York TCHE24 Technical Manual

York TCHE24 Technical Manual

Horizontal discharge split system air conditioners 14 seer – r-410a – 1 phase, 2, 3, 4 nominal tons
Hide thumbs Also See for TCHE24:

Advertisement

TECHNICAL GUIDE
HORIZONTAL DISCHARGE
SPLIT SYSTEM
AIR CONDITIONERS
14 SEER – R-410A – 1 PHASE
2, 3, 4 NOMINAL TONS
MODELS: TCHE24, 36, 48
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts warranty.
Standard 10-Years limited compressor warranty.
Extended 10-Years limited parts warranty when product is
registered online within 90 days of purchase for replacement
or closing for new home construction.
*Does not apply to 3-Phase models, or Internet sales.
See Limited Warranty certificate in User's Information Manual for details.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
FOR INSTALLATION IN ALL US REGIONS AND CANADA
Installation Allowed
®

DESCRIPTION

The 14 SEER TCHE Series condensing unit is the outdoor part
of a versatile system of air conditioning. Optimized for the new
14 SEER Regional Minimum Efficiency and the high EER
required in the Southwest US, these outdoor units are specifi-
cally designed to be matched with York indoor coils, furnaces,
and air handlers to provide a complete system solution.
These remarkably compact units require only minimal service
and airflow clearances, allowing them to be positioned as close
as six inches (6") from the wall. This design allows the unit to be
located virtually anywhere – on the ground, roof, balcony, or
mounted to an outside wall. When installation footprint is lim-
ited, these units can be stacked two-high using the approved
stacking kit.

FEATURES

• Performance - Optimized for the US DOE Southwest
Region and valid for installation in all US DOE Regions.
• Small Footprint - Compact "slim-line" design allows for easy
installation in tight spaces. Units can be stacked two-high
with approved stacking kit.
• QuietDrive™ System - The combination of a swept-wing
fan, rigid base pan, isolated compressor compartment, and
quiet scroll compressor reduce sound to as low as 70 dBA.
• Low Operating Sound Levels - The swept-wing condenser
fan in blow-through configuration provides for whisper-quiet
operation by allowing air to flow smoothly and efficiently
across the fan blades.
• Quality Condenser Coils - The coil is constructed of alumi-
num microchannel tubing and enhanced aluminum fins for
compact size and increased efficiency.
• Environmentally Friendly Refrigerant - The next genera-
tion refrigerant R-410A delivers environmentally friendly per-
formance with zero ozone depletion.
• Durable Cabinet - Heavy-gauge steel cabinet and tubular
base rails provide added support.
• Aesthetic Appearance - Powder paint "Champagne" color
provides an attractive retail finish.
• Agency Listed - Safety certified by CSA to UL 1995 / CSA
22.2. Performance certified to ANSI/AHRI Standard 210/240
in accordance with the Unitary Small Equipment certification
program.
• Other Features:
– Factory installed spun copper filter drier
– High pressure and low pressure switches
– Accumulator and crankcase heater in all sizes
– Up to 200' line set out of the box
– Zero lot line - only 6" minimum clearance from structure
5371951-YTG-A-0517

Advertisement

Table of Contents
loading

Summary of Contents for York TCHE24

  • Page 1: Description

    14 SEER Regional Minimum Efficiency and the high EER required in the Southwest US, these outdoor units are specifi- cally designed to be matched with York indoor coils, furnaces, and air handlers to provide a complete system solution. These remarkably compact units require only minimal service...
  • Page 2: Table Of Contents

    5371951-YTG-A-0517 LIST OF SECTIONS NOMENCLATURE DESCRIPTION ......... . 1 T = Factory Branded BRAND FEATURES .
  • Page 3: Physical And Electrical Data

    5371951-YTG-A-0517 PHYSICAL AND ELECTRICAL DATA TCHE24S41S1 TCHE36S41S1 TCHE48S41S1 MODEL Unit Supply Voltage 208-230V, 1 60Hz 187 to 252 Normal Voltage Range Minimum Circuit Ampacity 18.3 19.1 24.6 Max. Overcurrent Device Amps Min. Overcurrent Device Amps Type Scroll Scroll Scroll Compressor Amps Rated Load 13.5 14.1...
  • Page 4: System Charge For Various Matched Systems

