master is capable of sending new parameter telegrams. In some older master
systems, however, the system needs to be rebooted in this case, leading to an
interruption of the online-download. Modern master systems like Symphony
CMC60 from ABB provide the required functionality and are, therefore,
perfectly suited for online-parameterization.
Uninterrupted parameter download in accordance with the PROFIBUS
specifications requires that the slave is NOT working in DPV1-mode, i.e.
there is no non-cyclic communication with a Class_1 master. All systems
acting as a Class_2 master to access DPV1 communication and capable of
sending a new parameter telegram in online mode permit online-
parameterization.
Please refer to the user documentation of the PROFIBUS master for details
about how to perform online-parameterization.
Reaction in case of erroneous parameter telegrams
To comply with the PROFIBUS specification, the DataExchange state must
be left when a negative parameter telegram acknowledgement occurs.
Therefore, S900 always acknowledges the telegram with a positive response,
even if individual module parameters were identified as erroneous. The errors
are then communicated to the operator by a diagnostic message.
Modules that receive invalid new parameters retain their previous parameters.
This ensures continuous operation of all modules that are not directly affected
by the error.

Cyclic data exchange

I/O data transmission

Measuring value status
A status bit can be assigned to every measuring value, identifying it as valid
(status bit = 0) or invalid (status bit = 1). If a measuring value is "invalid", the
3BDD010422R0101
Communication Interface for PROFIBUS DP, CI920
I/O System S900
27