Sinclair SCV-50EA Service Manual page 86

Air-cooled mini chiller unit scv-xxea series
Table of Contents

Advertisement

Note: when the ambient temperature is less than 8℃, inlet water temperature and temperature of plate heat exchanger is less
than 2℃, crankcase heater of plate works. CP appears. If inlet water temperature and temperature of plate heat exchanger is
more than 7℃, crankcase heater stops working and CP code disappears.
CL malfunction: To low water temperature protection in heating mode for 10-16kW.
To low water temperature protection in heating mode.
Whether the 4-way valve switch can switch normally
Check whether the 4-way valve coil fall off and the valve body jammed.
Check whether 4-way valve coil and body jammed.
Pb malfunction: Anti-freeze protection
The actual measured temperature of outdoor water outlet temperature and plate heat
exchanger temperature is less than 3 ℃ in cooling mode. Water inlet temperature and
plate heat exchanger temperature is less than 5 ℃ in heating mode and waiting mode.
Check whether water inlet sensor and plate heat
exchanger is fall off or damaged.(especially when the
outdoor temperature is lower than 0℃)
Place temperature sensor to the related position or replace it.
Note:
1)
The actual measured temperature of outdoor water outlet temperature and plate heat exchanger temperature is less
than 3 ℃ in cooling mode, the compressor stops running. But the water pump continue operating. If the temperature is
℃, Pb code disappears.
more than 8
2)
The actual measured temperature of outdoor water inlet temperature and plate heat exchanger temperature is less
than 8
in waiting state, water pump works. The actual measured temperature of outdoor water inlet temperature and
plate heat exchanger temperature is less than 5
normal.
LED displays CL
NO
NO
YES
Replace 4-way valve
LED displays Pb
Anti-freeze protection
NO
YES
Determine the location again.
YES
Whether the thermometer bulb of water
outlet and inlet location are right.
YES
Plug
again
NO
Replace main PCB
NO
Replace main PCB.
, the unit enter heating mode in force. Compressor works too. This is
84
YES
NO
well
Replace main
PCB
YES
Normal
protection
system