Modbus Communications (continued)

RPM20 Variable List

Variable Name
Status Index
79
Room 1 Label
80 to 86
Room 2 Label
87 to 93
Anteroom Label
94 to 100
EXAMPLE of 06 Write Single Register function format:
This example changes the normal low face velocity alarm set point to 60 ft/min.
QUERY
Field Name
Slave Address
Function
Starting Address Hi
Starting Address Lo
Data Value (High)
Data Value (Low)
Error Check (CRC)
EXAMPLE of 03 Read Holding Registers function format:
This example reads the face velocity and current face velocity set point.
QUERY
Field Name
(Hex)
Slave Address
01
Function
03
Starting Address Hi
00
Starting Address Lo
00
No. Of Registers Hi
00
No. Of Registers Lo
02
Error Check (CRC)
--
®
Network/Modbus
Communications
Variable
Address
Read/Write
Read
Read
Read
Read
RESPONSE
(Hex)
Field Name
01
Slave Address
06
Function
00
Starting Address Hi
16
Starting Address Lo
00
Error Check (CRC)
3C
--
RESPONSE
Field Name
Slave Address
Function
Byte Count
Data Hi
Data Lo
Data Hi
Data Lo
Error Check (CRC)
Integer DDC system receives
1
Normal
2
Room 1 Negative Low Alarm
3
Room 1 Negative High Alarm
4
Room 1 Positive Low Alarm
5
Room 1 Positive High Alarm
6
Low Exhaust Alarm
7
Low Supply Alarm
8
Low Temperature Alarm
9
High Temperature Alarm
10
Low RH Alarm
11
High RH Alarm
12
Anteroom Negative Low Alarm
13
Anteroom Negative High Alarm
14
Anteroom Positive Low Alarm
15
Anteroom Positive High Alarm
16
Room 2 Negative Low Alarm
17
Room 2 Negative High Alarm
18
Room 2 Positive Low Alarm
19
Room 2 Positive High Alarm
20
Data Error
(Hex)
01
06
00
16
--
(Hex)
01
03
04
00
64 (100 ft/min)
00
64 (100 ft/min)
81