    5371951-YTG-A-0517 SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS System Charge for Various Matched Systems Outdoor Unit TCHE24S41S1 TCHE36S41S1 TCHE48S41S1 Required TXV 3,4,5 Additional Charge, Oz Indoor Unit CF/CM/CU30(B,C,D) – – CF/CM/CU36(A,B,C,D) – – FC38C – – FC49D – – AP30B – –...
  • Page 5: Cooling Capacity - With Air Handler Coils

    5371951-YTG-A-0517 COOLING CAPACITY - With Air Handler Coils AIR HANDLER COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE24S41S AE30BX21 17.5 – 24.0 18.5 15.50 12.75 TCHE24S41S AE36BX21 17.5 – 24.0 18.7 15.75 13.00 TCHE24S41S AE36CX21 21.0 –...
  • Page 6: Cooling Capacity - Upflow, Downflow & Horizontal Furnaces And Coils (Coil Only Ratings)

    5371951-YTG-A-0517 COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings) COIL COOLING CFM RANGE NET MBH UNIT MODEL RATED (MIN.-MAX.) MODEL WIDTH SEER TOTAL SENS. TCHE24S41S CF/CM/CU30B 17.5 600 - 1000 24.0 17.5 14.00 12.20 TCHE24S41S CF/CM/CU30B 17.5 600 - 1000...
  • Page 7 5371951-YTG-A-0517 COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued) FURNACE COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE24S41S TM8X100C16MP11 21.0 CF/CM/CU30D 24.0 18.5 16.00 13.00 TCHE24S41S TM8X100C16MP11 21.0 CF/CM/CU36C 24.0 19.1 16.00 13.00 TCHE24S41S TM8X100C16MP11 21.0...
  • Page 8 5371951-YTG-A-0517 COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued) FURNACE COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE24S41S TM9V080C16MP11 21.0 CF/CM/CU30C 24.0 19.0 15.50 12.75 TCHE24S41S TM9V080C16MP11 21.0 CF/CM/CU30D 24.0 18.6 15.75 13.00 TCHE24S41S TM9V080C16MP11 21.0...
  • Page 9 5371951-YTG-A-0517 COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued) FURNACE COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE24S41S TMLX100C20MP11 21.0 CF/CM/CU36D 24.0 19.1 14.50 12.25 TCHE24S41S TMLX120C20MP11 21.0 CF/CM/CU30C 23.8 18.3 14.50 12.25 TCHE24S41S TMLX120C20MP11 21.0...
  • Page 10 5371951-YTG-A-0517 COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued) FURNACE COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE36S41S TM8V080C16MP11 21.0 FC38C 1200 35.6 27.0 15.10 12.50 TCHE36S41S TM8V100C16MP11 21.0 FC38C 1200 35.6 27.0 15.10 12.50 TCHE36S41S...
  • Page 11 5371951-YTG-A-0517 COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued) FURNACE COOLING UNIT COIL NET MBH RATED MODEL MODEL MODEL WIDTH SEER TOTAL SENS. TCHE48S41S TM8Y100C16MP11 21.0 FC49D 1400 46.0 34.0 14.75 12.25 TCHE48S41S TM8Y100C20MP11 21.0 FC49D 1425 46.5 34.6 15.10 12.50 TCHE48S41S...
  • Page 12: Applications And Accessories

    For optimum performance, these Outdoor Communicating Board Kit (S1-33102952310): Elec- outdoor units are fully compatible with the York Hx™ Touch- tronic control upgrade for standard AC & HP units to provide screen Thermostat (S1-THXU280*) available through Source1.
  • Page 13: Mechanical Specifications

    5371951-YTG-A-0517 MECHANICAL SPECIFICATIONS UNIT CONSTRUCTION • Units shall be shipped completely wired, piped and assem- MANUFACTURE AND CERTIFICATIONS bled. Wiring pigtails shall be provided for field control wiring • Units shall be manufactured in an ISO 9001 certified facility. connections. Service valves shall be provided for field refrig- •...
  • Page 14: Typical Installation

    5371951-YTG-A-0517 TYPICAL INSTALLATION THERMOSTAT WEATHERPROOF DISCONNECT SWITCH NEC CLASS 1 WIRING 6” CLEARANCE AROUND PERIMETER TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING TO INDOOR UNIT AIRFLOW DIRECTION NOTES: ALL OUTDOOR WIRING MUST BE WEATHERPROOF. CAN BE STACKED TWO-HIGH WITH APPROVED STACKING KIT. MINIMUM 18”...
  • Page 15: Performance Data - 2 Ton

