Reparameterizing the ON / RUN output
A: Control voltage is present and the soft starter is in the normal, fault-free position:
The DEVICE LED is continuously lit (green) while the STATE / BYPASSED and FAILURE
LEDs are off.
The AUTO LED indicates the color of the set RESET mode.
B: Start programming:
(On the 3RW40 2 device, remove the RESET MODE cover as shown in chapter Setting the
RESET MODE [Page 113].) Press the RESET MODE button (2) for longer than 2 s until the
DEVICE LED (3) flickers (green). Hold the RESET MODE button (2) pressed down.
C: Simultaneously press the RESET / TEST button (1) for longer than 1 s until the DEVICE
LED (3) lights up (red). The active mode set at the ON / RUN output is indicated by the STATE
/ BYPASSED / FAILURE LED (4):
STATE / BYPASSED / FAILURE LED (4) flashes (green): ON mode (factory setting).
STATE / BYPASSED / FAILURE LED (4) flickers (green): RUN mode.
D: Change the mode:
Press the RESET MODE button (2) briefly. By pressing this button, you change the mode at
the output, and the new mode is indicated by the STATE / BYPASSED / FAILURE LED (4):
STATE / BYPASSED / FAILURE LED (4) flickers (green): RUN mode is set.
STATE / BYPASSED / FAILURE LED (4) flashes (green): ON mode is set.
E: Exit programming and save the settings:
Press the RESET / TEST MODE button (1) for longer than 1 s until the DEVICE LED (3) lights
up (green).
The LEDs indicate the following states again if the output was successfully parameterized:
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
Commissioning
12.9 Functions of the outputs
111