Supported I/O Modules - ABB S900 Manual

Table of Contents

Advertisement

I/O System S900
Communication Interface for PROFIBUS DP, CI920
every 20 ms. These times are independent of the cycle time specified for the
external fieldbus.
Output data
The transmission of output data is triggered by events. When an output data
telegram is received via the fieldbus, all data are transmitted synchronously to
the respective I/O modules.
I/O module monitoring
The connected I/O modules are monitored cyclically. When a module is not
found, a diagnostic messages is generated. For the input modules, the defined
default value is transmitted instead of the measured value. The default valid is
marked as invalid.

Supported I/O Modules

Type
Digital Input / Output
DO910
DX910
Analog Input / Output
AI910
AI930
AI931
AO910
AO920
AO930
Temperature
AI950
Counter / Frequency
DP910
12
Table 2-1 Supported I/O - modules
Description
Digital output, 4 x 1 channels (Solenoid driver)
Digital input / output, 1 x 8 channels
Analog input, 1 x 4 channels, active
Analog input, 1 x 4 channels, active, HART
Analog input, 1 x 4 channels, active, HART
Analog output, 1 x 4 channels
Analog output, 4 x 1 channels (isolated)
Analog output, 1 x 4 channels, HART
Temperature input, 4 x 1 channels, resistor
and thermocouple
Frequency input and counter, 2 blocks
CI920 Version (Softw.)
Prm.-M. 1
Prm.-M. 2
> 1.0.x
> 1.2.x
> 1.0.x
> 1.2.x
> 1.2.x
> 1.2.x
> 1.0.x
> 1.2.x
> 1.2.x
> 1.2.x
> 1.4.x
> 1.4.x
> 1.0.x
> 1.2.x
> 1.2.x
> 1.4.x.
> 1.2.x
> 1.4.x
> 1.4.x
> 1.4.x
3BDD010422R0101