    5371951-YTG-A-0517 PERFORMANCE DATA - 2 TON CONDENSER-ONLY DATA (OUTDOOR UNIT) Outdoor Ambient Temperature SATURATED SUCTION @ COMPRESSOR MODEL 55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 120 °F T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW 22.3 2.31 21.2 2.36 20.1 2.36 19.0 2.36 17.8 2.36 16.5 2.36 15.1 2.36 14.4 2.36 24.6 2.34 23.5 2.34 22.2 2.34 21.0 2.34 19.6 2.34 18.2 2.34 16.8 2.34 16.0 2.34 TCHE24S41S1...
  • Page 16 5371951-YTG-A-0517 FURNACE MULTIPLIERS - 2 TON (Continued) COIL MULTIPLIERS - 2 TON Furnaces Coil T.C. S.C. Air Handler Coil T.C. S.C. TM8X080C16MP11 CF/CM/CU36C 1.00 1.09 0.94 – CF/CM/CU30B 1.00 1.00 1.00 TM8X080C16MP11 CF/CM/CU36D 1.00 1.09 0.94 – CF/CM/CU30C 0.98 1.03 0.98 TM8X100C16MP11 CF/CM/CU30C...
  • Page 17 5371951-YTG-A-0517 FURNACE MULTIPLIERS - 2 TON (Continued) FURNACE MULTIPLIERS - 2 TON (Continued) Furnaces Coil T.C. S.C. Furnaces Coil T.C. S.C. TM9V080B12MP11 CF/CM/CU30B 1.00 1.05 0.96 TMLX100C20MP11 CF/CM/CU36D 1.00 1.09 1.00 TM9V080B12MP11 CF/CM/CU36B 1.00 1.09 0.96 TMLX120C20MP11 CF/CM/CU30C 0.99 1.04 0.99 TM9V080C16MP11 CF/CM/CU30C...
  • Page 18: Performance Data - 3 Ton

    5371951-YTG-A-0517 PERFORMANCE DATA - 3 TON CONDENSER-ONLY DATA (OUTDOOR UNIT) Outdoor Ambient Temperature SATURATED SUCTION @ COMPRESSOR MODEL 55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 120 °F T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW 33.3 3.24 31.8 3.24 30.2 3.24 28.6 3.24 26.9 3.24 25.0 3.24 23.0 3.24 21.9 3.24 36.6 3.22 35.0 3.22 33.3 3.22 31.6 3.22 29.7 3.22 27.7 3.22 25.5 3.22 24.4 3.22 TCHE36S41S1...
  • Page 19 5371951-YTG-A-0517 COIL MULTIPLIERS - 3 TON FURNACE MULTIPLIERS - 3 TON Air Handler Coil T.C. S.C. Furnaces Coil T.C. S.C. – FC38C 1.00 1.00 1.00 TM8V080C16MP11 FC38C 1.00 0.99 0.98 ME16CN21 FC38C 1.01 1.00 0.95 TM8V100C16MP11 FC38C 1.00 0.99 0.98 MVC16CN21 FC38C 1.01...
  • Page 20: Performance Data - 4 Ton

    5371951-YTG-A-0517 PERFORMANCE DATA - 4 TON CONDENSER-ONLY DATA (OUTDOOR UNIT) Outdoor Ambient Temperature SATURATED SUCTION @ COMPRESSOR MODEL 55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 120 °F T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW 45.1 4.13 42.9 4.22 40.7 4.22 38.5 4.22 36.2 4.22 33.7 4.22 31.1 4.22 29.8 4.22 49.5 4.20 47.0 4.20 44.7 4.20 42.3 4.20 39.9 4.20 37.2 4.20 34.4 4.20 33.0 4.20 TCHE48S41S1...
  • Page 21 5371951-YTG-A-0517 FURNACE MULTIPLIERS - 4 TON (Continued) COIL MULTIPLIERS - 4 TON Furnaces Coil T.C. S.C. Air Handler Coil T.C. S.C. TM9V120D20MP11 FC49D 1.00 1.00 0.97 – FC49D 1.00 1.00 1.00 TM9Y080C16MP11 FC49D 1.00 1.02 1.03 ME14DN21 FC49D 1.01 1.02 0.98 TM9Y100C16MP11 FC49D...
  • Page 22 NOTES Subject to change without notice. Published in U.S.A. 5371951-YTG-A-0517 Copyright © 2017 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Tche48Tche36

Table of Contents