5.3 Modbus
®
Modbus
connections to the XNX are made through a pluggable terminal block
®
on the Modbus® interface circuit board. A loop termination point (SW5) is
included on the Modbus® interface board to provide termination of the Modbus®
loop.
R
=120
T
TB-3 Modbus
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8
3-9
3-10
Use shorting jumper
supplied to maintain
connection during
service
Figure 25. XNX Modbus
XNX Universal Transmitter Quick Start Guide
250VAC 5A
24VDC 5A
NC
C
NO
NC
C
NO
NC
C
NO
supplied, disconnect at source
Figure 24. XNX relay option board and terminal block
Terminals 3-1 through 3-4 are provided to facilitate bus wiring;
there is no internal connection to other XNX circuitry. Terminal
3-1 is connected internally to 3-2. Similarly, terminal 3-3 is
connected to 3-4
S5 EOL Term
SW5 - Loop Termination
+
+
-
-
A
A
B
B
S
S
TB3 Modbus Connections
option board, terminal block, and jumper switch
®
TB3
TB4
TB3 Relay Connections
Warning: Power externally
prior to servicing
Relay Contact Ratings:
250 VAC 5 amps
24 VDC 5 amps
Use Jumper
to maintain
connection
during service
Relay
TB3
1
NC
2
C
3
NO
4
NC
5
C
6
NO
7
NC
8
C
9
NO
TB4
1
1
2
2
Modbus
®
TB3
1
+
2
+
3
-
4
-
5
A
6
A
7
B
8
B
9
S
10
S