8. COMPRESSOR CONTROL

1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table 10.
(Table 10 : Compressor Operation Frequency Range)
AS*A09LKC
AS*A12LKC
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the figure 10.
(Fig.10 : Compressor Control at Start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
AS*A09LKC
AS*A12LKC
(Time)
AS*A09LKC
AS*A12LKC
Cooling
Min
Max
22Hz
79Hz
18Hz
96Hz
Time
Time
Frequency
Frequency
70Hz
56Hz
Time
Time
80sec
60sec
80sec
60sec
Heating
Min
Max
22Hz
99Hz
18Hz
130Hz
Time
Time
Frequency
Frequency
82Hz
92Hz
74Hz
87Hz
Time
60sec
60sec
01-09
Dry
Min
Max
28Hz
37Hz
25Hz
33Hz
Time
Time
Frequency
96Hz
96Hz
97Hz
108Hz
Time
Time
180sec
60sec
180sec
60sec
Frequency
96Hz
119Hz
Time
60sec
60sec