Tripping Logic - ABB REB650 2.1 IEC Product Manual

Busbar protection, relion 650 series
Table of Contents

Advertisement

Busbar protection REB650 2.1 IEC
Product version: 2.1
Logic
Table 33. Tripping logic common 3-phase output SMPPTRC
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Evolving fault delay
Table 34. Number of SMPPTRC instances
Function
SMPPTRC
Table 35. Number of TMAGAPC instances
Function
TMAGAPC
Table 36. Number of ALMCALH instances
Function
ALMCALH
Table 37. Number of WRNCALH instances
Function
WRNCALH
Table 38. Number of INDCALH instances
Function
INDCALH
Table 39. Number of AND instances
Logic block
AND
40
M12380-1 v10
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
3 ms
6
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
3 ms
-
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
3 ms
-
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
3 ms
-
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v1
3 ms
108
Accuracy
-
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
Quantity with cycle time
3 ms
6
Quantity with cycle time
8 ms
6
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
5
Quantity with cycle time
8 ms
60
1MRK 505 362-BEN B
100 ms
-
100 ms
5
100 ms
5
100 ms
-
100 ms
160
ABB

Advertisement

Table of Contents
loading

Table of Contents