Single-, Two- Or Three-Pole Tripping - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 16
Logic
16.1.2.3
488
Other back-up functions are connected to the input TRINP_3P as described above for
three-pole tripping. A typical connection for a single-pole tripping scheme is shown in
figure 200.
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
Phase segregated trip A, B and C
from example line differential or
distance protection
Phase selection A, B and C from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide single pole trip
SMBRREC
To prepare 3 phase trip
for any trip signal
TR3P
To activate lockout for any trip
To reset lockout
ANSI05000545 V6 EN-US
Figure 200:
The trip logic function SMPPTRC (94) used for single-pole tripping
application

Single-, two- or three-pole tripping

The single-/two-/three-pole tripping mode provides single-pole tripping for single-
phase faults, two-pole tripping for two-phase faults and three-pole tripping for three-
phase faults. The operating mode is always used together with an autoreclosing scheme
with setting ARMode = 1/2/3 ph or ARMode = 1/2 Ph.
The functionality is very similar to the single-phase scheme described above. However,
in addition to the connections for single phase SMBRREC (79) must also be informed
that the trip is two phases by connecting the output TR2P to the input TR2P in the
SMBRREC (79) function.
OR
PREP3P
1MRK 511 401-UUS A
SMPPTRC (94)
TRIP
BLOCK
BLKLKOUT
TR_A
TRINP_3P
TR_B
TRINP_A
TR_C
TRINP_B
TR1P
TRINP_C
TR2P
PS_A
TR3P
PS_B
CLLKOUT
PS_C
BFI_3P
1PTRZ
BFI_A
1PTRGF
BFI_B
P3PTR
BFI_C
SETLKOUT
STN
RSTLKOUT
FW
CND
REV
ANSI05000545-6-en.vsdx
Bay control REC670 2.2 ANSI
Application manual
M14828-15 v5