CONTROLS SETUP

Controlling the Indoor Unit
The method and configuration of controlling the indoor unit will vary according to system requirements.
• It is possible to control up to 16 indoor units with one wired remote controller (Group Control). Master indoor unit determines how Slave
units operate.
• Set only one indoor unit to Master, set the others to Slave. After setting Group Control, turn off the power, and then turn it back on after one
(1) minute. To verify indoor units have been set to Group Control, Master indoor unit will beep once, each Slave indoor unit will beep five (5)
times.
• This indoor unit can be connected in a control group with any other types of LG indoor units.
It is possible to use a wireless remote controller at the same time as the wall controller.
• It is possible to connect a Dry Contact and Central controller at the same time (Master indoor unit only). Some Wired Remote Controllers,
however, can't operate when both Dry Contact and Central controller are connected.
• A Central controller can control all indoor units in a group by controlling the master unit of the group. (Set the address of the master indoor
unit first.)
• Slave indoor units cannot be individually controlled by the Central controller. The Wired Remote Controller will display indoor unit(s)
error(s).
DIP Switch Settings
Refer to Figure 18. If the indoor unit is a master, set switch 3 of the indoor unit' s DIP switch to Off. If the indoor unit is a slave, set switch 3
of the indoor unit's DIP switch to On. To ensure the remaining switches are set correctly, refer to the appropriate unit's DIP switch settings in
the wiring section of this manual.
Master Setting
DIP Switch No. 3 is OFF
*For Gen 4 Multi V floor standing indoor units, DIP switches 1, 2, 6 through 8 must be set to OFF. These DIP switches are
used for other models.
**To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V IV, Multi V Wa-
ter IV, Multi V S Engineering Manual for additional information.
34
Figure 18: Master / Slave Indoor Unit Settings.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Slave Setting
DIP Switch No. 3 is ON