Fujitsu AS*A09LKC Service Instructions Manual page 26

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for AS*A09LKC:
Table of Contents

Advertisement

Trouble shooting 2
INDOOR UNIT Error Method:
Serial Error
(Serial Forward Transfer Error)
Detective Actuators:
Indoor Unit Controller PCB
Forecast of Cause:
1. Connection failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
YES
YES
Check Point 2 : Check connection
Check any loose or removed connection line of
between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection condition in control unit.
(If there is loose connector, open cable or mis-wiring)
OK
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears
at outdoor unit terminal L - N.
OK
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal N - 3.
>> If it is abnormal, replace Controller PCB .
BLACK
L
N
WHITE
3
RED
Indicate or Display:
Refer to error code table.
Detective details:
When the indoor unit cannot properly receive the serial signal from
outdoor unit for 10 seconds or more.
2. External cause
3. Controller PCB failure
+
-
NO
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
02-04