Installation Requirements - Siemens SIRIUS 3RW30 Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW30:
Table of Contents

Advertisement

Installation
7.1 Installing the soft starter
Direct mounting
The term "direct mounting" is used if the top clearance b described in chapter Mounting
dimensions, clearances, and assembly type [Page 54] is not complied with, e.g. if the soft
starter is mounted directly on a motor starter protector (e.g. 3RV2) using a link module (e.g.
3RV29).
NOTICE
The permissible switching frequency values can vary according to the selected assembly
type. For information about factors and how to determine the new switching frequency, refer
to chapter Configuration [Page 73].
7.1.5

Installation requirements

Degree of protection IP00
The SIRIUS 3RW30 / 3RW40 soft starters conform to the IP00 degree of protection.
The devices must be installed in control cabinets with the IP54 degree of protection (pollution
degree 2), taking account of the ambient conditions.
Make sure no liquids, dust, or conductive objects can get inside the soft starter. The soft
starter produces waste heat (power loss) while it is operating (refer to chapter Technical data
[Page 121]).
CAUTION
Provide adequate cooling at the place of installation to prevent the switching device from
overheating.
56
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw40

Table of Contents