW mode and then press ENTER/CANCEL to
activate the function.
NOTE:
When BLOW is activated and the user turns off the unit by pressing ON/OFF or with the remote controller, the indoor fan will run
at low speed for 2 minutes, and "BLOW" appears on the LCD. If BLOW is deactivated, the indoor fan turns off. The BLOW
function is unavailable in the FAN or HEATING mode.
OTHER FUNCTIONS
1. LOCK: Upon start−up, without malfunction or under the
unit's "OFF" state, press
seconds until the wired remote controller enters the LOCK
state and the LCD displays
together for 5 seconds to exit this function. Under the
LOCK function, all buttons are inactive.
2. Memory:
S
Memory Switchover: Under the unit's OFF state, press
MODE and
at the same time for 5 seconds to switch the
memory states between MEMORY ON and MEMORY
OFF. When this function is activated, MEMORY appears.
If this function is not set, the unit remains under the OFF
state after a power failure and the subsequent power
recovery.
S
Memory Recovery: If this function has been set for the
wired remote controller, the controller, after power failure,
resumes its original running state upon power recovery.
S
Memory Contents: ON/OFF, MODE, set temperature
set fan speed and LOCK function.
3. Temperature Sensor Selection: Under the unit's OFF
state, press both FUNCTION and TIMER for five seconds
to enter the commissioning status. Under this status, use
MODE to adjust the display in the temperature display area
to "00" and then adjust the temperature sensor option in the
timer display area with either
Fig. 15 - Blow mode
and
at the same time for 5
. Next, press
and
or
.
When the BLOW function is activated, press FUNCTION, under
the BLOW mode interface, then press ENTER/CANCEL to
cancel the function (see Fig. 15).
(1.) Indoor ambient temperature is sensed at the return
air inlet (01 in the timer display area).
(2.) Indoor ambient temperature is sensed at the wired
controller (02 in the timer display area).
(3.) Select the temperature sensor ar the return air inlet
under the COOLING, DRY, and FAN modes.
(4.) Select the temperature sensor at the wired controller
under the COOLING, DRY, and FAN modes and
select the temperature sensor at the return air inlet
under the HEATING and AUTO modes (04
displayed in the timer display area). The factory
default setting is #3.
After the setting, press ENTER/CANCEL to confirm and exit the
setting status.
NOTE: Users can use ON/OFF to exit the commissioning status
however the set data will not be kept.
NOTE: Under the commissioning status, if there is no operation
requested within 20 seconds after the last button was pressed, the
system reverts to the previous state without retaining the current data.
7

Advertisement

loading

Related Products for CAC / BDP KSACN0301AAA