I/O System S900
Communication Interface for PROFIBUS DP, CI920
simulate (force) the S900 inputs/outputs
configure the connected HART field devices
Selective loading of configuration data and parameter settings while the
system is running allows you to
modify specific parameters of the communication interface or of
individual I/O modules
add more S900 stations
add, remove or replace S900 I/O modules.
All I/O modules whose parameter settings and configuration data are not
changed continue cyclic communication. As long as the master is
downloading data, all S900 outputs hold their states. Examples for modern
master systems meeting the requirements stated above are:
ABB AC800F
ABB Symphony CMC60-2 / CMC70
ABB AC800M

System Limits

Number of PROFIBUS stations

Up to 127 can be addressed within a PROFIBUS network. This number
includes the PROFIBUS – master. Up to 32 stations can be connected to a
PROFIBUS DP segment. When using repeaters, one can separate the network
into several segments. Using the intrinsically safe PROFIBUS - DP, up to 10
stations can be connected to each segment.
The transmission rate and the permissible cable length specified for the
segment must be observed. For example, a cable length of 400 m (1314ft) is
permissible for a network with a transmission rate of 500 kbaud. Longer
cables are possible when using fiber optic cables.

Number of I/O Modules

S900 can handle up to 16 I/O modules. They can be configured via the
PROFIBUS, and their parameters can be defined individually for every
14
3BDD010422R0101